Joint Electricity Regulatory Commission For
The Ut Of Jammu & Kashmir And The Ut Of Ladakh (Distribution Code)
Regulations, 2023
[29th November 2023]
In
exercise of the powers conferred on it by Section 181 (1) and 181 (2) read with
Section-14 of the Electricity Act 2003 (Act No. 36 of 2003) (hereinafter
referred to as "the Act"), and all powers enabling it in that behalf
including sub-ordinate legislation, rules, statutory orders, resolutions,
clarifications issued by the Government in terms of the Act, the Joint
Electricity Regulatory Commission for the UT of Jammu & Kashmir and the UT
of Ladakh hereby makes the following Regulations to enforce standards with
respect to Quality, Continuity and Reliability of service by the licensees.
CHAPTER 1 GENERAL
Regulation - 1.
1.1. Short Title, Commencement,
Extent, and Interpretation :-
(1)
These
regulations shall be called the Joint Electricity Regulatory Commission for the
UT of Jammu & Kashmir and the UT of Ladakh (Distribution Code) Regulations,
2023.
(2)
These
Regulations shall come into force from the date of its publication in the
official gazette.
(3)
These
Regulations shall extend to the UT of Jammu & Kashmir and the UT of Ladakh.
1.2. Definitions :-
1.2.1. :-
In
these regulations, the following words and expressions shall, unless the
subject matter or context otherwise requires or is inconsistent therewith, bear
the following meanings:
(a)
"Act"
means the Electricity Act, 2003 (Act no. 36 of 2003);
(b)
"Agreement"
means an agreement entered into by the Distribution Licensee and the User;
(c)
"Apparatus"
means electrical apparatus and includes all machines, fittings, accessories and
appliances connected to the Electrical Distribution System;
(d)
"CBIP"
means Central Board of Irrigation and Power;
(e)
"CEA"
means Central Electricity Authority;
(f)
"Circuit"
means an arrangement of conductor(s) for the purpose of conveying electrical
energy and forming a system or a branch of a system;
(g)
"Commission"
means the Joint Electricity Regulatory Commission for the UT of Jammu &
Kashmir and the UT of Ladakh;
(h)
"Conductor"
means any wire, cable, bar, tube, rail or plate used for conducting energy and
electrically connected to the system;
(i)
"Connected
Load" means the aggregate of the manufacturers rating of all energy-consuming
apparatus duly wired and connected to the power supply system of the licensee
including portable apparatus in the consumers premises. This shall not include
the load of spare plugs, sockets, load exclusively installed for firefighting
purposes. A load of either water and room heating or room cooling apparatus,
whichever is higher, shall be taken into account as per prevailing season (1st
April to 30th September for cooling use and 1st October to 31st March for
heating use). The definition of connected load shall be used only for the
purpose of assessment in case of direct theft or dishonest abstraction of
energy or unauthorized use of energy;
(j)
"Control
Person" means a person identified as having the technical capability and
responsibility for cross-boundary safety;
(k)
"DCR"
means Distribution Code Review;
(l)
"DCRP"
means Distribution Code Review Panel;
(m)
"Embedded"
means having a direct electrical connection to an intra-state electrical
system;
(n)
"Extra
High Tension (EHT)" means a voltage of 33000 Volts and above under normal
conditions subject to the percentage variation permissible under the Indian
Electricity Rules 1956;
(o)
"GSS"
means Grid Sub-station;
(p)
"High
Tension (HT) or High Voltage (HV)" means the voltage between 650 volts and
33000 Volts under normal conditions subject to the percentage variation
permissible under the Indian Electricity Rules 1956;
(q)
"Indian
Standards (IS)" means those Standards and specifications approved by the
Bureau of Indian Standards;
(r)
"Interface
Point/Connection Point/Boundary Point" means a point at which a Users
electrical system is connected to the Licensees Distribution System;
(s)
"Low
Tension (LT) or Low Voltage (LV)" means the voltage of 230 volts between
phase and neutral or 400 volts between any two phases under normal conditions
subject to the percentage variation permissible under the Electricity Rules;
(t)
"Power
Factor" means the ratio of Active Power (kW) to Apparent Power (KVA);
(u)
"PTW"
means a permit to work;
(v)
"REC"
means Rural Electrification Corporation;
(w)
"Transmission
System" means the system consisting of extra high voltage electric lines
being operated at EHT (excluding generator interconnection facilities) owned
and/or operated by the Transmission Licensee for the purposes of the
transmission of electricity from one power station to a sub-station or to
another power station or between sub-stations or to or from any external
interconnection equipment up to the interconnection with the distribution
system, any plant and apparatus and meters owned or used by the Transmission
Licensee in connection with the transmission of electricity, but shall not
include any part of the Licensee distribution system;
(x)
"User"
means any person having electrical interface with, or using the Distribution
System of the Distribution Licensee to whom this Code is applicable. Any other
Distribution Licensee, Transmission Licensee, and generating units connected to
the Distribution system are also included in this term;
1.2.2. :-
Words
and expressions used and not defined in this Code but defined in the Acts shall
have the meanings assigned to them in the said Acts. Expressions used herein
but not specifically defined in these regulations or in the said Acts but
defined under any law passed by a competent legislature and applicable to the
electricity industry in the state shall have the meaning assigned to them in
such law. Subject to the above, expressions used herein but not specifically
defined in these regulations or in the Acts or any law passed by a competent
legislature shall have the meaning as is generally assigned in the electricity
industry;
1.3. Abbreviations :-
1.3.1. :-
Abbreviations
used in these regulations are listed and explained in the list of abbreviations
annexed to these regulations as Annexure 5.
1.4. Introduction :-
1.4.1. :-
The
Distribution Code deals with technical aspects of the supply of electricity,
which have an impact on the quality, continuity, and reliability of service by
licensees and the use of the Licensees Distribution System for the distribution
of electricity. It specifies the rights and obligations of the Distribution
Licensee and the Users in system planning and operation.
1.4.2. :-
The
Distribution Code is not exhaustive as to the requirements to be complied with
by the Distribution Licensee and the Users connected or seeking connection to
the Licensees Distribution System. The Distribution Licensee and all
Users/Consumers must also comply with the requirement as laid down in various
codes, standards, and regulations under relevant laws in force.
1.5. Objectives :-
The
main objectives of this Distribution Code are
(a)
To
ensure the development and maintenance of an efficient, coordinated, and
economical distribution system and the distribution licensee and all
distribution system participants comply with respective obligations as provided
in the Act, and
(b)
To
bring together a set of rules, for using the distribution network and to
provide-
(i)
The
technical aspects of the working relationship between the licensees
distribution system and to those connected and seeking connection to it,
(ii)
The
facilitation of operation, maintenance, development, and planning of an
economical and reliable power distribution network.
(iii)
Safety
and protection parameters to be followed by the Distribution Licensees and
Users.
1.6. Applicability :-
1.6.1. :-
These
Regulations shall apply to all distribution licensees and the consumers of
electricity.
1.6.2. :-
These
regulations shall be interpreted and implemented in accordance with and not at
variance from, the provisions of the Electricity Act, 2003 read with the Indian
Electricity Rules, 1956 and any Central Electricity Authority regulations in
this regard.
1.6.3. :-
These
Regulations shall be applicable to all Distribution System participants
including;
(a)
Distribution
Licensee(s) including deemed licensees;
(b)
Open
Access consumers connected to the Distribution System;
(c)
Entities
covered under proviso 8 of Section-14 of the Act;
(d)
Bedded
Generators;
(e)
All
Consumer categories as defined under the Retail Supply Tariff Order.
1.7. Implementation :-
1.7.1. :-
The
distribution licensee shall be responsible for the implementation of the
Distribution code.
1.7.2. :-
Nothing
contained in this Code should be interpreted as imposing obligations/duties on
Consumers/ Distribution Licensees greater or more onerous than those mentioned
in the Electricity Act, 2003 under relevant clauses.
1.7.3. :-
The
Distribution Code contains procedures for the management of day-to-day technical
situations in the Distribution System, taking into account a wide range of
operational conditions likely to be encountered under both normal and abnormal
conditions. The Distribution Code cannot foresee all the possible operating
conditions. Users must therefore understand and accept that the Distribution
Licensee, in such unforeseen circumstances, may be required to act decisively
and with due expedition to discharge his obligations under the License. Users
shall provide such reasonable co-operation and assistance as the Distribution
Licensee may require in such circumstances. The concerned Distribution Licensee
shall however refer all such cases for ratification in to the
"Distribution Code Review Panel."
1.8. Confidentiality :-
Under
the terms of the Distribution Code, the Distribution Licensee will receive
information from Users relating to their business. The Distribution Licensee
shall not, other than as required by Distribution Code, disclose such
information to any other person without the prior written consent of such
informant unless required by Central/State government departments or any
authority.
1.9. Compliance :-
Non-compliance
with any provision of the Distribution Code by the Distribution Licensee shall
attract the consequences as provided in the Acts or in the License. However, in
the event of non-compliance with the Distribution Code, the Distribution
Licensee shall prepare and submit to Commission a plan of action for compliance
with the Distribution Code. Commission may exempt the Licensee from compliance
of any provisions for a particular period, if it is found that the compliance
is not feasible for such period, considering the resources available and the
circumstances prevailing.
1.10. Procedures to settle disputes
:-
In
the event of any dispute regarding the interpretation of any regulations
provided in the Distribution Code between any User and the Distribution
Licensee, the matter shall be referred to the Commission, and the decision of
the Commission shall be final and binding on both the parties.
CHAPTER
2 MANAGEMENT OF DISTRIBUTION CODE
Regulation - 2.
2.1. Objective :-
The
chapter defines the method of managing the Distribution Code, pursuing of any
changes/ modifications required, and the responsibilities of the Distribution
Licensees and the Users/ Consumers in this regard. This section facilitates
revisions taking into account the views of all parties in an equitable manner.
2.2. Distribution Code Review Panel
:-
2.2.1. :-
A
standing body called Distribution Code Review Panel (DCRP) shall be constituted
by Commission comprising of the representatives of the Distribution Licensee as
well as the Users of the Distribution System in line with the provisions of the
Distribution Code.
