THE JAMMU AND KASHMIR ELECTRICITY RULES, 1978 [SRO 396]
PREAMBLE
In exercise of the powers conferred by section 36
of the Jammu and Kashmir Electricity Act, Svt. 1997 the Government hereby makes
the following rules, namely:-
CHAPTER
I PRELIMINARY
Rule - 1. Short title and commencement.
(i) These rules may be
called the Jammu and Kashmir Electricity Rules, 1978.
(ii) These shall come into
force at once.
Rule - 2. Definitions.
(1) In these rules,
unless the context otherwise requires,-
(a) "Act" means
the Jammu and Kashmir Electricity Act, Svt. 1997;
(b) "accessible"
means within physical reach without the use of appliance or special efforts;
(c) "ampere"
mean a unit of electric current and is the unvarying electric current which
when passed through a solution of nitrate of silver in water, in accordance
with the specification set out in Annexure I, deposits silver at the rate of
0.001118 of a gramme per second. The aforesaid unit is equivalent to the
current which, in passing through the suspended coil of wire forming part of
the instrument marked, "Government of India Ampere Standard Verified"
when the suspended coil is in its sighted position, exerts a force which is
exactly balanced by the force exerted by gravity in Calcutta on the counter
balancing iridio-platinum Weight of the said instrument;
(d) "Annexure"
means an Annexure to these rules;
(e) "apparatus"
means electrical apparatus find include all machine fittings, accessories and
appliances in which conductors are used;
(f) "Bear"
means not covered with insulating material;
(g) "Cable"
means a length of insulated single conductor (Solid or Standard) or of two or
more such conductors, each provided with its own insulation, which are laid up
together. Such insulated conductor or conductors may or may not be provided with
an overall mechanical protective covering;
(h) "Flexible
Cable" means a cable consisting of one or more core each formed of a group
of wires, the diameter and the physical properties of the wires and the
insulating material being such as to afford flexibility;
(i) "Circuit"
means an arrangement of a conductor or conductors for the purpose of conveying
energy and forming a system or a branch of a system;
(j) "Circuit
breaker" means a device, capable of making and breaking the circuit under
all conditions, and unless otherwise specified, so designed as to break the
current automatically under abnormal conditions;
(k) "Concentric
Cable" means a composite cable comprising an inner conductor which is
insulated and one or more outer conductors which are insulated from one another
and are disposed over the insulation of, and more or less around the inner
conductor;
(l) "Conductor"
means any wire, cable, bar, tube, rail or plates used for conducting energy and
so arranged as to be electrically to a system; (m) "Conduit" means
rigid or flexible metallic tubing or mechanically strong and fire resisting
non-metallic tubing into which a cable or cables may be drawn for the purpose
of affording; it or then mechanical protection;
(m) "Covered with
insulating material" means adequately covered with insulating material of
such quality and thickness to prevent danger;
(n) "Cut-out"
means any appliance for automatically interrupting the transmission of energy
through any conductor when the current rises above a predetermined amount, and
shall also include fusible cut-out;
(o) "Danger"
means danger to health or danger to life or any part of body from shock, burn,
or other injury to persons or property, or from fire or explosion, attendant
upon the generation, transmission, transformation, conversion, distribution or use
of energy;
(p) "Dead"
means at or about earth potential and disconnected from any live system;
(q) Provided that
apparatus separated from a live conductor by a spark gap shall not be deemed to
be "dead";
Note.
The term "dead" is used only with reference to current carrying parts
when these parts are not live.
(r) "Earthed"
or "Connected with earth" means connected with the general mass of
earth in such manner as to ensure at all times an immediate discharge of energy
without danger;
(s) "earthing
system" means an electrical system in which all the conductors are
earthed;
(t) "enclosed
Sub-Station" means any premises or enclosure or part thereof being large
enough to admit the entrance of a person after the apparatus therein is in
position, containing apparatus for transforming or converting the energy to or
from a voltage at or above medium voltage (other than transforming or
converting solely for operation of switch-gear or instrument) with or without
any other apparatus for switching, controlling or otherwise regulating the energy
and includes the apparatus therein;
(u) "enclosed switch
station" means any premises or enclosure or part thereof, being large
enough to admit the entrance of a person after the apparatus therein is in
position, containing apparatus for switching, controlling or otherwise
regulating energy at or above medium voltage but not for transforming or
converting energy (other than for transforming or converting solely for
operation of switch gear or instruments), and includes the apparatus therein;
(v) "guarded"
means covered, shielded, fenced or otherwise protected by means of suitable
casings, barrier and rails or metal screens to remove the possibility of
dangerous contact or approach by persons or objects to a point of danger;
(w) "Government"
means Government of Jammu and Kashmir;
(x) "Hand-held
portable apparatus" means an apparatus which is so designed as to be
capable of being held in the hands and moved while connected to supply of
electricity;
(y) "Inspector"
means an Electrical Inspector appointed under section 35 of the Act;
(z) "Insulation"
means any composite electrical unit used for the purpose of generating,
transforming, transmitting, converting, distributing or utilizing energy;
(aa) "intrinsically Safe" as
applied to apparatus or associated circuits shall denote that any sparking;
that may occur in normal working is incapable of causing explosion of
inflammable gas or vapour;
(ab) "Lightning arrestor" means a
device which has the property of diverting to earth any electrical surges of
excessively high amplitude applied to its terminals and is capable of
interrupting follow current if present and restoring itself thereafter to its
original operating conditions;
(am) "Linked switch" means a switch
with all the poles mechanically linked so as to operate simultaneously;
(an) "Live" means electrically
charged;
(ao) "Metallic covering" means
mechanically strong metal covering surrounding one or more conductors;
(ap) "Neutral conductor" means that
conductor of a multiwire system, the voltage of which is normally midway
between the voltages of the other conductors of the system;
(aq) "Non-licensee" means a person
generating, supplying, transmitting or using energy to whom any of the
provisions of part III of the Act apply;
(ah) "Occupier" means the owner or
person in occupation of the premises where energy is used or proposed to be
used;
(ai) "Ohm" means a unit of electric
resistance and is the resistance offered to any unvarying electric current by a
column of mercury at the temperature of melting ice 14.4521 grammes in mass of
a uniform cross-sectional area and of a length of 106.3 centimeters the
aforesaid unit is represented by the resistance between the terminals of the
instrument marked "Government of India Ohm Standard Verified" to the
passage of an electric current when the coil of wire, forming part of the
aforesaid instrument and connected to the aforesaid terminals is in all parts
at a temperature of 300°C;
(aj) "Open sparking" means sparking
which owing to the lack of adequate provision for preventing the ignition of
inflammable gas external to the apparatus would ignite such inflammable gas;
(ak) "Overhead line" means any
electric supply line which is placed above ground and in the open space but
excluding live rails of a traction system;
(al) "Inspector of mines",
"Owner", "Agent" and "manager of a Mine" shall
have the same meanings as are assigned to them in the Mines Act, 1952;
(am) "Portable apparatus" means an
apparatus which is so designed as to be capable of being moved while in
operation;
(an) "Portable hand lamp" means a
portable light fitting provided with suitable hands, guard and flexible cord
connected to a plug;
(ao) "Section" means a section of
the Act';
(ap) "Span" means the horizontal
distance between the two adjacent supporting points of an over-head conductor;
(aq) "Street box" means a totally
enclosed structure, either above or below ground containing apparatus for
transforming switching controlling or otherwise regulating energy;
(ar) "Supplier" means a licensee, a
non-licensee or any other supplier of energy;
(as) "Switch" means a manually
operated device for opening and closing or for changing the connection of a
circuit;
(at) "Switch gear" shall denote
switches, circuit breakers, cut-outs ant other apparatus used for the
operation, regulation and control of circuits;
(au) "System" means an electrical
system in which all the conductors and apparatus are electrically connected to
a common source of electric supply;
(av) "Transportable apparatus"
means an apparatus which is operated in a fixed position but which is so
designed as to be capable of being moved readily from one place to another;
(aw) "Volt" means a unit of
electro-motive force and is the electric pressure which, when steadily apply to
a conductor, the resistance of which is one ohm, will produce a current of one
ampere;
(ax) "Voltage" means the difference
of electric potential measured in volts between any two conductors or between
any part of either conductor and the earth as measured by a suitable voltmeter
and is said to be:
(i) "low" where
the voltage does not exceed 250 volts under normal conditions subject, however,
to the percentage variation allowed by these rules;
(ii) "Medium"
where the voltage does not exceed 650 volts under normal conditions subject,
however, to the percentage variation allowed by these rules;
(iii) "High"
where the voltage does not exceed 33,000 volts under normal conditions subject,
however, to the percentage variation allowed by these: rules;
(iv) "Extra
high" where the voltage exceeds 33,000 volts under normal conditions
subject, however, to the percentage variation allowed by these rules;
(ay) "use of energy" means the
conversion of electrical energy into mechanical and chemical energy, heat or
light, for the purposes of providing mechanical energy, electrolysis heat or
light;
(az) "Load" includes use of energy
by lighting, fans and
(aaa) "Licensed contractor" means a
person or a firm licensed under these rules to carry out wiring work in
consumers, premises.
(2) All other words and
expressions used herein and not defined shall have the same meanings
respectively assigned to them in the Act.
Rule - 3. Authorisation
(1) A supplier or a
consumer, or the owner, agent or manager of a mine or the agent of any company
operating in an oil-field or the owner of a drilled well in an oil-field or a
contractor for the time being under contract with a supplier or a consumer to
carry out duties incidental to the generation, transformation, transmission,
conversion, distribution, or use of energy may authorise any person for the
purpose of any or all of the following namely: -
NP/Sub-rule
(2) of rule 36, clause (a) of sub-rule (1) of rule 51, clause (a) of sub-rule
(1) and clause (e) of sub-rule (2) of rule 64, sub-rule (2) of rule 110,
sub-rule (1) and (4) of rule 121, sub-rule (4) of rule 123, rule 124 and
sub-rule (8) of rule 125.
(2) No person shall be
authorised under sub-rule (1) unless he is competent to perform the duties
specified in the rules for the purpose of which he is authorised.
(3) No person shall be
deemed to be authorised under sub-rule (1) unless his name has been entered in
a list maintained at the office or premises of the person authorising him, and
giving the purpose for whom such person is authorized and entry has been
attested by the authorised person and the person authorising him.
(4) Every list maintained
under sub-rule (3) shall be produced before the Inspector when required.
CHAPTER II INSPECTORS
Rule - 4.Qualification of Inspectors.
No
person shall be appointed to be an Inspector unless-
(a) He possesses degree
or diploma in Electrical Engineering from a recognised University or college,
or qualifications equivalent to such degree or diploma; and
(b) He has been regularly
engaged for a period of at least seven years in the practice of Electrical
Engineering of which not less than two years have been spent in an Electrical
or Mechanical Engineering workshop or generation, transmission or distribution
of Electricity or in the administration of the Act and the rules made
thereunder.
Rule - 5.Functions of Inspectors.