2.2.2. :-
The
chairperson and members except the secretary shall be part-time members of the
panel. The review panel shall generally consist of the following members who
have the knowledge and practical experience of technical matters related to the
electricity supply by utilities. The commission shall nominate the chairperson
and secretary of the Distribution Code Review Panel on a rotation basis from
among the members of the Distribution Licensees, but at no point of time, the
chairperson and secretary shall belong to the same Distribution Licensee. The
secretary shall be a full-time member of the Review Panel. The members of the review
panel shall be as follows:
(a)
One
senior technical officer from each Distribution Licensee not below the rank of
Executive Engineer.
(b)
One
Member from Transmission Utility or SLDC.
(c)
One
Member from a Transmission Licensee to represent all Transmission Licensees.
After the tenure is over for such a Member, the representative of a different
Transmission Licensee (if operational in the region) will be a member of the
review panel.
(d)
One
Member from among Captive Power Plants, co-generation units, thermal power plants,
and renewable energy plants, to represent all such users in the UT of Jammu
& Kashmir and the UT of Ladakh.
(e)
Open
Access Customers connected to the Distribution Systems.
(f)
One
member each representing Industrial, Agricultural, Domestic, and Commercial
Consumers.
(g)
Such
other members as the Commission may direct and find appropriate.
(h)
Commission
shall develop a list of potential candidates to serve on the Distribution Code
Review Panel, which reflects a balance of the various interest groups in
consultation with the Distribution Licensee.
2.2.3. :-
The
members of the Review Panel shall normally have a tenure of two years unless
he/she ceases for any reason to be a member of the Review Panel. The
Chairperson of the Review Panel with the approval of the Commission shall
jointly consider the replacement of such members.
2.2.4. :-
The
functioning of the panel shall be coordinated by the secretary of the Review
Panel.
2.2.5. :-
Commission
shall publish the names of the members of the Review Panel and also inform the
same to each of the Distribution Licensee(s).
2.2.6. :-
The
model code of the functioning of the Review Panel shall be finalized at the
first meeting the of Review Panel.
2.3. Functions of the review panel
:-
The
functions of the Review Panel shall be:
(a)
Maintenance
of the Distribution Code and its working under continuous scrutiny and review.
(b)
Consideration
of all requests for review made by any User and publication of their
recommendations for changes in the Distribution Code together with reasons for
such changes.
(c)
Provide
guidance on the interpretation and implementation of the Distribution Code.
(d)
Examination
of the problems raised by any User as well as resolution of the problems.
(e)
Ensuring
that the changes/modifications proposed in the Distribution Code are consistent
and compatible with standard technical manuals or guidelines, codes, laws,
acts, rules, and regulations in force at that point of time.
2.4. Review and Revisions :-
2.4.1. :-
The
Users seeking any amendment to the Distribution Code shall send written
requests to the secretary of the Review Panel with a copy to Commission. If the
request is sent to the Commission directly, the same shall be forwarded to the
secretary of the Review Panel who shall, in consultation with the concerned
entities and such other persons as the Commission may direct, review the
Distribution Code provisions.
The
secretary will circulate the proposed changes/modifications to all the panel
members for their written comments within a reasonable time frame or the
secretary may call for the Review Panel meeting in consultation with the
chairperson. Based on this interaction/ discussion, the necessary amendments/
revisions may be incorporated into the Distribution Code after the approval of
the Commission.
2.4.2. :-
The
secretary shall send the following reports to the Commission at the conclusion
of each review meeting of the panel:
(a)
Reports
on the outcome of such review.
(b)
Any
proposed revision to the Distribution Code and its rationale.
(c)
All
written representations and objections submitted by the Users at the time of
review.
2.4.3. :-
All
revisions to the Distribution Code require the approval of the Commission. The
secretary shall publish revisions to the Distribution Code, after the approval
of the Commission. The Review Panel may also submit proposals for relaxation in
such cases where Users / Distribution Licensees have difficulties in meeting
the requirements of the Distribution Code.
2.4.4. :-
Any
changes from the previous version shall be clearly marked in the margin. In
addition, a revision sheet shall be placed at the front of the revised version,
noting the number of every changed Sub-section, together with reasons for such
change.
2.4.5. :-
The
secretary shall maintain copies of the Distribution Code incorporating the
latest amendments and shall make it available at a reasonable cost to any
person requiring it.
2.4.6. :-
The
Commission, may, on the application of the licensee or otherwise, call the
emergency meeting of the review panel as and when the situation so dictates and
make such alterations and amendments in the Distribution Code as it thinks fit.
CHAPTER
3 DISTRIBUTION PLANNING CODE
Regulation - 3.
3.1. Objectives :-
The
following are the objectives of the Distribution Planning Code:
(a)
To
enable the planning, design and construction of the Distribution System for a
safe and economical operation with the specified degree of reliability
conforming to the following standards:
(i)
Distribution
System Planning and Security Standard.
(ii)
Provisions
applicable to Distribution System under Power System Management and Operating
Standard and Power System Safety Standard as prescribed by the authority under
Electricity Act 2003.
(iii)
Statutory
Acts and Rules, which are in force,
(iv)
Relevant
Indian Standard Specifications, if applicable. The deviations may be permitted
as per specified limit; however, in any case, the security and safety shall not
be hampered.
(v)
REC
(Rural Electrification Corporation) Construction Standards and manuals.
(b)
To
facilitate the use of the Distribution System by any User connected to or
seeking connection with it,
(c)
To
prescribe the technical conditions to be followed by the respective
Distribution Licensees and Users in meeting the standards for an efficient
operation of the common electrical interface,
(d)
To
prescribe the procedure for the exchange of the system planning data between
the Distribution Licensee and the Users,
(e)
To
provide the required information to the Users for connection, planning, and
development of their own systems and make them compatible with the Distribution
System,
(f)
To
enable the Distribution Licensee to co-operate with the STU in furnishing the
required data as detailed in the Central / State Grid Code as the case may be.
3.2. Planning Policy :-
3.2.1. :-
The
Distribution Planning Code specifies the technical & design criteria and
procedures to be followed by the Distribution Licensee for proper planning and
development of the Distribution System. This Code is also applicable to the
Users of the Distribution System for their planning and development so far as
they affect the Distribution System.
3.2.2. :-
The
requirement of the Users may necessitate the extension or reinforcement of the
Distribution System. In some cases, the same may even require the Distribution
Licensee to seek the extension or reinforcement to the capacity of the
Transmission System at the Connection Point/ Interface Point. This may arise
for a number of reasons mentioned below, but not limited to the same:
(a)
A
development by any User in his system already connected to the Distribution
System;
(b)
Introduction
of a new Connection Point/ Interface Point between the Users System and the
Licensees System;
(c)
To
increase the capacity of the Distribution System for meeting the security
standards, removal of constraints in operation, etc., and accommodate a general
increase in Demand;
(d)
Introduction
of distributed renewable energy sources, battery storage, electric vehicles and
charging infrastructure, etc.
3.2.3. :-
The
development of the Distribution System must be planned sufficiently in advance
allowing adequate time to obtain the required statutory clearances, consents or
way leaves, the detailed engineering, design and construction work to be
carried out and completed. The suitable management techniques shall be
implemented allowing for sufficient time for critical activities and to
co-ordinate all the activities in an efficient manner. These shall be taken
care of at the time of planning itself.
3.3. Load Data :-
3.3.1. :-
The
Distribution Licensee shall develop load curves for the area fed by the
concerned substation of the Transmission Licensee from the metering data
available at the Connection Point/ Interface Point. Such data shall be compiled
for the entire Area of Supply combining the load curves of each substation
feeding its Distribution System. The Distribution Licensees shall collect data
and map the power factor of the network (feeder-wise as well as consumer
category wise by installing meters on typical distribution transformers.)
3.3.2. :-
The
actual energy drawn by the Distribution System as recorded in the energy meters
installed at Connection Points / Interface Points shall be reconciled with the
actual energy sales in the overall Area of Supply. The aggregate distribution
losses computed from these data shall be furnished to the Commission at the
time of filing for tariff petition every year.
3.3.3. :-
All
the Users with Demands of 1 MW and above seeking connection shall furnish their
load data/characteristics of the load and other relevant details to the
Distribution Licensee as detailed in Annexure 1.
3.3.4. :-
The
embedded generators connected with the Distribution System and seeking new
connections shall furnish planning data in the format specified in Annexure 2.
3.3.5. :-
The
Distribution Licensee shall exercise special care to monitor the actual
development of loads in respect of Consumers desiring to avail loads of 1 MW
and above at a single point. The Distribution Licensee on his part shall
furnish relevant data for designing and selecting the electrical equipment,
details of metering and relay for purpose of protection and System data as
detailed in Annexure 3, if required by the user seeking connection to his
Distribution System. The Distribution Licensee shall update the system data
regularly and at least once a year.
3.4. Forecast Methodology :-
3.4.1. :-
The
Distribution Licensee shall formulate a short-term demand forecast (to enable
the State Transmission Utility (STU) or SLDC in drawing down the annual planning
process corresponding to a 5 years forward annual plan for intra state
transmission system). This shall be formulated after considering the previous
financial year as a base and projecting the demand for the succeeding 5 years,
considering the overall development of various sectors in his Area of Supply in
succeeding five years. He should follow prudent practices to arrive at load
forecast for succeeding five years after considering all the aspects viz.
government policy/ economic development etc. During this process he shall also
review the status of loads materializing as per the previous load forecast.
Further these forecasts shall be in line with the plan to be developed at
national level by CEA. The variation to the forecast shall be incorporated by the
Distribution Licensee, as and when it is known to Distribution Licensee and
revise the forecast annually.
3.4.2. :-
Energy
sales in each tariff class shall be projected in the forecast period over the
corresponding figures relating to the base year by adopting an appropriate
statistical method.
3.4.3. :-
The
projections shall take into account the assumed normal growth for non-specific
loads, specific and identified loads of 1 MW and above, and the effects of
demand side management, if any, and energy conservation.
3.4.4. :-
The
peak load requirements at each Connection Point/ Interface Point shall be
estimated. The peak load requirement at each Connection Point / Interface Point
will essentially ensure that the Transmission Utility or SLDC may determine the
corrective measures to be taken to maintain the capacity adequacy in the
Transmission System up to the Connection Point /Interface Point. This will
facilitate the Transmission Utility (STU) to develop the compatible
Transmission System. However, if the Distribution Licensee receive power at a
number of Connection Points / Interface Points in a compact area, which are
interconnected in a ring, then such Distribution Licensee shall forward the
overall short-term Demand forecast at each Connection Point / Interface Point
with the variation or tolerance as mutually discussed and agreed upon with the
Transmission Utility.
3.4.5. :-
The
aggregate energy and peak load requirements for the Area of Supply shall be
estimated. The Distribution Licensee shall forward the short-term demand
forecast for each Connection Point/ Interface Point for peak load requirement
as well as aggregate energy and peak load demand for Area of Supply on annual
basis to the Transmission Utility (STU) and Commission along with the following
details on the basis of which the forecast is made:
(a)
Data,
(b)
Methodology,
(c)
Assumptions.
3.4.6. :-
It
shall be the responsibility of all the Distribution Licensees to fully
co-operate with the Transmission Licensees in preparation of demand forecasts
for their area of supply. The Distribution Licensee shall furnish the necessary
peak load and energy forecasts to the Transmission Utility (STU) for a period
succeeding 5 years and submit the same annually by 31st March to STU in order
to enable Transmission Utility or SLDC in formulating the perspective plan, as
detailed out in the applicable (State Grid Code) Regulations, enforce.
3.4.7. :-
The
licensee shall supply whole system data to the transmission Utility (STU) and
other distribution system participants on the formats as devised by the STU
under the applicable (State Grid Code) Regulations, enforce.
3.5. Technical and Design Criteria
:-
The
Distribution Licensee shall plan and develop his Distribution System on the
basis of the following technical and design criteria:
(1)
The
load demand of all the existing Users connected to the Distribution Licensees system
and all Users seeking connection with the Distribution Licensees system shall
be taken into consideration. All the Apparatus and Circuits shall have adequate
capacity to cater to their needs of electricity in a safe, economical and
reliable manner.
(2)
The
Distribution Licensee shall assess and forecast the load demand of each
category of Consumers in his Area of Supply on annual basis or more frequently
as decided by the Commission.
(3)
The
Distribution Licensee shall have a thorough knowledge of the nature of
electricity usage by the Consumers and the way they use electrical energy and
other alternative sources of energy in his area. The load forecasting shall
take into account all these along with other conservation programs and the
demand side management or off-peak usage programs which the Licensee may
sponsor, resulting in reduction of energy used and peak demand of the Consumers
over the years.
(4)
The
Distribution Licensee shall implement an appropriate load forecast program for
the systematic collection of data describing Consumers energy usage patterns
and analysis of these data for energy and demand forecast. For this purpose,
the Consumers shall be divided into all the tariff categories and may be
broadly in the following classes:
(a)
Domestic
category;
(b)
Non-Domestic
category;
(c)
Commercial
category;
(d)
Agricultural
category;
(e)
Industrial
category; and
(f)
Any
other Tariff category as determined by the Commission in the Retail Supply
Tariff Order.
The
pattern of energy consumed by each sector and the load demand, the period of
peak demand etc., shall be determined on the basis of sample surveys taking
representative samples from each sector for its different seasonal
requirements.
A
suitable questionnaire shall be prepared for these sample surveys and the data
obtained shall be analyzed using suitable statistical models. Based on this,
distribution licensee shall be implementing demand side management techniques
to match the availability from time to time.
(5)
The
load forecast program shall assess the following:
(a)
Demand
at the time of system peak, daily, monthly, seasonal or annual,
(b)
Hourly
demand for the day of the system peak, monthly, seasonal or annual,
(c)
Total
energy consumption for each category by month, season or year.
(6)
Based
on the results of the above analysis the load forecast shall be made using the
appropriate modern forecasting tools wherever applicable.
(7)
The
optimum Circuit loading and the maximum number of Circuits at any electrical
interface between the Distribution and Transmission Systems shall conform to
the Distribution System Planning and Security Standards as mentioned under
Chapter-4 of this code, Distribution System under Power System Management and
Operating Standard and Distribution System under Power System Safety Standard
as prescribed by authority under Electricity Act 2003.
(8)
As
far as practicable, separate Circuits shall be provided for the following:
(a)
Urban
non-industrial power supply,
(b)
Urban
industrial power supply,
(c)
Rural
supply -:
(i)
Agricultural
Supply,
(ii)
Non
- Agricultural Supply
(9)
The
loads shall be arranged as far as possible in discrete load blocks to
facilitate load management during emergency operations.
(10)
Load
flow and other system studies shall be conducted to locate the position of
outlets from substations, capacitor installations, distribution transformers,
and to contain voltage variation and energy losses within reasonable limits.
(11)
The
following parameters of equipment and system designs shall be standardized to
facilitate easy replacement and reduction of inventories of spares in stores:
(a)
Capacities
of power transformers,
(b)
Capacities
and designs of distribution transformers,
(c)
Substation
/ Switching Station layouts,
(d)
Pole
mounted substations,
(e)
Sizes
of bus bars,
(f)
Capacities
and ratings of circuit breakers and instrument transformers,
(g)
Earthing,
(h)
Lightning
arresters,
(i)
Control
panels,
(j)
Station
batteries,
(k)
Fire
extinguishers.
(l)
Maintenance
tools
(m)
Safety
equipment
(n)
Energy
meters
(o)
Wires
and accessories
(p)
Insulators
and accessories
(12)
The
planning of the Distribution System shall always keep in view the cost
effectiveness and reduction in energy losses without sacrificing the
requirements of Security Standards and Safety Standards for the Distribution
System.
(13)
The
Distribution Licensee shall plan the Distribution System expansion and
reinforcement keeping the following in view along with all other measures to
accommodate the advancement in technology prevailing at the time:
(a)
Economic
ratio of HT and LT line lengths,
(b)
Use
of aerial bunched conductors,
(c)
Underground
cables,
(d)
Optimizing
the number of distribution transformers and their location at the electrical
load centers.
3.6. Energy Audit :-
3.6.1. :-
The
Distribution Licensee shall create responsibility centers for energy audits.
They shall compute the month/year-wise distribution losses and prepare the
energy balance sheets for their respective areas.
3.6.2. :-
The
Distribution Licensee shall establish and maintain a system for the segregation
of technical and commercial losses through energy audits. Interface meters with
a data retaining capacity of at least 45 days shall be installed for all the
incoming/outgoing feeders in the area identified for each such unit.
3.6.3. :-
The
Distribution Licensee shall carry an out energy audit of his total system
compiling the data and analysis carried out in each responsibility center in
the best possible manner. The energy received from each substation shall be
measured at the 11 KV terminal switchgear of all the outgoing feeders installed
with appropriate energy meters such that the energy supplied to each feeder is
accurately available. It shall be compared with the corresponding figures of
monthly energy sales and the distribution loss for each feeder shall be worked
out. In case the Distribution Licensee has adopted the ring main system at 11KV
and there is difficulty in determining the distribution losses for each feeder,
then the Distribution Licensee shall work out distribution losses for the
overall Area of Supply.
3.6.4. :-
An
action plan for the reduction of losses with adequate investments and suitable
improvements in governance shall be drawn up and shall be submitted to the
Commission annually with the Annual Revenue Requirement filing. The
distribution licensee shall follow the provisions given under "The Bureau
of energy efficiency (Manner and Intervals for the Conduct of Energy Audit in
Electricity Distribution Companies) Regulations, 2021, and its amendments for
conducting energy audits in regular intervals and submit the necessary reports
to the Commission.
CHAPTER
4 DISTRIBUTION SYSTEM PLANNING AND SECURITY STANDARD
Regulation - 4.
4.1. Objective :-
The
Distribution System Planning and Security Standard specifies the guidelines for
the planning methodology of the Distribution System. The scope of this standard
covers:
(a)
Quality
of power supply
(b)
Load
forecast
(c)
Planning
procedure.
(d)
Service
area of a distribution network.
(e)
Planning
standards.
(f)
Reliability
analysis.
(g)
Standardization
of design of distribution transformer
(h)
Standardization
of substation layouts
(i)
Reactive
Compensation
(j)
Service
Mains
(k)
Metering
Cubicles
(l)
Security
Standards
4.2. Quality of power supply :-
(a)
Frequency:
The rated frequency shall be 50 Hz. All the constituents of the Power System
shall make all possible efforts to ensure that the grid frequency remains
within the bandwidth of 49.9Hz -50.05 Hz or as notified by the CERC through
amendments in the Indian Electricity Grid Code.
(b)
Voltage:
- The voltage at any point of the system under normal operating conditions
shall not depart from the declared voltage by more than the values specified
under IS Specifications.
(c)
Harmonic
content: - As per IEEE recommendations, the total harmonic content in the
supply voltage for sensitive loads shall not exceed 5 percent, with any single
harmonic content not exceeding 3 percent.
The
respective User responsible for generating harmonics and affecting the
distribution system shall be responsible for corrective action.
4.3. Load Forecast :-
4.3.1. :-
The
Distribution Licensee shall prepare a rolling short-term load forecast annually
for a period of five years in his Area of Supply duly estimating the probable
load growth and the consumption pattern of the Consumers. The forecast thus
made shall be updated every year depending on the actual load that has come in
that year and the changes in assumption, if any, required for the next years.
4.3.2. Preliminary Load
Estimation/Assessment :-
(a)
Domestic
and Commercial Loads: The consumption in domestic and commercial sectors shall
be estimated on the basis of the number of Consumers and their specific
consumption. The past growth rate in the number of Consumers in the area shall
be studied. In cases where power shortages have been experienced in the recent
past, the growth rate to be adopted shall take into consideration the
appropriate demand-making due allowance in the growth rate to account for the
increased tempo of household electrification envisaged in the future. The
higher level of electrification planned in the area should be kept in view.
Energy consumption per Consumer shall be estimated after studying past trends
and taking into account the anticipated improvements in the standard of living.
(b)
Public
Lighting and Water Works: The estimates of electricity consumption in public
lighting and water works shall be based on the average consumption per kilowatt
of connected load, projected on the basis of trends, keeping in mind the likely
increase in public lighting and water supply facilities. The number of hours of
operation shall be estimated taking into account the past trends and the power
cuts if any affected the area.
(c)
Agricultural
Loads: The power requirement for irrigation pump sets shall be based on the
program of energization of pump sets in the plan period, available resources,
and the ultimate ground water potential. The average capacity of pump sets
shall be worked out considering the mid-year figures for connected load and the
number of pump sets. The consumption per IP set per year shall be estimated by
means of representative sample studies till all the IP sets are metered.