(1) Subject to the
provisions of the Act the Inspectors shall discharge the following functions,
namely:-
(i) enforcement of
Electricity rules;
(ii) adjudication of
disputes between the supplier and the consumer;
(iii) investigation into
Electrical Accidents;
(iv) inspections of all
new Electrical Installations before energisation;
(v) periodical inspection
of existing Electrical Installations;
(vi) registration of
wiring contractors;
(vii) grant of competency
certificates to Electrical Supervisors.
(2) Any Inspector may
(i) enter, inspect and
examine any place, carriage or vessel in which he has reason to believe that
there is any appliance or apparatus used in the generation, transmission,
transformation, conversion, distribution or use of energy and may carryout
tests therein.
(ii) Every supplier,
consumer, owner and occupier shall afford at all times all reasonable
facilities to any such Inspector to make such examination and tests as may be
necessary to satisfy himself as to the due observance of the provisions of the
Act, the terms of the licence (if any) and these rules.
(iii) Every supplier and
every owner of a generating station or of a high or extra-high voltage
installation shall, if require so to do by an Inspector, provide reasonable
means for canning out all tests prescribed by or under the Act, of the
appliance or apparatus used for the supply or use of energy by him as the case
may be.
(iv) An Inspector may
serve an order in the form set out in Annexure IX, upon any supplier, consumer,
owner or occupier calling upon him to comply with any specified rule and the
person so served shall thereupon comply with the order within the period named
therein, and shall report in writing to the Inspector when the order is
complied with:
Provided
that, if within the period specified in the aforesaid order an appeal is filed
against the order the appellate authority may suspend its operation pending the
decision of the appeal.
Rule - 6.Appeals.
(1) An appeal against an
order served under clause (iv) sub-rule(4) of rule 5, shall lie-
(a) if the order is served
by an Assistant Electrical Inspector to the Electrical Inspector;
(b) if the order is
served by an Inspector, to the Chief Electrical Inspector.
(2) In the case of an
order of an Inspector on an appeal preferred to him under clause (a) of
sub-rule (1) a further appeal shall lie to the Chief Electrical Inspector.
(3) In the case of an
order of the Chief Electrical Inspector, an appeal shall lie to the Government.
(4) Every appeal shall be
in writing, shall be accompanied by a copy of the order appealed against, and shall
be presented within three months from the date of which such order has been
served or delivered.
[1]Note. [For
purpose of sub-rule (1) (Assistant Electrical Inspector), (Electrical
Inspector) and (Chief Electrical Inspector) shall mean (Asstt. Executive
Engineer/Assistant Engineer (Electric) of Inspection Wing of Power Development
Department], (Executive Engineer) of Inspection Wing and (Superintending
Engineer, Inspections) respectively.]
Rule - 7.Amount of fees.
(1) The fees set out in
Annexure II shall be payable in respect of the services therein mentioned where
the tests are carried out by comparison with the Government of India standards
referred to in sub-rule (1) of rule 2.
(2) The Government may
levy such fees for testing and inspection and generally for the services of
Inspectors, as it may from time to time by general or special order, direct,
and may, if thinks fit, remit any fee or any portion thereof.
Rule - 8.Incidence of fees recoverable in the cases of dispute.
When
an Inspector is called in to decide any difference or dispute and where a fee
for such services is recoverable, the Inspector shall decide by whom such fee
shall be payable.
Rule - 9.Submission of records.
An
Inspector may require a supplier or an owner to submit to him for examination
any records of tests made in connection with his works and he shall comply with
such requisition. Similarly, a supplier or an owner may require the Inspector
to submit to him for examination any records of tests made by the Inspector in
connection with his works and the Inspector shall comply with such requisition.
Rule - 10.Lists of consumers.
An
Inspector may require a supplier to submit to him a list of all persons
supplied with energy by him, of the addresses at which such energy is supplied,
the month of connecting services, the voltage of supply, the connected load,
the purpose of supply and the name of contractor carrying out the Installation
work and the supplier shall comply with such requisition.
CHAPTER
III LICENCE
Rule - 11.Application for licence.
(1) Every application for
a licence shall be signed by or on behalf of the applicant and addressed to
such officer as the Government may designate in this behalf and it shall be
accompanied by:—
(a) six copies, in print,
of the draft licence as proposed by the applicant, with the name and address of
the applicant and of his agent (if any), printed on the outside of the draft;
(b) three copies each
singed by the applicant, of maps of the proposed area of the supply and of the
streets or roads in which the supply of energy is to be compulsory, which shall
be so marked or coloured as to define any portion of such area and streets or
roads which are under the administrative control of any local authority and
shall be on a scale-
(i) of not less than six
inches to a mile; or
(ii) if no such maps are
available, of not less than that of the largest scale ordnance map available;
or
(iii) on such other scales
as may be approved by the Government;
(c) a list of any local
authorities invested with the administration of any portion of the area of
supply;
(d) an approximate
statement describing the land which the applicant proposes to acquire for the
purpose of the licence under the provisions of the State Land Acquisition Act,
1990;
(e) an approximate
statement of the Capital proposed to be expended in connection with the
undertaking and such other particulars as the Government may require;
(f) if the applicant is a
company which is registered under any of the enactments relating to companies
for the time being in force in the State or is a corporation by an Act of the
legislature, a copy of the Memorandum and Articles of Association; and
(g) a treasury receipt
for such fee not exceeding fifteen thousand rupees, as the Government may
require, paid into a Government treasury, unless such fee is remitted, wholly
or in part, by a general or special order of Government.
(2) If the application
for a licence is rejected or if a licence is revoked under sub-section (1) of
section 4 of the Act as to the whole or any part of the area of supply, the
Government may at its discretion refund, wholly or in a part, the fee referred
to in clause (g) of sub-rule
Rule - 12.Copies of maps and draft licence for public inspection.
The
applicant shall deposit at his own office and of his agent, if any, and at the
office of every local authority invested with the administration of any portion
of the proposed area of supply—
(a) copies of the maps
referred to in clause (b) of sub-rule (1) of rule 11 for public inspection; and
(b) a sufficient number
of copies of the draft licence to be furnished to all persons applying for them
at a price not exceeding rupees five per copy.
Rule - 13.Contents of draft licence.
The
draft licence shall contain the following particulars:—
(a) a short title
descriptive of the proposed undertaking together with the address and
description of the applicant or in the case of a firm, the names of all
directors or partners of the firm;
(b) a statement of the
boundaries of the proposed area of supply;
(c) if the generating
station is situated or is to be situated outside the area of supply or if any
intervening area not included in the area of supply is to be crossed, a list of
the streets not included in the area of supply along or across which electric
supply lines are to be laid down, or placed;
(d) the proposed limits
within which and the conditions under which the supply of energy is to be
compulsory or permissive, the nature and amount of the supply (if limited) and
the like;
(e) a list of the streets
(if any) which are repairable neither by the Central or the State Government,
nor by a local authority and of the railways and tramways (if any) the sod or
the pavement of which the applicant seeks powers to open or break up, and the
names of the person or designations of authorities by whom such streets are
repairable or who are for the time being entitled to work such railways or
tramways;
(f) the proposed periods
after which the right to purchase is to take effect;
(g) a statement of any
special term or purchase or orders proposed to be made under section 9 of the
Act; and
(h) any proposed modification
of the schedule to the Act to be made under clause (e) of sub-section (2) of
section 3.
Rule - 14.Form of draft licence.
The
form of draft licence contained in Annexure III may, with such variation as the
circumstances of each case require, be used for the purposes of rules 11 and 13
and if used, shall be sufficient.
Rule - 15.Advertisement of application and contents thereof.
(1) The applicant shall
within fourteen days from the submission of the application under rule 11,
publish notice of his application by public advertisement, and such
advertisement shall publish such particulars as the Government may specify.
(2) The advertisement
shall be headed by short title corresponding to that given at the head of the
draft licence and shall give the addresses of the offices at which, under rule
12, copies of maps therein referred to may be inspected and the copies of draft
licence perused or purchased and shall state that every local authority,
company or person, desirous of making any representation with reference to the
application to the Government, may do so by letter addressed to such officer as
the Government may designate in this behalf, within three months of the date of
issue of the first advertisement.
(3) The advertisement
shall be inserted by the applicant in at least two successive issues of such
newspaper as the Government having regard to its circulation among persons
likely to be interested, may direct, and in the absence of any such direction
in at least two successive issues of any newspaper published within the
proposed area of supply or if there is no such newspaper, in any newspaper
published within the State.
(4) The applicant shall
send a copy of each of the two successive issues of the newspaper containing
the advertisement to such officer as the Government may designate in this
behalf as soon as the second issue has appeared and the Government shall
publish the advertisement at least once in the Government Gazette within six
weeks from the date of the first advertisement published under sub-rule (3):
Provided
that any failure or delay on the part of the Government in publishing the
advertisement shall not of itself preclude the grant of a licence.
Rule - 16.Amendment of draft licence.
Any
person who desire to have any amendment made in the draft licence shall deliver
a statement of the amendment to the applicant and to such officer as the State
Government may designate in this behalf within the time allowed under sub-rule
(2) of rule 15 for the submission of representations referring to the
application.
Rule - 17.Local Inquries.
If
any person locally interested objects to the grant of a licence applied for
under the Act, the Government shall, if either the applicant or the objector so
desires, cause a local inquiry to be held of which the notice in writing shall
be given to both the applicant and the objector:
Provided
that the Government may refuse such an inquiry if in its opinion the objection
is of a trifling or vexatious nature.
Rule - 18.Approval of draft licence.
When
the Government has approved a draft licence, either in its original form or in
a modified form, such officer as the Government may designate in this behalf
shall inform the applicant of such approval and of the form in which is
proposed to grant the licence.
Rule - 19.Notification of grant of licence.
On
receiving an intimation in writing from the applicant that he is willing to
accept a licence in the form approved by the Government, the Government shall
publish the licence within two months by notification in the Government Gazette
together with a statement that it has been granted.
Rule - 20.Date of commencement of licence.
The
date of notification under rule 19 shall be deemed to be the date of
commencement of licence .
Rule - 21.Deposit of maps.
When
a licence has been granted, three sets of maps showing as regards such licence,
the particulars specified in clause (b) of sub-rule (1) of rule 11 shall be
signed and dated to correspond with the date of the notification of the grant
of the licence by such officer as the Government may designate in this behalf.
One set of such maps shall be retained as the deposited maps by the said
Officer and of the remaining two sets, one shall be furnished to the Jammu and
Kashmir State Electricity Board and the other to the licensee.
Rule - 22.Deposit of printed copies.
(1) Every person who is
granted a licence, shall within thirty days of the grant thereof:
(a) have adequate number
of copies of the licence printed;
(b) have adequate number
of maps prepared showing the area of supply and the compulsory areas specified
in the licence;
(c) arrange to exhibit a
copy of such licence and maps for public inspection at all reasonable times at
his head office, his local offices (if any), and at the office of every local
authority within the area of supply.