(d)
Industrial
Loads: The power requirements for the industrial sector shall be estimated
under the following three categories, viz.
(i)
L.T.
Industries;
(ii)
H.T.
Industries with a demand of less than 1 MW;
(iii)
H.T.
Industries with a demand of 1 MW & above.
The
consumption in category (i) & (ii) shall be on the basis of historical data
duly considering the developments in future. In case of category (iii), the
projection shall be made separately for each industrial unit on the basis of
the information furnished by the industrialists and the Department of
Industries.
(e)
Non-industrial
Bulk Supply: The available data regarding the consumption of bulk supply to
nonindustrial Consumers such as research establishments, port trusts, military
engineering services, supply to power projects etc., and the probable future
developments in these areas, shall be considered for the forecast.
(f)
Other
Loads: For other loads, the projections shall be based on the best Judgment.
4.4. Load Forecast Procedure :-
4.4.1. :-
Load
forecasting methods using the above data and relevant indices by adopting one
of the suitable methods applicable to specific locations and prevailing
conditions shall be adopted.
4.4.2. :-
In
addition to the above, the effects of demand side management, requirement of
power for pending applications, the increase in demand due to improvement in
the operating frequency close to 50 Hz shall also be estimated. The
Distribution Licensee shall work out Peak Demand for each of the succeeding
five years relating to Connection Point/ Interface Point with the Transmission
System as well as the annual Energy Demand and Peak Demand for each of the
succeeding five years for overall Area of Supply on the basis of Load forecast.
However, if the Distribution Licensee receive power at a number of Connection
Points / Interface Points in a compact area, which are interconnected in a
ring, then such Distribution Licensee shall forward the overall short-term
Demand forecast at each Connection Point / Interface Point with the variation
or tolerance as mutually discussed and agreed upon with the Transmission
Utility or SLDC.
4.4.3. :-
The
diversity factor of each category of Consumers fed in the Area of Supply shall
be worked out by installation of load survey meters at selected typical
locations. A record of such data shall be maintained and continuously updated.
The short-term load forecast for a period of five years, based on these data
shall be prepared.
4.5. Planning Procedure :-
The
Distribution System shall be planned and developed in such a way that the
system should be capable of catering the requirement of all categories of
Consumers with a safe, reliable, economical and quality supply of electricity
as indicated in clause 2.0 of this section. However, the Consumer shall extend
full support to the Distribution Licensee to enable the Distribution Licensee
for quality supply of electricity. The Distribution System shall conform to the
statutory requirements of all the relevant code, standards and acts in force.
4.6. Planning Standards :-
4.6.1. Standardization of Sizes and
Ratings :-
Adequate
provision for future load development shall be made while selecting the sizes
of power conductors and rating of distribution transformers. The sizes of power
conductors, insulators, lightning arresters, transformers, switchgear, etc.
used in the Distribution System shall be standardized with the objective of
reducing inventory and standard specifications shall be prepared.
4.6.2. Design Criteria for
Distribution Lines :-
(1)
Radial
system of distribution can be adopted in rural areas and as far as possible
loop system with provision for feeding from at least one alternate source shall
be adopted in urban areas.
(2)
The
HT and LT distribution lines shall be any of the following types according to
the necessity at the required area.
(a)
Over-head
line with bare conductors;
(b)
Over-head
line with Aerial Bunched Cables;
(c)
Under-ground
Cables.
(3)
In
thickly populated cities, in areas having heavy traffic densities, underground cable
installation shall be considered to the extent possible. Wherever a number of
trees are encountered, either in residential locations or in gardens and
forests, over-headlines with aerial bunched cables shall be adopted. In other
places over- headlines with bare conductors shall be adopted. The following
standards shall be adopted for planning and design purposes:
(a)
The
design and construction of over-headlines with bare conductors shall be
generally in accordance with IS 5613 Part I, sections 1 and 2.
(b)
Vertical
configuration of conductors for LT distribution lines, to prevent accidental
short circuit due to galloping of conductors, shall preferably be adopted in
rural areas since the spans are large in such areas.
(c)
The
maximum length of LT and HT lines shall be maintained within the prescribed
limit so as a safe and quality power may be delivered.
(d)
The
design and construction of over-headlines with aerial bunched cables shall be
generally in accordance with REC Specifications 32 and IS 14255.
(e)
The
design and construction of under-ground cables shall be generally in accordance
with IS 1255.
(4)
The
line supports can be of steel, wood, RCC or PCC. The RCC and PCC poles are
preferred over the other two considering their cost and longer life. The choice
of the size of conductor for a line shall be made based on the following
criteria:
(a)
Power
to be transmitted and the techno-economic studies conducted for selecting the
size of conductor according to the cost of loss of power and the interest and
depreciation charges on the cost of the conductor thus selected;
(b)
Length
of Line;
(c)
Line
Voltage;
(d)
Permissible
voltage regulation;
(e)
Mechanical
strength;
4.6.3. Standardization of Design and
Rating of Distribution Transformers :-
(1)
The
design and rating of distribution transformers shall be standardized. As an
initial step, the various technical parameters required for the design shall be
incorporated in the specifications based on the experience on performance
gained among the various designs so far adopted. Later, standard designs of the
transformers and their detailed construction drawings shall be evolved based on
the performance of these transformers. These shall be adopted for future
procurement. This also ensures the interchangeability of components of similar
transformers manufactured by any manufacturer.
(2)
A
good quality assurance plan shall be aimed at the following:
(a)
Good
quality of raw materials;
(b)
Quality
control during manufacturing and routine tests;
(c)
Acceptance
tests at the time of taking delivery;
(d)
Inspection
and tests on transformers received at stores on random sampling;
(e)
Thorough
test on one transformer in a lot selected at random. The transformer should be
completely dismantled. The qualities of core, coil, insulation etc. are
physically inspected and samples of insulation and other components used etc.,
are tested.
(f)
Ensuring
performance guarantee for all distribution transformers for a minimum period of
3 years.
4.6.4. Standardization of
Sub-Station Layouts :-
The
Distribution Licensee shall develop standard layouts following relevant
standards, manuals, and provisions of the Electricity Act, 2003. The Licensee
shall also adopt the latest technology as well as feedback from the experience
gained.
4.6.5. Reactive Compensation :-
(1)
Shunt
capacitors un-switched/switched type, shall be installed at the appropriate
places in the Distribution System for power factor improvement, maintaining a
satisfactory voltage profile, and reduction of sub transmission and
Distribution losses. The size and location of the capacitor installations shall
be determined using an appropriate program, with reliable field data. Suitable
precautionary measures, such as automatic switching, etc, shall be adopted to avoid
over voltage at light load periods.
(2)
Optimization
studies of shunt compensation shall be conducted by the Distribution Licensee
to determine the most appropriate sizes and locations for shunt capacitor
installations.
4.6.6. Service Area of a Distribution
Network :-
(1)
The
service area of a distribution network is an area in which the load is supplied
by a substation by one or more number of feeders, as required. The distribution
network fed from the distribution transformers and the substations from which
the 11 kV feeders emanate shall be initially planned as independent networks
within their respective service areas. Further, wherever possible, provision
shall be made for interconnection with adjacent networks and/or substations for
an alternate supply in case of failure. The design of distribution lines shall
incorporate features to enable their augmentation in future, with minimum
interruption to power supply. The existing right of way shall be fully
exploited.
(2)
The
Distribution Licensee shall take suitable measures, sufficiently in advance, to
augment the capacity of the feeders in the event the voltage regulation limit
is exceeded within the area.
(3)
Appropriate
software to compute the design of the distribution network shall be used to
obtain lowest possible energy losses for different loading conditions for the
following:
(a)
The
location and the capacity of the distribution transformers;
(b)
Routing
of LV and HV networks;
(c)
The
sizes of conductors;
(d)
The
ratio of the lengths of HT and LT distribution lines for the new lines planned
shall be optimized and the existing Distribution System shall be modified in a
phased manner to reduce the distribution losses.
(e)
The
voltage regulation limits for all loading conditions.
4.6.7. Service Mains :-
The
service mains to Consumers shall be laid in accordance with relevant REC
Construction Standards for 230 V single phase and 400 V three phase supply and
shall conform to the provisions of Relevant Rules under Electricity Act, 2003.
4.6.8. Metering Cubicles :-
(1)
The
metering for 230 V single-phase supply shall be provided on a suitable board,
located in such a place protected from sun and rain and shall be in a
convenient position for taking readings. The terminals of the meter shall be
made tamper-proof and sealed. For 400 Volts three phase supply, the meters and
associated metering equipment including connections shall be enclosed in a
suitable tamper-proof box. The tamperproof box shall be of sufficient strength
and design with locking and sealing devices and shall have adequate provision
for heat dissipation with the required electrical clearances. The design shall
permit readings to be taken without access to the meter or its connections.
(2)
For
HT Consumers the meters, maximum demand indicators, and secondary connections, shall
be housed in a separate compartment and other secondary apparatus such as
instrument transformers and connections required shall be housed in a separate
metering compartment, which shall be locked / sealed to prevent tampering.
(3)
The
HT metering cubicle shall be suitable for cable entry on both sides or at least
on one side. No fuses are permitted in the secondary circuits of the instrument
transformers. The metering cubicle shall be painted with suitable epoxy paint
for installation in areas experiencing heavy rainfall. The instrument
transformers shall be of fixed ratio and shall not have any taps. The primary
current rating of the current transformers shall match with the normal full
load current and the saturation point of the core shall be higher than the
maximum current that may occur due to simultaneous full load operation of all
the connected equipment and machinery.
(4)
For
EHT Consumers, the secondary terminals of the instrument transformers shall be
locked and sealed and the secondary wires brought out in a suitable GI conduit
pipe up to the metering panel. There shall be no joints in the conduit pipes.
The meters shall be as close to the instrument transformers as possible and in
no case shall exceed ten (10) meters. The metering panel shall be housed in a
weather proof and tamper proof box and sealed.
4.7. Reliability Analysis :-
4.7.1. :-
The
planning of the extension and improvement to a Distribution System shall also
take into consideration the improvement in reliability of power supply to Consumers.
The appropriate reliability indices of power supply in the area fed by the
Distribution System before and after the implementation of the extension and
improvement program shall be estimated. The planning of the distribution system
shall also take into consideration the improvement in reliability and efforts
should be made to collect the data in this regard.
4.7.2. :-
The
provisions of the Joint Electricity Regulatory Commission for The UT of Jammu
& Kashmir and the UT of Ladakh (Standard of Performance for Distribution
Licensees) Regulations, 2023 as amended from time to time for determining the
Reliability indices of power supply to the Consumers shall be adhered to by the
licensees.
4.7.3. :-
The
following factors, which affect reliability indices, shall be considered
subject to availability of data:
(a)
Momentary
incoming supply failures
(b)
Momentary
interruptions on 33 and 11 kV feeders
(c)
Feeder
wise affected consumers
(d)
Breakdown
on LT feeders
(e)
Prearranged
shutdowns on lines and feeders
(f)
Blowing
out of distribution transformer fuses
(g)
Individual
fuse off calls
4.8. Standing committee for design,
construction and maintenance practices :-
4.8.1. :-
Standing
Committee for design, construction and maintenance practices shall under the
chairmanship of the Technical Member/Director of the licensee be constituted by
the licensee, within one-month w.e.f. the commencement of this Code and shall
comprise of-
(a)
the
senior most Engineer (Planning) of the licensee
(b)
the
senior most Engineer (Materials Management) of the licensee
(c)
the
senior most Engineer (Design and Planning) of the STU; and
(d)
any
other person as the licensee may deem appropriate.
4.8.2. :-
The
Standing Committee shall be an advisory body having perpetual term and shall
hold its meeting at least once in each quarter. The Standing Committee shall
suggest and make recommendations to the licensee on matters amongst others in
the following areas: -
(a)
to
review and suggest the latest practices on design and technical specifications
of line materials, meters and metering equipment, service line materials,
sub-station equipment like transformers, circuit breakers, CT/PT sets etc.;
(b)
to
suggest vendor selection and short-listing procedures for various equipment and
materials being used in bulk;
(c)
to
suggest best industry practices and innovative techniques for construction,
operation, and maintenance of HT / LT lines and Grid Substations, Pole mounted
and other plinth-mounted substations etc.;
(d)
to
recommend and suggest the latest technology upgradation and process such as IT
tools and SCADA and other Control System;
(e)
to
recommend embargo and restrictions on dangerous, unhygienic practices and
material from point of view of safety, environmental upkeep and pollution
norms.
4.9. Security Standards :-
4.9.1. :-
The
Distribution System shall be planned and maintained so as to fulfill the
following security standards except under Force Majeure conditions beyond the
reasonable control of the Distribution Licensee.
4.9.2. :-
The
feeders, either HT or LT, feeding important loads such as hospitals,
crematoria, airports, railway stations, and the like shall be planned to have a
selective switching system, so that selective switching can be operated to
transfer the load on to an alternate healthy feeder. Appropriate safety
precautions shall invariably be taken in this regard. In case of failure of the
feeder, these switches shall be operated immediately either manually or
automatically depending on the importance of the load.
4.9.3. :-
The
feeders connected to important industries which are very sensitive to
interruption of even short duration shall be planned to have automatic
switchover to an alternate healthy feeder in case of failure of supply.
4.9.4. :-
Loading
in any current carrying component of the Distribution System (e.g., Conductors,
joints, transformers, switchgear, cables and other apparatus) shall not exceed
75% of their respective thermal limit.
4.9.5. :-
The
rupturing capacity of the switchgear employed in the system shall have at least
25% more capacity than the short circuit level computed even considering the
anticipated future development of the system.
4.9.6. :-
Provision
shall be made for every HT feeder, either primary or secondary, to manually
switch over to the immediately available HT feeder of the same voltage class
available in the vicinity. Provision shall be made in the design itself for any
HT feeder to share at least 50% of the loads in the adjacent feeder during
emergencies.
4.9.7. :-
In
case of single contingency; failure of any substation equipment controlling any
outgoing 11 kV feeder, the load interrupted shall not generally exceed 50% of
the total demand on the substation. The Distribution Licensee has to bring it
down to 20% within a period of three years.
4.9.8. :-
There
shall be adequate stand by capacity in the system.
4.9.9. :-
The
design of the Distribution System shall accommodate the arrangements in such a
way that the electricity supply need not be interrupted for more than the
specified duration as per Joint Electricity Regulatory Commission for The UT of
Jammu & Kashmir and the UT of Ladakh (Standard of Performance for
Distribution Licensees) Regulations, 2023 as amended from time to time of the
Licensee in case of breakdown of any distribution transformer. Similarly, in case
of failure of 11 kV feeders including terminal equipment, the design shall
accommodate an arrangement for the power supply not to be interrupted to the
extent possible.
4.10. Construction Practices :-
4.10.1. :-
All
electric supply lines and apparatus shall be of sufficient ratings for power,
insulation and estimated fault current and of sufficient mechanical strength,
for the duty, which may be required to be performed under the environmental
conditions of installation, and shall be constructed, installed, protected,
worked and maintained in such a manner as to ensure the safety of human beings,
animals and property.
4.10.2. :-
The
relevant Code of Practices of the Bureau of Indian Standards, REC Standard,
including the National Electrical Code, if any, may be followed. The material
and apparatus used shall conform to the relevant specification of the Bureau of
Indian Standards where such specifications have been already laid.
4.10.3. :-
The
licensee and the User shall prepare and observe the Construction and
Maintenance Manuals for various equipment/works for HT / LT Lines and Grid /
Switching sub-stations. The Construction and Maintenance Manual shall be
prepared to take into consideration the following:
(a)
Technical
Standards for construction of electrical plants, electric lines, and
connectivity to the grid specified by the Central Electricity Authority under
Clause (b) of section 73 of the Electricity Act 2003;
(b)
Safety
requirements for construction, operation, and maintenance of electrical plants and
electric lines specified by the Central Electricity Authority under Clause (c)
of section 73 of the Act;
(c)
REC
Construction Standards and Standard Design Layouts;
(d)
CBIP
Publications on Code of Practices;
(e)
Code
of Practices issued by the Bureau of Indian Standards for various equipment and
maintenance practices; and
(f)
Instruction
Manuals for installation, operation, and maintenance issued by the standard
equipment manufacturer concerned.
4.10.4. :-
The
standard tables for conductor size, fuse size, wire gauge, electrical
clearance, ground wire size, insulation resistance and earth resistively etc.
shall be included in the Construction and Maintenance Manuals. The licensee
shall ensure that its construction and maintenance staff strictly observe these
Manuals. The copy of Construction and Maintenance Manuals shall be furnished to
the Commission.
4.11. Preventive Maintenance
Schedule and Inspection Manual :-
4.11.1. :-
The
licensee and the User shall prepare a Preventative Maintenance Schedule and
Inspection Manual for various line and sub-station equipment installed in
distribution system.
4.11.2. :-
The
Preventive Maintenance Schedule and Inspection Manual shall cover the
following: -
(a)
Recommended
Schedule for inspection;
(b)
Recommended
Schedule for preventive maintenance; and
(c)
Recommended
Schedule for overhauling.
4.11.3. :-
The
inspection schedule and preventive maintenance schedule shall have daily,
weekly, monthly, quarterly and annual periodic activity, to be carried out for
various equipment.
4.12. Maintenance Records :-
4.12.1. :-
The
licensee as User shall maintain records of periodic inspections carried out in
the standard formats prescribed in the Preventive Maintenance Schedule and
Inspection Manual.
4.12.2. :-
Periodic
testing of all the equipment such as transformers, switchgear, protective
relays, etc., should be carried out as recommended by the manufacturer and the
relevant Code of Practices issued by the Bureau of Indian Standards and the
CBIP. These shall be carried out at fixed intervals and the test results shall
be recorded in the maintenance registers. Wherever the test results indicate a
decline in the insulation resistance and/or deterioration of the equipment,
preventive maintenance shall be carried out to ensure serviceability, safety,
and efficiency.
4.12.3. :-
The
licensee shall maintain well-trained hot-line maintenance personnel with all
the required tools in good condition and conduct maintenance work by using the
hot-line technique, wherever possible, to reduce period of interruption.
4.12.4. :-
The
consumers shall maintain their apparatus and power lines at all times
conforming to the Electricity Rules, and these shall be suitable for connection
to the distribution system in a safe and reliable manner.
4.13. Energy Conservation :-
4.13.1. :-
The
licensee, in order to minimize the overall requirement, energy conservation and
Demand Side Management (DSM), shall accord high priority to ensure compliance
with the Energy Conservation Act, 2001 and shall adhere to the guidelines of
the Bureau of Energy Efficiency along with the provisions of the applicable
(Demand Side Management) Regulations, enforce.
4.13.2. :-
The
licensee shall ensure that the periodic energy audits, wherever made compulsory
for power-intensive industries under the Energy Conservation Act, 2001 are
complied with by its consumers. Other industrial consumers may also be
encouraged to adopt energy audits and energy conservation measures.
4.13.3. :-
In
the agriculture sector the licensee shall promote the pump sets and the water
delivery system engineered for high efficiency. In the industrial sector, the
licensee shall take action for promoting energy-efficient technologies as
energy conservation measures. Motors and drive systems are the major sources of
high consumption in the agricultural and industrial sectors. The licensee shall
encourage the consumers use high-efficiency motors in the agricultural and
industrial sectors. The licensee shall take effective steps so that
energy-efficient lighting technologies are adopted in industries, commercial
and domestic establishments.
CHAPTER
5 CONNECTIVITY CONDITIONS
Regulation - 5.
5.1. Objectives :-
The
Connectivity Conditions are provided to ensure that:
(a)
The
basic rules for connections are compiled by all agencies. This will help to
treat all agencies in a nondiscriminatory manner.
(b)
Any
new or modified connection, when established, shall not suffer unacceptable
effects due to its connection to the Distribution System nor produce
unacceptable effects on the system or any other connected agency.
(c)
The
ownership and responsibility for all the equipment shall be clearly specified
in a schedule (site responsibility schedule) for every site, where a connection
is made.