(2) Every such licensee
shall, within the aforesaid period of thirty days supply free of charge one
copy of the licence and the relevant maps to every local authority within the
area of supply and shall also make necessary arrangement for the sale of
printed copies of the licence to all persons applying for the same, at a price
not exceeding rupees five per copy.
Rule - 23.Application for written consent of Government in certain cases.
If
a licensee desires the written consent of the Government under sub-section (5)
of section 11 to enable him to open or break up the soil or pavement of any
street (which is repairable neither by the Central or the State Government nor
by a local authority) or any railway or tramway, he shall apply for such
consent in writing to such officer as the Government may designate in this
behalf and shall describe accurately the street, railways or tramway, which he
seeks power to open or break up and the names of the person or designations of
the authorities by whom such street is repairable or who are for the time being
entitled to work such railway or tramway, and the extent to which he proposes
to open or break up the same.
Rule - 24.Amendment of licence.
(1) If a licensee desires
that any alterations or amendments should be made in the terms and conditions
of his licence under clause (b) of sub-section (3) of section 4 of the Act, he
shall submit a written application to the officer designated by the Government
under rule 11 and shall within 14 days from the submission of the application
publish notice of his application by public advertisement; and the provisions
of sub-rules (2), (3) and (4) of rule 15 shall apply to such publication.
(2) The Government shall
within six months of the date of submission of the application, either approve
of the alterations or amendments in the form proposed by the licensee or in any
other modified form which he accepts, or rejects them when the Government has
approved of the alterations or amendments either in the form proposed by the
licensee or in any other modified form which he accepts, it shall notify the
alteration or amendments so approved, in the Government Gazette.
Rule - 25.Sale of Plans.
Copies
of plans or sections such as are referred to in clause XV of the schedule to
the Act shall be supplied by the licensee to every applicant at a price not
exceeding one rupee per 929,03 square centimeters.
Rule - 26.Preparation and submission of accounts.
(1) Every licensee,
unless exempted under section 10 of the Act shall cause the accounts of his
undertaking to be made up to the thirty-first day of March each year.
(2) Such licensee shall
prepare and render an annual statement of his accounts in accordance with the
provisions of section 10 of the Act within a period of six months from the
aforesaid date or such extended period as the Government may authorise after it
is satisfied that the time allowed is insufficient owing to any cause beyond
the control of the licensee; and the statement shall be rendered in
quadruplicate if the Government so desires.
(3) The accounts shall be
made up in the prescribed form set out in Annexures1 IV and V
and shall be rendered in Indian currency. "All the forms shall be signed
by the licensee or his accredited agent or manager".
(4) The Government may by
special or general order direct that in addition to the submission of the
annual statements of accounts in the forms prescribed in sub-rule (3), a
licensee, shall submit to the Government or such other authority as it may
appoint in this behalf such additional information as it may require for the
purpose.
Rule - 27.Model condition of supply.
(1) Without prejudice to
the power conferred by section 21 on the Government in this behalf, the model
conditions of supply contained in Annexure VI may, with such variations as the
circumstance of each case require, be adopted by the licensee for the purpose
of sub-section (2) of that section with the previous sanction of the
Government. The licensee shall always keep in his Office an adequate number of
printed copies of the sanctioned conditions of supply and shall, on demand,
sell such copies to any applicant at a price not exceeding per copy.
Rule - 28.Form of requisition.
Requisition
under sub-clause (4) of clause V or sub-clause (5) of clause VI, as the case
may be, of the schedule to the Act, shall be made in the form set out in the
Annexure VII or Annexure VIII.
CHAPTER
IV GENERAL SAFETY PRECAUTIONS
Rule - 29.Construction, Installation, Protection, operation and maintenance of electric supply lines and apparatus.
All
electric supply lines and apparatus shall be sufficient in power and size and
of sufficient mechanical strength for the work they may be required to do, and,
so far as it is practicable, shall be constructed, installed, protected, worked
and maintained in accordance with the standards of the Indian Standards
Institution so as to prevent danger.
Rule - 30.Service lines and apparatus on consumer's premises.
(1) The supplier shall
ensure that all electric supply lines, wires, fittings, and apparatus belonging
to him or under his control, which are on a consumer's premises, are in a safe
condition and in all respects fit for supplying energy, and the supplier shall
take due precautions to avoid danger arising on such premises from such supply
lines, wires, fittings and apparatus.
(2) Service-lines placed
by the supplier on the premises of consumer which are underground or which are
accessible shall be so insulated and protected by the supplier as to be secured
under all ordinary conditions against electrical, mechanical, chemical or other
injury to the insulation.
(3) The consumer shall,
as far as circumstances permit, take precautions for the safe custody of the
equipment on his premises belonging to the supplier.
(4) The consumer shall
also ensure that the installation under his control is maintained in a safe
condition.
Rule - 31.Cut-out on consumer's premises.
(1) The supplier shall
provide a suitable cut-out in each conductor of every service line other than
an earthed or earthed neutral conductor or the earthed external conductor of a
concentric cable within a consumers's premises, in an accessible position. Such
cut-out shall be contained within an adequately enclosed fire-proof receptacle.
Where
more than one consumer is supplied through a common service-line, each such
consumer shall be provided with an independent cut-out at the point of junction
to the common service
The
owner of every electric supply line, other than the earthed or earthed neutral
conductor or any system of the earthed external conductor of a concentric cable
shall protect by a substitute cut-out.
Rule - 32.Identification of earthed and earthed neutral conductor and position of switches and cut-outs therein.
Where
the conductors include an earthed conductor of a two-wire system or an earthed
neutral conductor of a multiwire system or a conductor which is to be connected
thereto the following conditions shall be complied with:—
(1) An indication of a
permanent nature shall be provided by the owner of the earthed or earthed
neutral conductor, or the conductor which is to be connected thereto, to enable
such conductor to be distinguished from any live conductor. Such indication
shall be provided:-
(a) Where the earthed or
earthed neutral conductor is the property of the supplier, at or near the point
of commencement of supply;
(b) Where a conductor
forming part of a consumer's system is to be connected to the supplier's
earthed or earthed neutral conductor at the point where connection is to be
made;
(c) In all other cases a
point corresponding to the point of commencement of supply or at such other
point as may be approved by an Inspector.
(2) No cut-out, line or
switch other than a switch arranged to operate simultaneously on the earthed or
earthed neutral conductor and live conductors shall be inserted or remain in
any earthed or earthed neutral conductor of a two-wire system or in any earthed
or earthed neutral conductor of a multi-wire system or in any conductor
connected thereto with the following exceptions:-
(a) A link for testing
purposes, or
(b) A switch for use in
controlling a generator or transformer.
Rule - 33.Earthed terminal on consumer's premises.
(1) The supplier shall
provide and maintain on the consumer's premises for the consumer's use a
suitable earthed terminal in an accessible position at or near the point of
commencement of supply as defined under rule 58:
Provided
that in the case of medium, high or extra high voltage, installation, the
consumer shall, in addition to the afore-mentioned earthing arrangement,
provide his own earthing system with an independent electrode and maintain the
same:
Provided
further that the supplier may not provide any terminal in the case of
installations already connected to his system on or before the date to be
specified by the Government in this behalf if he is satisfied that the
consumer's earthing arrangement is efficient.
(2) The consumer shall
take all reasonable precautions to prevent mechanical damage to the earthed
terminal and its load belonging to the supplier.
(3) The supplier may
recover from the consumer the cast of installation of such earthed terminal on
the basis laid down in sub-rule (2) of rule 82.
Rule - 34.Accessibility of bare conductors.
Where
bare conductors are used in a building, the owner of such conductors shall :-
(a) ensure that they are inaccessible;
(b) provide in readily
accessible position switches for rendering them dead whenever necessary; and
(c) take such other
safety measures as are considered necessary by the Inspector.
Rule - 35.Caution notices.
The
owner of every medium, high and extra high voltage installation shall affix
permanently in a conspicuous position a Danger notice in Hindi/Urdu and the
local language of the district, and of a type approved by the Inspector on:-
(a) every motor,
generator, transformer and other electrical plant equipment together with
apparatus used for controlling or regulating the same;
(b) all supports of high
and extra-high voltage overhead lines;
(c) luminous tube sign
requiring high voltage supply, X-ray and similar high-frequency installations:
Provided
that, where it is not possible to affix such notice on any generator, motor,
transformer or other apparatus, they shall be affixed as near as possible
thereto or the word danger and the voltage of ^he apparatus concerned shall be
permanently painted on it:
Provided
further that where the generator, motor, transformer or other apparatus is
within an enclosure, one notice affixed to the said enclosure shall be
sufficient for the purposes of this rule.
Rule - 36.Handling of electric supply lines and apparatus.
(1) Before any conductor
or apparatus is handled adequate precautions shall be taken, by earthing or
other suitable means to discharge electricity such conductors or apparatus, and
any adjacent conductor or apparatus if there is danger therefrom and to prevent
any conductor or apparatus from being accidentally or inadvertantly
electrically charged when persons are working thereon:
Provided
that this sub-rule shall not apply to the cleaning of commutators and
slip-rings working at low or medium voltage.
(2) No person shall work
on any live electric supply line or apparatus and no person shall assist such
person on such work, unless he is authorised in that behalf, and takes the
safety measures approved by the Inspector.
(3) Every
telecommunication line on supports carrying a high or extra high voltage line
shall, for the purpose of working thereon, be deemed to be a high voltage line.
Rule - 37.Supply to Vehicles, Cranes, etc.
Every
person owning a vehicle, travelling crane or the like to which energy is
supplied from an external source shall ensure that it is efficiently controlled
by a suitable switch enabling all voltage to be cut off in one operation and,
where such vehicle, travelling crane or the like runs on metal rails, the owner
shall ensure that the rails are electrically continuous and earthed.
Rule - 38.Cable for portable or transportable apparatus.
(1) Flexible cables shall
not be used for portable or transportable motors, generators, transformers,
rectifiers, electric drills, electric sprayers, welding sets or any other
portable or transportable apparatus unless they are heavily insulated and
adequately protected from mechanical injury.
(2) Where the protection
is by means of metallic covering, the covering shall be in metallic connection
with the frame of any such apparatus and earth.
Rule - 39.Cables protected by bituminous materials.
(a) Where the supplier or
the owner has brought into use an electric supply line (other than an overhead
line) which is not completely enclosed in a continuous metallic covering
connected with earth, and is insulated or protected in situ by composition or
material of a bituminous character-
(i) any-pipe, conduit or
the like into which such electric supply line may have been drawn or placed
shall, unless other arrangements are approved by the Inspector in any
particular case, be effectively scaled at its point of entry into any street
box so as to prevent any flow of gas to or from the street box, and
(ii) such electric supply
line shall be periodically inspected and tested where accessible and the result
of each such inspection and test shall be duly recorded by the supplier or the
owner.
(b) It shall not be
permissible for the supplier or the owner after coming into force of these
rules, to bring into use any further electric supply line as aforesaid which is
insulated or protected in situ by any composition or material known to be
liable to produce noxious or explosive gases on excessive heating.
Rule - 40.Street boxes.
(1) Street boxes shall
not contain gas pipes, and precautions shall be taken to prevent, as far as
reasonably possible, any influx of water or gas.
(2) Where electric supply
lines forming part of different system pass through the same street box, they
shall be readily distinguishable from one another and all electric supply
lines at high or extra-high voltage in street boxes shall be adequately
supported and protected so as to prevent risk of damage to or danger from
adjacent electric supply lines.
(3) All street boxes
shall be regularly inspected for the purpose of detecting the presence of gas and
if any influx or accumulation is discovered, the owner shall give immediate
notice to any authority or company who have gas mains in the neighbourhood of
the street box and in cases where a street is large enough to admit the
entrance, of a person after the electric supply lines or apparatus therein have
been placed in position, ample provision shall be made:-
(a) to ensure that any
gas which by accident have obtained access to the box shall escape before a
person is allowed to enter; and
(b) for the prevention of
danger from sparking.
(4) The owner of all
street boxes or pillars containing circuits or apparatus shall ensure that
their covers and doors are so provided that they can be opened only by means of
a key or a special appliance.
Rule - 41.Distinction of circuits of different voltages.
The
owner of every generating station sub-station, junction-box or pillar in which
there are any circuits or apparatus, intended for operation at different
voltages, shall ensure by means of indication of a permanent nature that the
respective circuits are readily distinguishable from one another.
Rule - 42.Accident charge.
The
owner of all circuits and apparatus shall so arrange them that there shall be
no danger of any part thereof becoming accidentally charged to any voltage
beyond the limits of voltage for which they are intended.
Where
A.C. and D.C. circuits are installed on the same support they shall be so
arranged and protected that they shall not come into contact with each other
when live.
Rule - 43.Provision applicable to protective equipments.
(1) Fire buckets filled
with clean dry sand and ready for immediate use for extinguishing fires, in
addition to fire extinguishers suitable for dealing with electric fires, shall
be conspicuously marked and kept in all generating stations, enclosed
sub-stations and enclosed switch stations in convenient situation.
(2) First-aid boxes or
cupboards, conspicuously marked and equipped with such contents as the
Government may specify, shall be provided and maintained in every generating station
enclosed sub-stations and enclosed switch stations so as to be readily
accessible during all working hours. All such boxes and cupboards shall except
in case of unattended sub-stations and switch stations, be kept incharge of
responsible persons who are trained in first-aid treatment and one of such
persons shall be available during the working hour.
Rule - 44.Instructions for restoration of persons suffering from electric shocks.
(1) Instructions in
English, Hindi, Urdu and the local languages of the district, for the
restoration of persons suffering from electric shocks, shall be affixed by the
owner in a conspicuous place in ever generating station, enclosed
sub-station, enclosed switch-station and in every factory as defined in clause
(m) of section 2 of the Factories Act, 1948 (63 of 1948) of the Government of
India in which electricity is used and in such other premises where electricity
is used as the Inspector may, by notice in writing served on the owner, direct.
(2) Copies of the
instructions shall be supplied on demand by an officer or officers appointed by
the Government in this behalf at a price to be fixed by the Government.
(3) The owner of every
generating station, enclosed sub-station, enclosed switch-station, and every
factory or other premises to which this rule applies, shall ensure that all
authorised persons employed by him are acquainted with and are competent to
apply the instructions referred to in sub-rule (1).
Rule - 44A.Intimation of accidents.
A
notice of the occurrence of any accident in connection with generation,
transformation, transmission, conversion, distribution, supply or use of
energy, shall be forwarded to the Inspector and other authorities referred to
in section 33 in the form set out in Annexure-XIII and in accordance with the
following procedure, namely: -
(1) In the case of an
accident which results in the death of a person, either the person responsible
for the generation, transformation, transmission, conversion, distribution,
supply or use of energy or any other person authorised by the State Electricity
Board in this behalf, shall-
(a) within twenty-four
hours of the knowledge of the occurrence of the accident, send a telegraphic
report of the occurrence of such accident to the Inspector and later send a
written statement in the prescribed form within twenty-four hours of sending
the telegraphic report;
(b) send a copy of the
written statement in the prescribed form to the Secretary to the Government in
the department concerned; and
(c) within three hours of
the coming to his knowledge of the accident, send a report of the occurrence of
the accident to the District Magistrate having jurisdiction over the area in
which the accident has occurred and to the officer incharge of the nearest
Police Station.
(2) In the case of an
accident which results in the death of an animal or disablement of a person,
either the persons responsible for the generation, transformation,
transmission, conversion, distribution, supply or use of energy or any other
person authorised by the State Electricity Board in this behalf shall within
twenty-four hours of the knowledge of occurrence of such accident send a
telegraphic report of the occurrence of such accident to the inspector and
later send a written statement in the prescribed form within twenty-four hours
of sending the telegraphic report.
Rule - 45.Precautions to be adopted by consumers, owner, electrical contractors, electric workmen and suppliers.
(1) No electrical
installation work, including additions, alterations, repairs and adjustments
to existing installations except such replacement of lamps, fans, fuses,
switches, low voltage, domestic appliances and fittings as in no way alters its
capacity or character, shall be carried upon the premises of or on behalf of
any consumer or owner, for purpose of supply to such consumer or owner, except
by an electrical contractor licenced in this behalf by the Inspector and under
the direct supervision of a person holding a certificate of competency issued
or recognised by the Government:
Provided
that in the case of works, executed for or on behalf of the Central Government
and in the case of installations in mines, oil fields and railways, the
Government may, by notification in the official Gazette, exempt, on such conditions
as it may impose, any such works described therein either generally or in the
case of any specified class of consumers or owners, from so much of this
sub-rule as requires such work to be carried by any electrical contractor
licenced by the Inspector in this behalf.
(2) No electrical
installation work which has been carried out in contravention of sub-rule (1)
shall be connected with the works of any supplier.
Rule - 46.Periodical inspection and testing of consumer's installations.
(1) (a) Where an installation
is already connected to the supply system of the supplier, every such
installation shall be periodically inspected and tested at intervals not
exceeding five years either by the Inspector or by the supplier as may be
directed by the Government in this behalf or in the case of installations in
mines, oil-fields and railways, by the Central Government.
(b)
Where the supplier is directed by the Government to inspect and test the
installation he shall report on the condition of the installation to the consumer
concerned in a form approved by the Inspector and shall submit a copy of such
report to the Inspector,
(2) (a) The fees for such
inspection and test shall be determined by the Government in the case of each
class of consumers and shall be payable by the consumer in advance.
(b)
In the event of the failure of any consumer to pay the fees on or before the
date specified in the fee-notice, supply to the installation of such consumer
shall be liable to be disconnected under the direction of the Inspector. Such
disconnection, however, shall not be made by the supplier without giving to the
consumer seven clear days notice in writing of his intention so to do.
(3) Notwithstanding the
provisions of this rule, the consumer shall at all times be solely responsible
for the maintenance of his installation in such condition as to be free from
danger.
CHAPTER
V GENERAL CONDITIONS RELATING TO SUPPLY AND USE OF ENERGY
Rule - 47.Testing of consumers installation.
(1) Upon receipt of an
application for a new or additional supply of energy and before connecting the
supply or reconnecting the same after a period of six months the supplier shall
inspect and test the applicant's installation.
The
supplier shall maintain a record of test results obtained at each supply points
to a consumer, in a form to be approved by the Inspector.
(2) If as a result of
such inspection and test, the supplier is satisfied that the installation is
likely to constitute danger, he shall serve on the applicant a notice in
writing requiring him to make such modifications as are necessary to render the
installation safe. The supplier may refuse to connect or reconnect the supply
until the required modifications have been completed and he has been notified
by the applicant.
Rule - 48.Precaution against leakage before connection.
(1) The supplier shall
not connect with his works the installation or apparatus on the premises of any
applicant for supply unless he is reasonably satisfied that the connection will
not, at the time of making the connection, cause a leakage from that
installation or apparatus exceeding one five-thousandth part of the maximum
current supplied to the applicant's premises.
(2) If the supplier
declines to make a connection under the provisions of sub-rule (1) he shall
serve upon the applicant a notice in writing stating his reason for so
declining.
Rule - 49.Leakage on consumer's premises.
(1) If the Inspector or
the supplier has reason to believe that there is in the system of a consumer
leakage which is likely to affect injuriously the use of energy by the supplier
or by other persons, or which is likely to cause danger, he may give the
consumer reasonable notice in writing that he desires to inspect and test the
consumer's installation.
(2) If, no such notice
being given-
(a) the consumer does not
give all reasonable facilities for inspection and testing of his installation;
or
(b) a leakage exceeding
one five-thousandth part of the maximum current supplied to the consumer's
installation is shown to exist, the supplier may, and if directed so to do by
the Inspector shall discontinue the supply of energy to the installation but
only after giving to the consumer forty-eight hours notice in writing of
disconnection of supply and shall not recommence the supply until he or the
Inspector is satisfied that the cause of the leakage has been removed.
Rule - 50.Supply and use of energy.
(1) The energy shall not
be supplied, transformed, converted, or used or continued to be supplied,
transformed, converted or used unless the following provisions are observed:
(a) a suitable linked
switch or a circuit-breaker of requisite capacity to carry and break the
current is placed as near as possible to, but after the point of commencement
of supply as denned under rule 58. So as to be readily accessible and capable
of being easily operated to completely isolate the supply to the installation,
such equipment being in addition to any equipment installed for controlling
individual circuits or apparatus:
Provided
that where the point of commencement of supply and consumer's apparatus are
near each other, one linked switch or circuit-breaker near the point of
commencement of supply shall be considered sufficient for the purpose of this
rule;
(b) a suitable linked
switch or a circuit-breaker of requisite capacity to carry and break the full
load current is inserted on the secondary side of a transformer, in the case of
high or extra high voltage installation;
Provided,
however, that the linked switch on the primary side of the transformer may be
of such capacity as to carry the full load current and to break only the
magnetising current of the transformer:
Provided
further that the provision of this clause shall not apply to transformers
installed in sub-stations up to and including 100 KVA belonging to the
suppliers;
(c) every distinct
circuit is protected against excess energy by means of a suitable cut-out or a
circuit breaker of adequate breaking capacity suitably located and so
constructed as to prevent danger from over-heating, arcing or scattering of hot
metal when it comes into operation and to permit of ready renewal of the
fusible metal of the cut-out without danger;
(d) the supply of energy
to each motor or other apparatus is controlled by a suitable linked switch or a
circuit-breaker of requisite capacity placed in such a position as to be
adjacent to the motor or other apparatus readily accessible to and easily
operated by the persons incharge and so connected in circuit that by its means
all supply of energy can be cut off from the motor or apparatus, and from any
regulating switch, resistance or other device associated therewith;
(e) all insulating
material is chosen with special regard to the circumstances of its proposed
use, the mechanical strength being sufficient for its purpose and so far as is
practicable, is of such a character or so protected as to maintain adequately
its insulating properties under all working conditions in respect of
temperature and moisture; and
(f) adequate precautions
are taken to ensure that no live parts are so exposed as to cause danger.