(d)
The
Connectivity Conditions specify the minimum technical and design criteria,
which shall be complied with any agency connected to, or seeking connection to
the Distribution System. The Distribution Licensee shall ensure compliance of
the above criteria by any agency as a pre-requisite for the establishment of an
agreed connection. The connectivity conditions should fulfill the requirement
stipulated in sections 50 and 53 of the Electricity Act, 2003, and provisions
of the Joint Electricity Regulatory Commission for the UT of Jammu &
Kashmir and the UT of Ladakh (Electricity Supply Code) Regulations, 2023.
5.2. Operational Labeling :-
The
Licensee and the Consumers shall be responsible for the provision and
maintenance of clear, unambiguous signs and labels indicating the numbering and
/ or name of the equipment/apparatus and circuit at the substations and
connection sites. The equipment installed shall confirm to its relevant I.S
specification and the ratings and salient specification shall be maintained on
the equipments nameplate.
No
electrical equipment shall be used without its manufacturers nameplate
permanently affixed to it. In the event of such discrepancies observed, the
same shall be treated as per the pertinent section of the Electricity Act,
2003.
5.3. System Performance :-
5.3.1. :-
The
design and construction of all the equipment connected to the Distribution
System shall satisfy the relevant Indian Standard Specifications. In case of
equipment for which the Indian Standard Specifications do not exist, the
appropriate IEC, IEEE or other International Standards shall apply.
5.3.2. :-
Installation
of all electrical equipment shall comply with the rules and code of practice in
force.
5.3.3. :-
For
every new connection sought, the Distribution Licensee shall specify the
Connection Point/ Interface Point and the supply voltage, along with the
metering and protection requirements as specified in the "Metering and
Protection code" under section - 7 of this code.
5.3.4. :-
The
operation of the Distribution System shall be in accordance with the
"Distribution System Operating Standard" under Power System
Management & Operation Standard as prescribed by authority under the
Electricity Act 2003. The User shall however be subjected to the distribution
discipline prescribed by the SLDC/Distribution Licensee.
5.3.5. :-
The
insulation co-ordination of the Users equipment shall conform to the applicable
Indian Standards/Code of practices. The rupturing capacity of the switchgear
shall not be less than that notified by the Distribution Licensee.
5.4. Connection Point/ Interface
Point :-
5.4.1. :-
Connection
to Transmission System shall be governed by the relevant clauses of the Central
/ State Grid Code as the case may be.
5.4.2. Connection of Small
Generators (not below 1MW) to the Distribution Systems :-
Bus
bars may be provided at the Generating station. All generating units shall
inject the output into the bus bars via the synchronizing breaker. The isolator
between the synchronizing breaker and the bus bars is the boundary between the
Generator and the Distribution Licensee. The current transformers for the
metering shall be connected near the synchronizing breaker. The voltage
transformers (including the standby set) of the metering shall be connected to
the bus-bars. However, the small generators based on renewable sources of
energy will be allowed for the connection with Distribution System/
Transmission System as feasible and decided by the Commission on a case-to-case
basis.
5.4.3. EHT/HT Consumers :-
The
supply voltage may be 220kV, 132kV, 66kV, 33 kV, 22kV, or 11 kV or the voltage
as agreed by the Distribution Licensee. The substations shall be owned by the
Users. The boundary shall be the feeder entry in the premises of the Users or
when so provided it shall be the bus-bar between breakers of the Distribution
Licensee and the EHT/ HT Consumers.
5.4.4. Low voltage and Medium
Voltage Consumers :-
The
incoming terminal of the cut-out circuit breaker installed by the Consumer is
the boundary of low-voltage and medium-voltage Consumers. The metering shall be
provided before a fuse unit/circuit breaker of the Consumer. The metering
equipment shall be provided at the entry point of Consumer Premises in a safe
location, preferably at the entry of the Premises or in a common passage on the
ground floor for easy access for the purpose of meter reading, maintenance,
repairs, inspection, etc. The metering equipment shall be provided inside a box
sealed by the Distribution Licensee and the User/Consumer shall not disturb the
sealed metering equipment and shall take reasonable care for protecting the
meter and equipment.
5.5. Procedure for Applications for
Connections to The System :-
Any
User seeking use of Distribution System may submit an application for
connection to the Licensee as per the procedures and formats prescribed under
the Joint Electricity Regulatory Commission for the UT of Jammu & Kashmir
and the UT of Ladakh (Electricity Supply Code) Regulations 2023. Prospective
large customers may enclose information as per Annexure - 1.
5.6. Acceptance or Rejection of
Application for Connection :-
The
acceptance or rejection of Consumers application for supply connection shall be
as per the provisions of the Joint Electricity Regulatory Commission for the UT
of Jammu & Kashmir and the UT of Ladakh (Electricity Supply Code)
Regulations 2023.
5.7. Connection Agreements :-
A
connection Agreement of Consumer shall be as per provisions of the Joint
Electricity Regulatory Commission for the UT of Jammu & Kashmir and the UT
of Ladakh (Electricity Supply Code) Regulations, 2023.
CHAPTER
6 OPERATION CODE
Regulation - 6.
6.1. Objectives :-
6.1.1. :-
This
Chapter contains the procedures and practices to be followed for a safe and
efficient operation of the Distribution System by the Distribution Licensee and
by the Users of the Distribution System of their electrical plant and lines
which are connected to the Distribution Licensees system. This shall also apply
to any electrical interface between two Distribution Licensees for a safe and
efficient operation of interface.
6.1.2. :-
The
following aspects of operation are covered in this section:
(a)
Demand
Estimation
(b)
Outage
Planning
(c)
Contingency
Planning
(d)
Demand
Side Management
(e)
Interface
with Small Generating Plant including CPPs
(f)
Operational
Communication
(g)
Monitoring
and Control of voltage, frequency and power factor.
(h)
Safety
Co-ordination.
(i)
Maintenance
and testing
(j)
Tools
and spares
(k)
Human
Resource Development and Training
(l)
Geographical
Information System (GIS)/Global Positioning System (GPS) based information
system
6.2. Demand Estimation :-
6.2.1. :-
The
Distribution Licensee shall estimate the Demand and Energy requirement in
15-minute time blocks at the Transmission-Distribution Interface Points on a
day-ahead/week-ahead/month-ahead basis for their Area of Supply on the basis of
relevant load curves drawn on day ahead basis subject to modifications
depending upon the communication received from any specific User or caused by
any contingency. This may be given to SLDC as may be required.
6.2.2. :-
For
this purpose, the concerned major Users identified by the Distribution Licensee
shall furnish the required data pertaining to the demands of their installation
to him.
6.3. Outage Planning :-
6.3.1. :-
The
Distribution Licensee shall furnish his proposed outage programs to the
Transmission Licensee on a month-ahead basis.
6.3.2. :-
The
outage program shall contain the identification of lines and equipment of the
Distribution System proposed by the Licensee.
6.3.3. :-
The
outage plan proposed by the Licensee shall come into effect only after the
Transmission Licensee releases the finally agreed transmission outage plan.
6.3.4. :-
However,
at the time the line or equipment is taken out of service, the Distribution
Licensee shall intimate the Transmission Licensee to facilitate in
accommodating their maintenance work, which can be carried out under minimum
shutdown period.
6.3.5. :-
The
above procedure shall not apply under the following circumstances:
(a)
Emergency
situations to save plant and machinery;
(b)
In
case of unforeseen emergency situations requiring isolation of lines or
equipment to save human life,
(c)
Where
disconnection is to be effected on any User installation due to breach of
Agreement. In this case, the SLDC shall be informed wherever the load to the
extent of 1 MW or more is affected.
6.3.6. :-
Planned
outages of the Power System for the duration as specified in the Joint
Electricity Regulatory Commission for the UT of Jammu & Kashmir and the UT
of Ladakh (Standard of Performance for Distribution Licensees) Regulations 2023
for maintenance purposes shall be intimated to the public through media
including publishing in at least two largely circulated newspapers (one in
English and one in local language) of that area, two days in advance.
6.4. Contingency Planning &
Crisis Management :-
6.4.1. :-
A
contingency situation may arise in the event of a total or partial blackout in
the Transmission System. A contingency may also arise on a part of the
Distribution System due to local breakdowns in the Distribution System itself.
It may also arise due to a breakdown in the Apparatus of the Transmission
Licensee at the point of interconnection.
6.4.2. :-
Contingency
Planning & Crisis Management procedure shall be documented unambiguously to
achieve restoration of the total system and associated demand and
re-synchronization of parts of the total system that came out of synchronism
with each other, at the shortest possible time.
6.4.3. Transmission System Failure
:-
(a)
In
case of a total blackout at any point in the Area of Supply of the Distribution
Licensee, the Distribution Licensee shall follow the black start procedures
framed by the Transmission Utility (STU)/SLDC.
(b)
The
Distribution Licensee shall sectionalize the Distribution System into discrete
blocks of demand. The Licensee shall advise and co-operate with the SLDC for
the amount of MW load likely to be picked up on switching each demand block.
(c)
The
Distribution Licensee shall prepare a schedule of essential and non- essential
loads in order of priority at each connection to be picked up during the
restoration process.
(d)
The
Distribution Licensee shall ensure and maintain the load generation balance
under the direction of the SLDC.
(e)
The
Distribution Licensee shall maintain direct communication links with the SLDC.
(f)
The
Distribution Licensee shall furnish the names and designations of the person(s)
with their telephone numbers, e-mail IDs, and stations, authorized to deal with
contingency operations, to the SLDC, who shall co-ordinate for restoration
process as per State/ Central Grid Code/ Regulations of the Commission as the
case may be.
6.4.4. Distribution System Failure
:-
(a)
Interruptions
to the power supply in any part of the Distribution System lasting for the
period as specified in the Joint Electricity Regulatory Commission for the UT
of Jammu & Kashmir and the UT of Ladakh (Standard of Performance for
Distribution Licensees) Regulations 2023 and amendments thereof for Licensee
due to breakdown in any part of the Distribution System may be termed as a
Distribution System Failure.
(b)
The
Distribution Licensee shall co-ordinate with SLDC for the restoration process,
which shall be as per provisions of the applicable (State Grid Code)
Regulations, enforce and amendments thereof.
(c)
The
Distribution Licensee shall designate a Nodal Officer to coordinate with SLDC
for Distribution System restoration.
6.4.5. Failure of the Apparatus of
the Transmission Licensee :-
(a)
The
Distribution Licensee shall immediately contact the authorized person at the
substation of the Transmission Licensee, and assess the probable period of
restoration and the probable restriction of load drawl from the affected
substation.
(b)
The
Distribution Licensee shall affect the demand management plan accordingly.
6.5. Demand Side Management (DSM) :-
6.5.1. :-
DSM
should be made an integral part of the day-to-day operations of the
Distribution Licensee with the objective of improving end-use efficiency in the
use of electricity, environmental conservation, and cost reduction.
6.5.2. :-
Promote
and implement Load Shifting, Power Shortage Mitigation, seasonal peak
reduction, cost effective energy savings, lowering the cost of electricity,
reduction in emissions of greenhouse gases, and pricing initiatives i.e., Time
of Use / Seasonal, etc.
6.5.3. :-
Complement
supply-side strategies in order to avoid, reduce or postpone unnecessary
investments in generation, transmission, and distribution infrastructure.
6.5.4. :-
Reduction
of transmission and distribution losses through implementation of end-use
energy efficiency programs in areas reporting high AT&C losses.
6.5.5. :-
Reduce
the environmental damage by reducing the emission of greenhouse gases.
6.5.6. :-
Encourage
consumers to revise their electricity consumption pattern both with respect to
timing and level of electricity demand for efficient use of energy.
6.5.7. :-
Create
awareness about Solar Pumps, Solar Lights, LED lamps etc.
6.5.8. :-
DSM
Plan and Program preparation, submission and approval by the Commission:
(a)
Distribution
Licensee shall formulate a perspective DSM Plan and submit the same to the
Commission for in-principal approval for the specified period and as per the
time lines that may be specified by the Commission from time to time;
(b)
The
perspective DSM plan shall include:
(i)
A
section outlining the goals sought to be achieved in the specified period.
(ii)
Annual
DSM Plan for each year of the perspective plan period containing description of
DSM program proposed to be undertaken and its prioritization along with program
wise details like:
(1)
indicative
cost & its cost effectiveness pursuant to these Regulations and any
guidelines issued by the Commission from time to time;
(2)
indicative
baseline data and expected reduction in tariff and/or gain in energy
efficiency;
(3)
consumer
segments and estimated level of participation;
(4)
implementation
strategy and schedule including process / mechanism for execution e.g., Energy
Service Companies, Bidding for DSM Projects, DSM Resource Acquisition, etc.;
(5)
expected
payback period and mechanism for recovery of cost and performance incentives;
(c)
Mechanism
for Monitoring, evaluation and reporting of perspective plan and annual
plan/programs;
(d)
Programme/Plan
for Training/Seminars/Workshops to increase consumer awareness.
6.6. Interfaces with Small
Generating Units Including CPPs :-
If
the Distribution Licensee has an interface with any generating unit including
CPP and an Agreement for this purpose exists, the Distribution Licensee and the
concerned owner of the generating unit shall abide by the following provisions
in addition to the provisions contained in this Code as applicable to all the
Users:
(a)
The
owner shall provide suitable protection at the interface to protect his system
from any damage due to normal and abnormal conditions in the Distribution
System.
(b)
In
case of induction generator, the owner shall take adequate precautions to limit
the system disturbances, when the induction generator is synchronized in
consent with the Distribution Licensee.
Induction
generators shall be installed with adequate capacitors to compensate the
reactive power drawl. Also, whenever the power factor is found very low during
starting period and causes a voltage dip in the Licensees system the Licensee
may advise the owner to install capacitors and the owner shall comply.
Failure
to comply entails penalty and/or disconnection from the system as per provision
of rules and Acts.
(c)
The
owner shall comply with the provisions of the (State / Central) Grid Code
Regulations of the Commission as the case may be.
6.7. Operational Communication :-
Reliable
communication links viz telephone, email, fax, tele printer, etc. shall be
established for the exchange of data, information, and operating instructions
between the Licensee, Consumer with a demand of 1 MW and above, and the SLDC.
Each constituent shall ensure installation and maintenance of proper
communication infrastructure at his end.
6.8. Monitoring and Control of
Voltage, Frequency and Power Factor :-
6.8.1. :-
The
Distribution Licensee shall monitor the voltage, frequency, and power factors
in the Distribution System at different points at peak and off-peak hours and
take reasonable measures for improvement of the same in coordination with the
Users with the demand of 1 MW and above, and the Transmission Licensee.
6.8.2. :-
The
Distribution Licensee shall take power factor improvement measures at strategic
points in the Distribution System by carrying out system studies and installing
the required reactive compensation equipment.
6.8.3. :-
The
voltage in the Distribution System may vary depending upon the available
generation, system demand, and the configuration of Transmission and
Distribution Systems at any time. Under normal operating conditions the
Licensee shall exercise proper voltage management in the Distribution System
beyond the point of connection with the Transmission System to maintain voltage
at all levels according to the quality of supply mentioned in the Distribution
System Planning and Security Standard as mentioned under Chapter-4 of this
code. The capacitors, wherever available in the Grid substations shall be
operated to maintain reactive compensation to be within acceptable limits of
power factor of at least 0.9 keeping the bus voltage in view.
6.8.4. :-
Users
having loads with high harmonic content, low Power Factor and fluctuations
shall install appropriate correction equipment.
6.8.5. :-
The
Distribution Licensee shall abide by the instructions issued by the SLDC from
time to time on load management for maintaining the frequency of supply within
the specified limits.
6.9. Safety Co-Ordination :-
6.9.1. :-
The
Distribution Licensee and the Users and any other Distribution Licensee having
a common electrical interface with the Licensee shall designate suitable persons
to be responsible for safety coordination.
These
persons shall be referred to as Control Persons. Their designations and
telephone numbers shall be exchanged between all the concerned persons. Any
change in the list shall be notified promptly to all the concerned.
6.9.2. :-
The
Distribution Licensee and such Users shall prepare safety manuals incorporating
all the safety precautions to be taken for each component of the Distribution
System. All the safety rules and precautions shall be observed when work is to
be carried out on any line or apparatus, switchgear, or circuits in any part of
the Distribution System or in any part of the User System. The safety manuals
thus prepared shall be issued to all the control persons and such Users for
compliance.
6.9.3. :-
There
shall be coordination between persons of the Distribution Licensee and the
Users, between persons of two Distribution Licensees having electrical
interfaces, for carrying out the work on any apparatus or lines etc., belonging
to either party at the point of interconnection.
6.9.4. :-
The
provisions of the (State / Central) Grid Code Regulation (as the case may be)
shall be followed at Connection Points/ Interface Points in co-ordination with
the Transmission Licensee.
6.9.5. :-
The
disconnecting device(s) at each electrical interface, which shall be capable of
effectively disconnecting the system of the Distribution Licensee and the other
Users, and the grounding devices of the respective systems at the control
boundary shall be identified and marked by the Licensee and the respective
Users. These shall be maintained in good condition at all times. To prevent
inadvertent switching operations by unauthorized persons, such disconnecting
devices shall be provided with interlocks.
6.9.6. :-
Wherever
any Consumer has installed an emergency power supply system, either an
electronic system with storage batteries or with generators, the arrangement
shall be such that the same cannot be operated without clearly isolating the
system from the supply mains. The responsibility of making the required
arrangement for isolation from supply mains shall be of the User and this shall
be part of the electrical layout submitted to Electrical Inspector for his
approval. The possibility of a feedback from these devices to the Distribution
System from any of the conductors, including the neutral conductor shall be
clearly ruled out.
6.9.7. :-
The
appropriate Control Person at the electrical interface shall issue written
permission to his counterpart for carrying out the work on any apparatus,
switchgear or lines beyond the electrical interface. Such permissions shall be
termed as "Permit to Work" (PTW). The format for PTW shall be
standardized by the Distribution Licensee and shall be used by all concerned.
6.9.8. :-
The
Distribution Licensee in consultation with the concerned User shall frame
checklist of operations to be carried out and the procedures for safety
coordination for each electrical interface, before issue and return of PTWs.
Such procedures and checklists shall be issued to all the concerned by the
Licensee for implementation.
6.10. Maintenance and Testing :-
6.10.1. :-
The
Distribution Licensee shall prepare maintenance schedules for lines and
equipment to meet the level of maintenance as required in the
"Distribution System under Power System Management and Operating
Standard" and "Distribution System under Power System Safety Standard
".
6.10.2. :-
Regular
testing of all the equipment, such as transformers, switchgear, protective
relays etc., should be carried out as recommended by the manufacturers and the
relevant code of practices issued by the Bureau of Indian Standards and CBIP.
These shall be carried out at the prescribed intervals and the test results
shall be recorded in the maintenance registers. Wherever the test results
indicate a decline in the insulation resistance and/or deterioration of the
equipment, preventive maintenance shall be carried out to ensure
serviceability, safety and efficiency.
6.10.3. :-
The
Distribution Licensee shall maintain well trained hot-line personnel, and all
the required tools in good condition, and conduct the maintenance work by using
hot-line technique, wherever possible, to reduce the period of interruption.
6.10.4. :-
The
Users shall maintain their Apparatus and Power Lines at all times conforming to
I.E. Rules 1956 which are in force for time being and will be replaced by new
rules made under Electricity Act, 2003 and shall be suitable for being
connected to the Distribution System in a safe and reliable manner.
6.11. Tools and Spares :-
6.11.1. :-
The
Distribution Licensee shall ensure the availability of proper tools and tackles
at workplaces for carrying out maintenance. The tools and tackles shall be
checked from time to time and their serviceability shall be ensured.
6.11.2. :-
The
Distribution Licensee shall maintain an inventory of spares required for
maintenance and replacement purposes at suitable locations according to a clear
policy to be laid down by the Licensee.
6.12. Human Resource Development and
Training :-
The
Distribution Licensee shall make appropriate arrangements for imparting
training to the workmen and supervisory staff, incorporating up-to-date
techniques of Distribution System design, construction and maintenance, safety,
consumer services etc. The Licensee shall frame a suitable syllabus for this
purpose.
6.13. Geographical Information
System (GIS) / Global Positioning System (GPS) based information system :-
6.13.1. :-
The
Distribution Licensee shall, in stages, deploy GIS/GPS based Geographical
Facilities Information System for planning operation and maintenance of
distribution system. The GIS shall be utilized for mapping the all-important
elements of distribution system which includes lines, transformers, substations,
generating stations, all unit locations and shall eventually covers all
consumers. The GIS shall be linked to active relational database management
system (RDBMS) and GPS shall be utilized for time synchronization.