(2) (a) Where energy is
being supplied, transformed, converted, or used the consumer or the owner of
the concerned installation shall be responsible for the continuous observance
of the provisions of sub-rule (1) in respect of his installation.
(b)
Every consumer shall use all reasonable means to ensure that where energy is
being supplied by a supplier, no person other than the supplier shall interfere
with the service lines and apparatus placed by the supplier on the premises of
the consumer.
Rule - 51.Provisions applicable to medium, high or extra-high voltage installation.
The
following provisions shall be observed where energy at medium, high or
extra-high voltage is supplied, converted, transformed, or used:-
(1) (a) All conductors
(other than those of overhead line) shall be completely enclosed in
mechanically strong metal casing or metallic covering which is electrically and
mechanically continuous and adequately protected against mechanical damage
unless the said conductors are accessible only to an authorised person or are
installed and protected to the satisfaction of an Inspector so a to prevent
danger.
(b)
All metal work enclosing, supporting or associated with the installation, other
than that designed to serve as a conductor shall, if considered necessary by
the Inspector be connected with earth.
(c)
Every main switch board shall comply with the following provisions namely:-
(i) a clear space of not
less than (0.914 meter) 3 feet in width shall be provided in front of the
switch board;
(ii) if there are any
attachments or bare connections at the back of the switch board the space (if
any) behind the switch board shall be either less than (0.229 metre) 9 inches,
or more than (0.762 metre) 30 inches in width, measured from the furthest
outstanding part of any attachment or conductor;
(iii) if the space behind the
switch board exceeds (0.762 metre) 30 inches in width, there shall be a passage
way from either end of the switch board clear to a height of (1.829 metre) 6
feet.
(2) Where an application
has been made to a supplier for supply of energy to any installation, he shall
not commence, or where the supply has been discontinued, recommence the supply
unless he is satisfied that the consumer has complied in all respects with the
conditions of supply, set out in sub-rule (1) of this rule, rules 53 and 64.
(3) Where a supplier
proposes to supply or use energy at medium voltage or to recommence supply
after it has been discontinued for a period of six months, he shall, before
connecting or reconnecting the supply, give notice in writing of such intension
to the Inspector.
(4) If at any time after
connecting the supply the supplier is satisfied that any provision of sub-rule
(1) of this rule, or rules 50 and 64 is not being observed, he shall give
notice of the same in writing to the consumer and the Inspector
specifying how the provision has not been observed, and may discontinue the
supply if the Inspector so direct.
Rule - 52.Appeal to Inspector in regard to defect.
(1) If any applicant for
a supply or a consumer is dissatisfied with the action of the supplier in
declining to commence, to continue or to recommence the supply of energy to his
premises on the grounds that the installation is defective or is likely to
constitute danger, he may appeal to the Inspector to test the installation and
the supply shall not, if the Inspector or under his orders, any other officer
appointed to assist the Inspector, is satisfied that the installation is free
from the defect or danger complaining of, be entitled to refuse supply to the
consumer on the grounds aforesaid, and shall, within twenty-four hours after
the receipt of such intimation from the Inspector, commence, continue or
recommence the supply of energy.
(2) Any test for which
application has been made under the provision of sub-rule (1) shall be carried
out within seven days after receipt of such application.
(3) This rule shall be
enclosed on every notice given under the provision of rule 47, 48 and 49.
Rule - 53.Cost of inspection and test of consumer's installation.
(1) The cost of the first
inspection and test of a consumer's installation carried out in pursuance of
the provisions of rules 47 shall be borne by the supplier and the cost of every
subsequent inspection and test shall be borne by the consumer, unless in the
appeal under rule 52, the Inspector directs otherwise.
(2) The cost of any inspection
and test made by the Inspector at request of the consumer or other interested
party, shall be borne by the consumer or other interested party, unless the
Inspector directs otherwise.
(3) The cost of each and
every such inspection and test by whom so borne shall be calculated in
accordance with the scale specified by the Government in this behalf.
Rule - 54.Declared voltage of supply to consumer.
Except
with the written consent of the consumer or with the previous sanction of the
Government a supplier shall not permit the voltage at the point of commencement
of supply as defined under rule 58 to vary from the declared voltage by more
than 5 per cent in the case of low or medium voltage or by more than twelve and
a half per cent in the case of high or extra high voltage.
Rule - 55.Declared frequency of supply to consumer.
Except
with the written consent of the consumer or with the previous sanction of the
Government a supplier shall not permit the frequency of an alternating current
supply to vary from the declared frequency by more than 3 per cent.
Rule - 56.Sealing of meters and cut-outs.
(1) A supplier may affix
one or more seals to any cut-out and to any meter, maximum demand indicator, or
other apparatus placed upon a consumer's premises in accordance with section
26, and no person other than the supplier shall break any such seal.
(2) The consumer shall
use all reasonable means in his power to ensure that no such seal is broken
otherwise than by the supplier.
(3) The word
"supplier" shall for the purpose of this rule include the Government
when any meter, maximum demand indicator or other apparatus is placed upon a
consumer's premises by the Government.
Rule - 57.Meters maximum, demand indicators and other apparatus on consumer's premises.
(1) Any meter or maximum
demand indicator or other apparatus placed upon a consumer's premises in
accordance with section 26 shall be of appropriate capacity and shall be deemed
to be correct if its limits of error do not exceed 3 per cent above or below
absolute accuracy at all loads in excess of one-tenth of full load and up to
full load.
(2) No meter shall
register at no load.
(3) Every supplier shall
provide and maintain in proper condition such suitable apparatus as may be
prescribed or approved by the Inspector for the examination, testing and
regulation of meters used or intended to be used in connection with the supply
of energy:
Provided
that the supply may with the approval of the. Inspector and shall, if required
by Inspector, enter into a joint arrangement with any other supplier for the
purpose aforesaid.
(4) Every supplier shall
examine, test and regulate all meters, maximum demand indicators and other
apparatus for ascertaining the amount of energy supplied before their first
installation at the consumer's premises and at such other intervals as may be
directed by the Government in this behalf.
(5) Every supplier shall
maintain a register of meters showing the date of the last test, the error
recorded at the time of the test, the limit of accuracy after adjustment and
final, test, the date of installation, withdrawal, reinstallation, etc., for
the examination of the Inspector or his authorised representative.
Rule - 58.Point of commencement of supply.
The
point of commencement of supply of energy to a consumer shall be deemed to be
the point at the out-going terminals of the cut-outs inserted by the supplier
in each conductor of every service line other than an earthed or earthed
neutral conductor or the earthed external conductor of a concentric cable at
the consumer's cable.
Rule - 59.Precautions against failure of supply-notice of failure.
(1) The lay-out of the
electric supply lines of the supplier for the supply of energy throughout his
area of supply shall under normal working conditions be sectionalised and so
arranged, and provided with cut-outs or circuit breaker, so located as to
restrict within reasonable limits the extent of the portion of the system
affected by any failure of supply.
(2) The supplier shall
take all reasonable precaution to avoid any accidental interruptions of supply,
and also to avoid danger to the public or to any employee or authorised person
when engaged on any operation during and in connection with the installation,
extension, replacement, repair and maintenance of any works.
(3) The supplier shall
send to the Inspector notice of failure of supply of such kind as the Inspector
may from time to time require to be notified to him, and such notice shall be
sent by the earliest practicable post after the failure occurs or after the
failure becomes known to the supplier and shall be in such form and contain
such particulars as Inspector may from time to time specify.
(4) For the purposes of
testing or for any other purposes connected with the efficient working of the
undertaking, the supply of energy may be discontinued by the supplier for such
period as may be necessary subject (except in case of emergency) to not less
than twenty-four hour's notice being given by the supplier to all classes of
consumers specified by the Inspector likely to be affected by such discontinuance
and in the event of any consumer or consumers from such classes of consumer
objecting, the supply of energy shall not be discontinued (except in cases of
emergency), without the consent of the Inspector and subject to such conditions
as he may impose.
CHAPTER
VI ELECTRIC SUPPLY LINES, SYSTEM AND
APPARATUS FOR LOW AND MEDIUM VOLTAGE
Rule - 60.Test for resistance of insulation
(1) Where any electric
supply line for use at low or medium voltage has been disconnected from a
system for the purpose of addition or alteration or repair, such electric
supply lines shall not be reconnected to the system until the supplier or the
owner has applied the test prescribed under rule 48.
(2) The provisions of
sub-rule (1) shall not apply to overhead lines except overhead insulated cables
unless the Inspector otherwise directs in any particular case.
Rule - 61.Connection with earth
(1) The following
provisions shall apply to the connection with earth of system at low voltage in
cases where the voltage (between phases or outers) normally exceeds 125 volts
and of systems at medium voltage:-
(a) The neutral conductor
of a three-phase four-wire system and the middle conductor of a two-phase
three-phase wire system shall be earthed by not less than two separate and
distinct connections with earth both at the generating station and at the
sub-station. It may also be earthed at one or more points along the
distribution system or service line in addition to any connection with earth
which may be at the consumer's premises.
(b) In the case of a
system comprising electric supply lines having concentric cables, the external
conductor of such cable shall be earthed by two separate and distinct
connections with earth.
(c) The connection with
earth may (include a link by means of which the connection may be temporarily
interrupted for the purpose of testing or for locating a fault.
(d) (i) In a direct
current three-wire system the middle conductor shall be earthed at the
generating station only, and the current from the middle conductor to earth be
continuously recorded by means of a recording meter, and if at any time current
exceeds one-thousandth part of the maximum supply-current, immediate steps
shall be taken to improve the insulation of the system.
(ii)
Where the middle conductor is earthed by means of a circuit-breaker with a
resistance connected in paralleled the resistance shall not exceed 1,0 ohms and
on the opening of the circuit breaker, immediate steps shall be taken to
improve the insulation of the system, and the circuit-breaker shall be reclosed
as soon as possible.
(iii)
The resistance shall be used only as a protection for the ammeter in case of
earths on the system and until such earths are removed. Immediate steps shall
be taken to locate and remove the earth.
(e) In the case of an
alternating current system, there shall not be inserted in the connection with
earth any impedance (other than that required solely for the operation of
switch-gear or instruments), cut-out or circuit-breaker and the result of any
test made to ascertain whether the current (if any) passing through the
connection with earth is normal, shall be duly recorded by the supplier.
(f) No person shall make
connection with earth by the aid of nor shall he keep it in contact with, any
water main not belonging to him except with the consent of the owner thereof
and of the Inspector.
(g) Alternating current
systems which are connected with earth as aforesaid may be electrically
interconnected:
Provided
that each connection with earth is bonded to the metal sheathing and metallic
armouring (if any), of the electric supply lines concerned.
(2) The frame of every
generator, stationary motor, and so far as is practicable, portable motor, and
the metallic parts (not intended as conductors) of all transformers and any
other apparatus used for regulating or controlling energy and all medium
voltage energy consuming apparatus shall be earthed by the owner by two
separate and distinct connections with earth.
(3) All metal casings or
metallic coverings containing or protecting any electric supply-line or
apparatus shall be connected with earth and shall be so joined and connected
with boxes and other openings as to make good mechanical and electrical
connection throughout their whole length:
Provided
that where the supply is at low voltage, this sub-rule shall not apply to
isolate wall tubes or to brackets, electroliers, switches, ceiling fans,
regulator covers or other fittings (other than portable hand lamps and portable
and transportable apparatus) unless provided with earth terminal. Provided
further that where the supply is at low voltage and when the installations are
either new or renovated all plug sockets shall be three pin type, and the third
pin shall be permanently and efficiently earthed.
This
sub-rule shall come into force immediately in the case of new installations and
in the case of existing installations the provisions of this sub-rule shall be
complied with before the expiry of a period of two years from the commencement
of these rules.
(4) All earthing systems
shall, before electric supply lines or apparatus are energised, be tested for
electrical resistance to ensure efficient earthing.
(5) All earthing systems
belonging to the supplier, shall, in addition, be tested for resistance on dry
day during the dry season not less than once every two years.
(6) A record of every
earth test made and the result thereof shall be kept by the supplier for a
period of not less than two years after the day of testing and shall be
available to the Inspector when required.
Rule - 62.Systems at medium voltage
Where
a medium voltage supply system is employed, the voltage between earth and any
conductor forming part of the said system shall not, under normal conditions,
exceed low voltage.
CHAPTER
VII ELECTRIC SUPPLY LINES, SYSTEM AND APPARATUS FOR
HIGH AND EXTRA-HIGH VOLTAGE
Rule - 63.Approval by inspection.
(1) Before making an
application to the Inspector for permission to commence supply of energy at
high or extra-high voltage to any person, the supplier shall ensure that the
high or extra-high voltage electric supply lines or apparatus belonging to him
are placed in position, properly joined and duly completed and examined. The
supply of energy shall not be commenced by the supplier unless and until the
Inspector is satisfied that the provisions of rules 65 to 69both inclusive have
been complied with the approval in writing of the Inspector has been obtained
by him:
Provided
that the supplier may energise the aforesaid electric supply lines or apparatus
for the purpose of tests specified in rule 65.
(2) The owner of any high
or extra-high voltage installation shall, before making application to the
Inspector for approval of his installation or additions thereto test, every
high or extra-high voltage circuit or additions thereto other than an over-head
line, and satisfy himself that they withstand the application of the testing
voltage setout in sub-rule (1) of rule 65 and shall duly record the results of
such tests and forward them to the inspector:
Provided
that, an Inspector may direct such owner to carry out such tests as he deems
necessary or if he thinks fit, accept the manufacturer's satisfied tests in
respect of any particular apparatus in place of the tests required by this
rule.
(3) The owner of any high
or extra-high voltage installation who makes any additions or alterations or
his installations shall not connect to the supply his apparatus or electric
supply lines, comprising the said alterations or additions unless and until
such alterations or additions have been approved in writing by the Inspector.
Rule - 64.Use of energy at high and extra-high voltage.
(1) The Inspector shall
not authorise a supplier to connect a supply of energy at high or extra-high
voltage to any consumer, unless—
(a) all conductors and
apparatus intended for use at high or extra-high voltage and situated on the
premises of the consumer are inaccessible except to an authorised person and
all operations in connection with the said conductors and apparatus are carried
out by an authorised person;
(b) the consumer has
provided and agreed to maintain a separate building locked, weather-proof and
fire-proof enclosure of agreed design and location, to which the supplier shall
at all times have access for the purpose of housing his high or extra-high
voltage apparatus and metering equipment, or where the provisions of a separate
building or enclosure is impracticable, the consumer has segregated the
aforesaid apparatus of the supplier from any other part of his own apparatus:
Provided
that such segregation shall be by the provision fire-proof walls, if the
Inspector considers it to be necessary:
Provided
further that in the case of an outdoor installation the consumer shall suitably
segregate the aforesaid apparatus belonging to the supplier from his own to the
satisfaction of the Inspector;
(c) all pole type
sub-stations are constructed and maintained in accordance with rule 69.
(2) The following
provisions shall be observed where energy at high of extra-high voltage is
supplied, converted, transformed or used:-
(a) All conductors of
live part of any apparatus shall ordinarly be inaccessible.
(b) All windings, at high
or extra-high voltage or motors or other apparatus within reach from any
position in which a person may require to be, shall be suitably protected so as
to prevent danger.
(c) Where transformer or
transformers are used, suitable provision shall be made, either by connecting
with earth a point of the circuit at the lower voltage or otherwise, to guard
against danger by reason of the said circuit becoming accidentally charged
above its normal voltage by leakages from or contact with circuit at the high
voltage,
(d) (i) Where a
sub-station or a switch-station is situated in any building and where fire in
the sub-station or a switch-station might involve risk to the said building and
the said sub-station or switch-station contains oil immersed transformers,
switches or static condensers involving the use of more than 2272.8 liters (500
gallons) of oil in one chamber, provision shall be made for suitable oils soak
pits and where use of more than 9091.9 litres (2000 gallons) of oil in any one
oil tank, receptacle or chamber is involved, provisions shall be made for the
draining away or removal of any oil which may leave or escape from the tanks,
receptacles or chambers containing the same; special precautions shall be taken
to prevent the spread of any fire resulting from the ignition of the oil from
any cause and adequate provision shall be made for extinguishing any fire which
may occur. Spare oil shall not be stored in any such sub-station or switch
station.
(ii)
Cable trenches inside sub-stations and switch-stations containing the cables
shall be filled with sand, pebbles or similar non-inflammable materials or
completely covered with non-inflammable slabs.
(e) Unless the conditions
are such that all the conductors and the apparatus for use of high or
extra-high voltage may be made dead at the same time for the purpose of
cleaning or for other work thereof, the said conductor and apparatus shall be
so arranged that they may be made dead in sections, and that work on any
section made dead may be carried on by an authorised person without danger.
(f) Adequate precautions
shall be taken to prevent unauthorised access to any part of the installation
designed to be electrically charged at high or extra-high voltage.
Rule - 65.Voltage tests.
(1) High and extra-high
voltage electric supply lines (other than overhead lines) and apparatus of the
supplier shall not be connected to a system for the purposes of supply or use
of energy unless the insulations of the said electric supply lines and
apparatus has withstood, either- I
(i) The 'tests prescribed
in that behalf in the appropriate specification of the Indian Standards
Institution or in its absence the British Standards Institution then current;
or
(ii) In cases where no
such tests have been prescribed, the continuous application, between conductors
and also between conductors and earth during the period of one minute of the
testing voltage given in sub-rule (2).
(2) for the purposes of
clause (ii) of sub-rule (1)—
(a) if the normal working
voltage does not exceed 1,000 volts, the testing voltage shall be 2,000 volts;
(b) if the normal working
voltage exceeds 1,000 volts, but does not exceed 11,000 volts, the testing
voltage shall be double the normal working voltage;
(c) if the normal working
voltage exceeds 11,000 volts, the testing voltage shall be normal working
voltage plus 10,000 volts:
Provided
that an apparatus which is not new shall be tested in such manner as the
Inspector may specify.
(3) If the test
prescribed in sub-rule (1) is made prior to the said electric supply lines and
apparatus being placed in position for the purposes of supply of energy, the
said electric supply lines and the apparatus after having being placed in
position and before being connected to the system shall have withstood a
further test for resistance of insulation either by the application of tests
prescribed in sub-rule (1) whenever reasonably practicable, or by the
application of a testing voltage of not less than 1,000 volts either
alternating current or direct current between conductors and also between conductors
and earth during a period of not less than one minute.
(4) Where any electric
supply line (other than an overhead line) or apparatus for use at high or
extra-high voltage has been disconnected from a system for alteration or
repair, such electric supply line or apparatus shall not be reconnected to the
system until the supplier has applied the test prescribed in sub-rule (3) and
satisfied himself that the insulation of the electric supply line or apparatus
is in sound condition.
(5) The supplier shall
duly record the result of every test made under this rule.
(6) Notwithstanding the
provisions of sub-rule (1) to (4) (both inclusive) the Inspector may, where he
thinks fit, accept the manufacturer's certified tests in place of the tests
prescribed in this rule.
Rule - 66.Metal sheathed electric supply lines, precautions against excess leakage.
(1) The following
provisions shall apply to electric supply lines (other than overhead lines) of
a supplier for use at high or extra-high voltage:-
(a) The conductors shall be
enclosed in metal sheathing which shall be electrically continuous and
connected with earth, and the conductivity of the metal sheathing shall be
maintained and reasonable precautions taken where necessary to avoid corrosion
of the sheathing.
(b) In the event of a
failure of insulation occurring between one conductor and the metal sheathing
at any point along an electric supply line as aforesaid, the impedance of the
relevant circuit shall be such that, with the full voltage maintained at the
source of supply, the current resulting from such failure shall not be less
than twice the value of the current for which a suitable cut-out of adequate
rupturing capacity or other suitable overload protective device has been set to
operate or the current required to operate a suitable discriminative fault
current relay:
Provided
that the operation of the aforesaid overhead protective device or of the
discriminative fault current relay shall cause the automatic operation of a
circuit breaker of adequate rupturing capacity. The relevant circuit here
before referred to means the complete circuit from the source of supply to the
point of failure of the insulation including any connection with earth of the
system of which the electric supply lines as aforesaid forms part and any
current limiting device inserted in such connection with earth; and the source
of supply means the point at which energy is given to the system or circuit of
which the electric supply line as aforesaid forms part.
(c) Where an electric
supply line as aforesaid lids concentric cables and the external conductor is
insulated from an outer metal sheathing and connected with earth, the external
conductor may be regarded as the metal sheathing for the purposes of this rule
provided that, the foregoing provisions as to conductivity are complied with.
(2) Nothing in the
provisions of sub-rule (1) shall preclude the employment in generating
stations, sub-stations and switch-stations (including outdoor sub-stations and
outdoor switch-stations) of conductors for use at high or extra-high voltage
which are not enclosed in metal sheathing or preclude the use of electric
supply lines laid before the prescribed date to which the provisions of these
rules apply.
Rule - 67.Connection with earth.
(1) The following
provisions shall apply to the connection with earth of three-phase system for
use at high or extra-high voltages:-
(a) The neutral point
shall be earthed by not less than two separate and distinct connections with
earth each having its own electrode at the generating station and at the
sub-stations and may be earthed at any other point provided that no
interference of any description is caused by such earthing;
(b) In the event of an
appreciable harmonic current following in the neutral connection so as to cause
interference with communication circuits, the generator or transformer neutral
shall be earthed through a suitable impedence.
(2) Single phase high or
extra-high voltage system shall be earthed in a manner approved by the
Inspector.
(3) In the case of a
system comprising electric supply lines having concentric cables, the external
conductor shall be the one to be connected with earth.
(4) Where, a supplier
proposes to connect with earth an existing system for use at high or extra-high
voltage which has not hitherto been so connected with earth, he shall give not
less than fourteen days notice in writing together with particulars to the
telegraph authority of the proposed connection with earth.
(5) Where the earthing
load and earth connection are used only in connection with earthing guards erected
under high or extra-high voltage overhead lines where they cross a
telecommunications line, or a railway line, and where such lines are equipped
with earth leakage relays of a type and setting approved by the Inspector, the
resistance shall not exceed 25 ohms.
(6) In so far as the
provisions of rule 61 are consistent with the provisions of this rule all
connections with earth shall also comply with the provision of that rule.
Rule - 68.General conditions as to transformation and control of energy.
(1) Where energy at high
or extra-high voltage is transformed, converted, regulated or otherwise
controlled in sub-stations or switch-stations (including outdoor sub-stations
and outdoor switch-stations) or in street boxes constructed under ground, the
following provisions shall have effect:—
(a) Sub-stations and
switch-stations shall preferably be erected above ground but where necessarily
constructed underground due provision for ventilation and drainage shall be
made;
(b) Outdoor sub-stations
except pole type sub-stations, and outdoor switch stations shall (unless the
apparatus is completely enclosed in a metal covering connected with earth, the
said apparatus also being connected with the system by armoured cables) be
efficiently protected by fencing not less than (2.439 meters) eight feet in
height or other means so as to prevent access to the electric supply lines and
apparatus therein by an authorised person;
(c) Underground street
boxes (other than sub-stations) which contain transformers shall not contain
switches or other apparatus, and switches, cut-outs or other purposes shall be
fixed in separate receptacles above ground wherever practicable;
(2) Where energy is
transformed, suitable provisions shall be made either by connecting with earth
a point of the system at the lower voltage or otherwise to guard against danger
by reason of the system becoming accidentally charged above its normal voltage
from a contact with the system at the higher voltage.
Rule - 69.Pole type sub-stations.
Where
platform type construction is used for a pole type sub-station and sufficient
space for a person to stand on the platform is provided, a substantial hand
rail shall be built around the said platform and if the hand rail is of metal,
it shall be built around the said platform and if the hand rail is of metal, it
shall be connected with earth; provided that in the case of pole type
sub-station on wooden support and wooden platform the metal hand rail shall not
be connected with earth.
Rule - 70.Condenser.
Suitable
provision shall be made for immediate and automatic discharge of every static
condenser on disconnection of supply.
Rule - 71.Additional provisions for supply to high voltage luminous tube sign installation.
(1) Any person who
proposed to use or who is using energy for the purpose of operating a luminous
tube sign installation, or who proposes to transform or who is transforming
energy to a high voltage for any such purpose shall comply with the following
conditions:-
(a) All live parts of the
installation (including all apparatus and live conductors in the secondary
circuit, but excluding the tubes except in the neighbourhood of their
terminals) shall be inaccessible to authorised persons and such parts shall be
effectively screened.
(b) Irrespective of the
method of obtained the voltage of the circuit which feeds the luminous
discharge tube sign, no part of any conductor of such circuit shall be in
metallic connection (except in respect or its connections with earth) with any
conductor of the supply system or with the primary winding of the transformer.
(c) All live parts of an
exterior installation shall be so disposed as to protect them against the
effects of the weather, and such installation shall be so arranged and
separated from its surroundings as to limit, as far as possible, the spreading
of fire.
(d) The secondary circuit
shall be permanently earthed at the transformer and the core of every
transformer shall be earthed.
(e) Where the conductors
of the primary circuit are not in metallic connection with the supply
conductors (e. g. where a motor-generator or a double wound convertor is used)
the phase of such primary circuit shall be permanently earthed at the motor
generator or convertor, or at the transformer.
(f) A final sub-circuit
which forms the primary circuit of a fixed luminous discharge tube sign
installation shall be reserved solely for such purpose.
(g) An interior
installation shall be provided with suitable adjacent means for disconnecting
all phases of the supply except the "neutral" in three-phase
four-wire circuit.
(h) A separate primary
final sub-circuit shall be provided for each transformer or each group of
transformers having an aggregate input not exceeding 1,000 volt amperes, of a
fixed luminous discharge tube sign installation.
(i) For installations on
the exterior of a building a suitable emergency fireproof linked switch to
operate on all phases except the neutral in a three phase four wire circuit
shall be provided and fixed in a conspicuous position at not more than 2.743
meters (9ft.) above the ground.
(j) A special
"Caution" notice shall be affixed in conspicuous place on the door of
every high voltage enclosure to the effect that the low voltage supply must be
cut off before the enclosure is opened.
(k) Where static
condensers are used they shall be installed on the load side of the fuses and
the primary (low voltage) side of the transformer.
(l) Where static
condensers are used on the primary side, means shall be provided for
automatically discharging the condensers when the supply is cut off; provided
that static condensers or any circuit interrupting devices on the high or
extra-high voltage side shall not be used without the approval in writing of
the Inspector.
(2) The owner or user of
any luminous tube sign or similar high voltage installation shall not bring the
same into use without giving to the Inspector not less than 14 day's notice in
writing of his intention so to do.
Rule - 72.Additional provision for supply to high voltage electrode boilers.
(1) Where a system having
a point connected with earth is used for supply of energy at high or extra-high
voltage to an electrode boiler which is also connected with earth, the
following conditions shall apply:—
(a) The metal work of the
electrode boiler shall be efficiently connected to the metal sheathing and
metallic armouring (if any), of the high voltage electric supply-line whereby
energy is supplied to the electrode boiler.
(b) The supply of energy
at high or extra-high voltage to the electrode boiler shall be controlled by a
suitable circuit breaker so set as to operate in the event of the phase
currents becoming unbalanced to the extent of 10% of the rated current
consumption of the electrode boiler under normal conditions of operation:
Provided
that if in any case a higher setting is essential to ensure stability of
operation of the electrode boiler, the setting may be increased so as not to
exceed 15 per cent of the rated current consumption of the electrode boiler
under normal conditions of operation.
(c) An inverse time
element device may be used in conjunction with the aforesaid circuit breaker to
prevent the operation thereof unnecessarily on the occurrence of unbalanced
currents of momentary or short duration.
(d) The supplier shall
serve a notice in writing on the telegraph authority at least seven days prior
to the date on which such supply of energy is to be afforded specifying the
location of every point (including the earth connection of the electrode
boiler) at which the system is connected with earth.
(2) The owner or user of
any high or extra-high voltage electrode boiler shall not bring the same into
use without giving the Inspector not less then 14 days notice in writing of his
intention so to do.
Rule - 73.Supply to X-ray and high frequency installation.
(1) Any person who
proposes to employ or who is employing energy for the purpose of operating an
X-ray or similar high-frequency installation shall comply with the following
conditions:-
(a) Mechanical barriers
shall be provided to prevent too close an approach to any high-voltage parts of
the X-ray apparatus, except the X-ray tube and its lead, unless such high-voltage
parts have been rendered shock-proof by being shielded by earthed metal or
adequate insulating material.
(b) Where extra-high
voltage generators operating at 300 peak KV or more are used, such generators
shall be installed in rooms separate from those containing the other equipment
and any step up transformer employed shall be so installed and protected as to
prevent danger.
(c) A suitable switch
shall be provided to control the circuit supplying a generator, and shall be so
arranged so to be open except while the door of the room housing the generator
is locked from the outside.
(d) X-ray tubs used in
therapy shall be mounted in an earthed metal enclosure.
(e) Every X-ray machine
shall be provided with a millimeter or other suitable measuring instrument,
readily visible from the control position and connected, if practicable in the
earthed lead but guarded if connected in the high voltage lead.
(f) This sub-rule shall
not apply to shock-proof portable units or shockproof self-contained and
stationary units.
Note. The
expression "Shock-proof", as applied to X-ray and high frequency
equipment, shall mean that such equipment is guarded with earthed
metal so that no person may come into contact with any live part.
(2) (a) In the case of
non-shock-proof equipment, overhead high-voltage conductors, unless suitably
guarded against personal contact, shall be adequately spaced and high-voltage
leads on tilting tables and fluroscope shall be adequately insulated or so
surrounded by barriers as to prevent inadvertent contact.
(b) The
low voltage circuit of the step up transformer shall contain a manually
operated control device having overload protection in addition to the
over-current device for circuit protection, and these devices shall have no
exposed live parts and for diagnostic work there shall be an additional switch
in the said circuit, which shall be of one of the following types:-
(i) a switch with a
spring or other mechanism which will open automatically except while held
closed by the operator; or
(ii) a time-switch which
will open automatically after a definite period of time for which it has been
set.
(c)
If more than one piece of apparatus be operated from the same high or extra
high voltage, sources, each shall be provided with a high or extra high voltage
switch to give independent control.
(d)
Low frequency current carrying parts of machine of the quenched gap or open gap
type shall be so insulated or guarded that they cannot be touched during
operation, the high frequency circuit proper which delivers high frequency
current normally for the thereapeutic proposed, being exempted.
(e)
All X-ray generators having capacitors shall have suitable means for
discharging the capacitors manually.
(f)
Except in the case of self-contained units, all 200 peak KV or higher X-ray
generators shall have a sphere gap installed in the high voltage system
adjusted so that it will breakdown on over voltage urges.
(3) (a) All non-current
carrying metal parts of tube stands, fluroscopes and other apparatus shall be
properly earthed and insulating floors, mats or platforms shall be provided for
operators in proximity to high or extra-high voltage parts unless such parts
have been rendered shock-proof. (b) Where short-wave thereapy machines are
used, the treatment tables and examining charts shall be wholly non-metallic.
(4) The owner of any
X-ray installation or similar high frequency apparatus shall not bring the same
into use without giving to the Inspector not less than 14 days notice in
writing of his intention so to do:
Provided
that the aforesaid notice shall not be necessary in the case of shock-proof
Portable X-ray and high frequency equipment which have been inspected before
the commencement of the rules and periodically thereafter
CHAPTER VIII OVERHEAD LINES
Rule - 74.Material and strength.
(1)
All conductors of overhead lines other than those
specified in sub-rule (1) of rule 86 shall have a breaking strength of not less
than 317.51 Kg. (700 lbs.)
(2)
Where the voltage is low and the span is of less than
15.24 meters (50 feet) and is on the owner's or consumer's premises, a
conductor having an actual breaking strength of not less than 136.08 Kg. (300
lbs.) may be used.
Rule - 75.Joints.
Joints between
conductors of overhead lines shall be mechanically and electrically secure
under the conditions of operation. The ultimate strength of the joint shall not
be less than 95% of that of the conductor, and the electrical conductivity not
less than that of the conductor.
Rule - 76.Maximum stresses, factors of safety.
(1) (a)
The owner of every overhead lines shall ensure that it has the following
minimum factors of safety. The minimum factors of safety of supports based on
crippling load shall be as follows:-
(i) for metal
supports |
2.0 |
(ii) for
mechanically processed concrete supports |
2.5 |
(iii) for
hand-moulded concrete supports |
3.0 |
(iv) for wood
supports |
3.5 |
The said owner
shall also ensure that the strength of the supports in the direction of the
line is not less than one-fourth of the strength required in the direction
transverse to the line:
Provided that in
the case of latticed steel or other compound structures, the factors of safety
shall not be less than 1.5 under such broken wire conditions as may be
specified by the Government in this behalf.
(b) The minimum
factors of safety for stay-wires, guard wires or bearer wires shall be 2.5
based on the ultimate tensile strength of the wire.
(c) The minimum
factor of safety for conductors shall be based on their ultimate tensile
strength. In addition, the conductor tension at 32.20C (9000 without external
load, shall not exceed the following percentage of the ultimate tensile
strength of the conductor:-
Initial unloaded
tension |
35% |
Final unloaded
tension |
25% |
Provided that in
the case of conductors having a cross-section of a generally triangular shape,
such as conductors composed of 3 wires, the final unloaded tension at 32.20C
(900f) shall not exceed 30 per cent of the ultimate tensile strength of each
conductor.
(2)
For the purpose of calculating the factors of safety
prescribed in sub rule (1)-
(a)
the maximum wind pressure shall be such as the Government
may specify in each case;
(b)
for cylindrical bodies the effective area shall be taken
as two-thirds of the projected area exposed to wind pressure;
(c)
for lattice steel or other compound structures the wind
pressure on the leaside members shall be taken as one-half of the wind pressure
on the windward side members and the factors of safety shall be calculated on
the crippling load of struts and upon the elastic limit of tension members;
(d)
the maximum and minimum temperatures shall be such as the
Government may specify in each case.
(3)
Notwithstanding anything contained in sub-rule (1) and
(2) in localities where overhead lines are liable to accumulation of ice or
snow the Government may, by order in writing, specify the loading conditions
for the purpose of calculating the factor of safety.
Rule - 77.Clearance above ground of the lowest conductor.
(1) No
conductor of an overhead line, including service lines, erected across a street
shall at any part thereof be at a height less than:-
(a) for low and
medium voltage lines |
5.791 Mts.(19
feet) |
(b) for high
voltage lines |
6.069 Mts. (20
feet) |
(2) No conductor
of an overhead line, including service lines, erected along any street shall
at any part thereof be at a height less than:- |
|
(a) for low and
medium voltage lines (b) for high
voltage lines |
5.486 Mts. (18
feet) 5.791 Mts. (19
feet) |
(3) No conductor
of an overhead line including service lines erected elsewhere than along or
across any street shall be at a height less than:- |
|
(a) for low,
medium and high voltage lines up to and including 11,000 volts, if bare (b) for
low, medium and high voltage lines up to and including 11,000 volts, if
insulated (c) for
high voltage lines above11,000 volts |
4.572 Mts. (15
feet) 3.963 Mts. (13 feet) 5.182 Mts. (17
feet) |
(2) For
extra-high voltage lines the clearance above ground shall not be less than
5.182 Mtrs. (17 feet); plus 0.305 Mtrs. (1 feet) for every 33,000 volts or part
thereof by which the voltage of the line exceeds :33,000 volts:
Provided that the
minimum clearance along or across any street shall not be less than (20 Feet)
6.965 meters.
Rule - 78.Clearance between conductors and trolley wires.
No conductor of an
overhead line crossing a tramway or trolleybus route using trolley wires shall
have less than the following clearance above any trolley wire:-
(a) low and
medium voltage |
1.219 Mtrs.
(4feet): |
Provided that
where an insulated conductor suspended from a bearer wire crosses over a
trolley wire the minimum clearance for such insulated conductor shall be (2
feet) 0.6 10 meters.
(b) high voltage
lines up to and including 11,000 volts (6 feet) 1.829 Mtrs. |
|
(c) high
voltage lines above 11,000 volts. lines |
(8 feet) 2.439
Mtrs. (10 feet) 3.408 Mtrs. |
(d) extra-high
voltage lines |
Rule - 79.Clearance from buildings of low and medium voltage lines and service lines.
(1)
Where a low or medium voltage overhead line passes above
or adjacent to or terminates on any building, the following minimum clearance
from any accessible point, on the basis of maximum sag shall be observed:-
(a)
for any flat roof, open balcony, verandah roof, pitched
roof and lean-to-roof-
(i)
when the line passes above the building a vertical
clearance of 2.439 meters (8 ft.) from the highest point or immediately under
the line, and
(ii)
when the line passes adjacent to the building a horizontal
clearance of 1.219 meters (4 feet) from the nearest point.
(2)
Any conductor so situated as to have a clearance less
than that specified in sub-rule (1) shall be adequately insulated and shall be
attached by means of metal clips at suitable intervals to a bare earthed bearer
wire having a breaking strength of not less than (700lbs.) 317.51 Kg. .
(3)
The horizontal clearance shall be measured when the line
is at a maximum deflection from the vertical due to wind pressure.
Rule - 80.Clearance from building of high and extra-high voltage line.
(1) Where
a high or extra-high voltage overhead line passes above or adjacent to any
building or part of a building it shall have on the basis of maximum sag a
vertical clearance above the highest part of the building immediately under
such line, of not less than:
(a) for high
voltage lines up to and including |
|
33,000 volts |
3.658 Mts.
(12ft.) |
(b) for extra
high-voltage line |
3.658 Mts. (12
ft.) plus 0.305 Mts. (1 ft.) for every addl. 33,000 volts or part thereof. |
(2) The
horizontal clearance between the nearest conductor and any part of such
building shall, on the basis of maximum deflection due to wind pressure, be not
less than -
(a) for high
voltage lines up to and including |
|
11,000 volts |
1.319 Mts.
(4ft.) |
(b) for high
voltage lines above 11,000 volts and |
|
up to and including 33,000 volts |
1.529 Mts.
(5fts). |
(c) for
extra-high voltage lines |
1.829 Mtrs. (6
ft.) plus 0.305 Mtrs. (1 foot)-for every additional 33,000 volts or part
thereof. |
Rule - 81.Conductors at different voltages on same supports.
Where conductors
forming parts of system at different voltages are erected on the same supports
the owner shall make adequate provision to guard against danger to lines on and
others from the lower voltage system being charged above its normal working
voltage by leakage from or contact with the higher voltage system, and the
methods of construction and the clearance between the conductors of the two system
shall be subject to the prior approval of the Inspector.
Rule - 82.Erection of or alteration to building.
(1)
If at any time subsequent to the erection of an overhead
line (whether covered with insulating material or bare), any person proposes to
erect a new building or structure, whether permanent or temporary, or to make
in or upon any building or structure any permanent or temporary addition or
alteration he and the contractor be employ to carry out the erection, addition
or alteration shall if such building, structure, addition or alteration would
during or after construction result in contravention of the provisions of rule
79 or 80 give notice in writing of his intention to the supplier, and to an
Inspector and shall furnish therewith a scale drawing showing the proposed
building structure, addition or alteration and scaffolding required during its
construction.
(2)
On receipt of such notice the supplier shall, without
undue delay, so alter the overhead line as to ensure that it will not be
accessible in such a manner as to contravene the provisions of rule 79 or 80
either during or after construction. In the absence of an agreement to the
contrary between the parties concerned, the supplier shall be entitled to
recover from the person from whom the notice was received or from the person
from whom he is entitled to receive such notice the cost of, such alteration
which shall be deemed to include the following items, namely:-
(a)
the cost of additional material used on the alteration;
(b)
the wages of labour employed in effecting the alteration;
(c)
supervision charges to the extent of 15 per cent of item
(b); and
(d)
any charges incurred by the supplier in complying with
the provisions of section 15 in respect of such alteration:
Provided that the
supplier may, before so altering the overhead line, require the person from
whom the notice was received to deposit the estimated cost of such alteration,
which shall in case of dispute be determined by the Inspector.
(3) No
work upon such building, structure, addition or alteration, shall be commenced
until the Inspector has satisfied that neither during nor after construction,
the provisions of rule 79 or 80 will be contravened:
Provided that an
Inspector may, if he is satisfied that the overhead line has been so guarded
as to secure the protection of persons and the property from injury, or risk of
injury, permit to work to be executed prior to the alteration of overhead line
or, in the case of temporary addition or alteration, without the alteration of
the overhead line.
Rule - 83.Clearances general.
For the purpose of
computing the vertical clearance of an overhead line, the maximum sag of any
conductor shall be calculated on the basis of maximum sag in still air and the
maximum temperature as specified by the Government under rule 76 (2) (d).
Similarly for the purpose of computing any horizontal clearance of an overhead
line the maximum deflection of any conductor shall be calculated on the basis
of the wind pressure specified by the Government under rule 76 (2) (a).
Rule - 84.Routes: proximity to aerodromes.
Overhead lines
shall not be erected in the vicinity of aerodromes until the aerodrome
authorities have approved in writing the route of the proposed lines.
Rule - 85.Maximum intervals between supports.
All conductors shall
be attached to supports at intervals not exceeding the safe limits based on the
ultimate tensile strength of the conductor and the factor of safety prescribed
in rule 76:
Provided that in
the case of overhead lines carrying low or medium voltage conductors when
erected in, over, along or across any street the intervals shall not without
the consent in writing of the Inspector exceed 67.056 meters (220 feet).
Rule - 86.Conditions to apply where telecommunication lines and power lines are carried on same supports.
(1)
Every overhead telecommunication line erected on supports
carrying a power line shall consist of conductors each having a breaking
strength of not less than 272.16 Kg. (600 lbs).
(2)
Every telephone used on a telecommunication line erected
on support carrying a Power line shall be suitably guarded against lighting and
shall be protected by cut-outs.
(3)
Where a telecommunication line is erected on supports
carrying a high or extra-high voltage power line arrangement shall be made to
safeguard any person using the telephone against injury resulting from contact
leakage or induction between such power and telecommunication lines.
Rule - 87.Lines crossing or approaching each other.
(1)
Where an overhead line crosses or is in proximity to any
telecommunication line the owner of the overhead line shall protect it in a
manner laid down in the code of practice of the power and telecommunication
co-ordination committee.
(2)
When it is intended to erect a telecommunication line
which will cross or be in proximity to an overhead line the person proposing to
erect such telecommunication line shall give notice in writing of his intention
to the owner of the over head line and the owner of the overhead line shall
within twenty-one days of receiving such notice, provide the protection
referred to in sub-rule (1).
(3)
Where an overhead line crosses or is in proximity to an
overhead line belonging to another person, the owner of the line which was last
erected shall so protect it as to guard against the possibility of its coming into
contact with the other overhead line.
(4)
A person erecting or proposing to erect an overhead line
may require the owner of the other overhead line to provide the protection'
referred to in sub-rule (3) within twenty-one days of the receipt of the notice
in that behalf.
(5)
In all cases referred to in the preceding sub-rules, the
expenses of making the guarding arrangement shall be borne by the persons whose
line was last erected.
(6)
Where two lines cross, the crossing shall be made as
nearly at right angle as the nature of the case admits.
(7)
The guarding arrangement shall ordinarily be carried out
by the owner of the supports on which it is made and he shall be responsible
for its efficient maintenance.
(8)
All work required to be done by or under this rule shall be
carried out to the satisfaction of the Inspector.