6.13.2. :-
The
digital maps of distribution network shall be developed for each of the
following preferably by conducting GPS survey which is easier, fast, accurate
and economical:
(a)
33
kV network of complete distribution system indicating distance, type and size
of conductor /size of Under Ground (UG) cable with single core or 3 core for
lines and sub-station particulars with Single Line Diagram (SLD).
(b)
The
feeder-wise 11 kV lines/cables indicating distance, type and size of conductor
/UG cable, location and capacity of distribution transformers.
(c)
The
distribution transformer-wise L.T. line/cables with a number of consumers and
connected load of each of L.T. support/L.T. feeder pillar Box.
CHAPTER
7 METERING AND PROTECTION CODE
Regulation - 7.
7.1. Objectives :-
The
Chapter specifies the procedure for metering in Distribution System with
respect to operational metering as well as tariff and commercial metering. This
section also specifies the general guidelines for protection of Distribution
system.
Provided
that the licensee shall abide by the CEA (Installation and Operation of Meters)
Regulations 2006 and amendments thereof.
7.2. Operational Metering :-
The
minimum requirement of operational metering at Distribution System substations
shall be as follows:
(a)
Grid
substation
·
66 / 33 kV bus voltage
·
33 / 22 / 11 kV bus voltage
·
66 / 33 / 22 / 11 kV incoming / outgoing current in each phase and each
circuit.
·
Power transformer primary and secondary currents in each phase of every
transformer.
·
HT outgoing feeder current in each phase for each feeder.
·
Power factor in each HT feeder.
·
Load survey meters having a memory duration of at least 45 days for all the
incoming and outgoing feeders.
·
Facility to record energy in MWH and frequency at intervals of 15 minutes at
point of connection with Transmission Licensee.
(b)
Users
System with Demand of 1 MW and above
·
Voltage
·
Current
·
Load
·
Power Factor
·
Energy
7.3. Tariff and Commercial Metering
:-
7.3.1. :-
Tariff
metering shall be provided at each point of interconnection between the
Distribution and Transmission Systems in accordance with the Central / State
Grid Code as the case may be and the Transmission Services Agreement thereof.
7.3.2. :-
Tariff
metering shall be provided at the Connection Points/ Interface Points between
the Users system and the Distribution System and shall be governed by the
provision in the Distribution Services Agreement.
7.3.3. :-
All
the meters, instrument transformers (CT/PT), metering cubicles and testing
procedures shall conform to the relevant Indian Standard Specification and
relevant provision made under the Electricity Act, 2003.
7.3.4. :-
The
CT/PT deployed for metering of energy supplied to the Consumers shall be of class
0.2 accuracy. However, in case of rating of instrument transformers in service,
which are of 0.5 class, which may continue to be used. These shall also conform
to relevant IEC or IS specifications. On failure, the same shall be replaced by
a suitable CT/PT of 0.2 class accuracy after exhausting the CT/PT of 0.5 class
accuracy (as available in their inventory). It is desirable that the
Distribution Licensee shall purchase new CT/PT of 0.2 class accuracy.
7.3.5. :-
The
open access consumer, generating company, Distribution licensee and traders
shall provide Meters, as may be specified by the Commission for such consumer
based on voltage, point and period of supply and tariff category as also
incorporated in the applicable (State Grid Code) Regulations, enforce.
7.4. Measurement of Energy
Import/Export :-
7.4.1. :-
The
Distribution Licensees shall install the following meters for all of their
sub-transmission lines connecting the generating stations, and substations for
the measurement of energy import/export from each Connection Point/ Interface
Point, energy generated in generating units and energy consumed in power
stations and substations:
(a)
Active
energy imports.
(b)
Active
energy export.
(c)
Reactive
energy imports.
(d)
Reactive
energy export.
Each
metering point associated with the determination of energy exported or
imported, between the Generating Companies, Transmission Licensees and
Distribution Licensees shall be provided with both main and check meters. The
minimum standard of accuracy of these meters shall be of accuracy class 0.2.
These
meters shall conform to the relevant IEC or IS specifications.
7.4.2. :-
All
the instrument transformers used in conjunction with commercial (tariff)
metering shall also be of accuracy class 0.2 and conform to the relevant IEC or
IS specifications. The rating shall be suitable for catering the burdens of
lead wires and metering. However, in case of rating of instrument transformers
in service, which are of 0.5 class, which may continue to be used. These shall
also conform to relevant IEC or IS specifications. On failure, the same shall
be replaced by suitable CT/PT of 0.2 class accuracy after exhausting the CT/PT
of 0.5 class accuracy (as available in their inventory). It is desirable that
the Distribution Licensee shall purchase new CT/PT of 0.2 class accuracy.
7.4.3. :-
Data
collection shall be used to integrate impulses from meters over each
integration period as per the agreement, store values, and transmit the same to
the data collection system of the Distribution Licensee. Data shall be
collected from both the main and check metering schemes.
7.4.4. :-
Voltage
failure relays shall be provided to initiate an alarm on loss of one or more
phases of the voltage supply to the meter.
7.4.5. :-
Main
and check meters shall be provided at all Connection Points/ Interface Points.
All the meters shall be tested and calibrated according to the guidelines
provided in the relevant IEC/IS specifications at least once a year and also
whenever the difference in readings between the main and check meters exceed
0.5%.
7.4.6. :-
Records
of these calibrations and tests shall be maintained for reference.
7.4.7. :-
The
Generating Companies, Transmission Licensees and Distribution Licensees shall
formulate and agree upon a procedure covering summation, collection and
processing of tariff meter readings at various interconnection sites of their
area. Whenever necessary, these procedures can be revised.
7.4.8. :-
The
ownership, responsibility of maintenance and testing of these meters shall be
as mutually agreed to between the Users and the concerned Licensees.
7.4.9. :-
The
term Meter shall include Current transformers, voltage/potential transformers,
wiring between them and meter box/panel.
7.5. Protection System :-
7.5.1. :-
No
item of electrical equipment shall be allowed to remain connected to the system
unless it is covered by the appropriate protection aimed at reliability,
selectivity, speed, and sensitivity. The Distribution Licensees shall cooperate
with the Transmission Licensee to ensure correct and appropriate settings of
protection to achieve effective, discriminatory isolation of faulty
line/equipment within the time target clearance specified by the Transmission
Licensee.
7.5.2. :-
Protection
settings shall not be altered, or protection bypassed and/or disconnected
without consultation and agreement of all the affected Users. In case the
protection has been bypassed and/or disconnected by agreement due to any cause,
the same should be rectified and protection restored to normal condition as
quickly as possible. If agreement has not been reached, the electrical
equipment shall be isolated forthwith.
7.5.3. :-
The
settings of protective relays for 33 kV, 22 kV and 11 kV lines shall be such
that a fault in any section does not affect the section between the generating
unit and the faulty section under all conditions. The Transmission Licensee
shall notify the initial settings and any subsequent changes to the Users from
time to time. Routine checks on the performance of the protective relays shall
be conducted and any malfunction shall be noted and corrected as soon as
possible. Short circuit studies required for deciding the relay settings shall
be conducted by the Licensee with the data collected from the Transmission Licensee
and the Users. Representatives of the Generating Companies, Transmission
Licensees and Distribution Licensees shall meet periodically to discuss such
malfunctions, changes in the system configuration, if any, and possible revised
settings of relays.
7.5.4. :-
The
Transmission Licensee shall be responsible for arranging periodical meetings
between the Generating Companies and the Distribution Licensees to discuss the
coordination of protection. The Transmission Licensee shall investigate any
malfunction of protection or other unsatisfactory protection issues. The
concerned Licensees shall take prompt action to correct any protection
malfunction or other unsatisfactory protection issue as discussed and agreed to
in these periodical meetings.
7.5.5. :-
All
generating units and all associated electrical equipment of the Generating
Company connected to the Distribution System shall be protected by adequate
protection, as per CBIP manual, so that the system does not suffer due to any
disturbances originating at the generating unit.
7.5.6. Distribution System :-
For
Power Transformers of HV class in the Distribution System, differential
protection shall be provided for 10 MVA and above along with backup time lag
over current and earth fault protection with directional feature for parallel
operation. Transformers of 1 MVA and above but less than 10 MVA shall be
protected by time lag over current and earth fault. In addition, all power
transformers shall be provided with gas operated relays, winding and oil temperature
alarm and protection.
7.5.7. Distribution lines :-
All
the 33 kV, 22 kV and 11 kV lines at Connection Points / Interface Points shall
be provided with a minimum of over current and earth fault relays as follows:
(a)
Plain
radial feeders: Non-directional time lag over current and earth fault relays
with suitable settings to obtain discrimination between adjacent relay
settings.
(b)
Parallel/ring
feeders: Directional time lag over current and earth fault relay.
7.6. Fire Protection :-
All
adequate precautions shall be taken and protection shall be provided against
fire hazards to all apparatus in the System conforming to the relevant Indian
Standard Specifications and/or provisions under other relevant rules as amended
from time to time.
CHAPTER
8 CROSS BOUNDARY SAFETY CODE
Regulation - 8.
8.1. Objective :-
8.1.1. :-
The
objective of this section is to achieve an agreement on the principles of
safety when working across a control boundary between the Distribution Licensee
and the Users.
8.1.2. :-
This
chapter specifies the requirements for safe working practices for the
maintenance of equipment associated with cross-boundary operations and lays
down the procedure to be followed when the work is carried out on electrical
equipment connected to another Users System.
8.1.3. :-
User
may mean another Licensee so that this Code applies for safety across the
boundary between two Licensees also, by substituting "another
Licensee" for User.
8.2. Control Persons and their
Responsibility :-
The
Distribution Licensee and all the Users (comprising Generation Companies,
Transmission Licensees and consumers having load above 1MW or dedicated line)
shall nominate suitably authorized and technically qualified persons to be
responsible for the co-ordination of safety across their boundary. These
persons shall be referred to as "Control Persons".
8.3. Procedure :-
8.3.1. :-
The
Distribution Licensee shall issue a list of Control Persons with their names,
designations, addresses, telephone numbers and email IDs, to all the Users
having direct control boundary with him. This list shall be updated promptly
whenever there is any change of Control Person or details as shared in the
list.
8.3.2. :-
All
the Users such as mentioned in 8.3.1 having a direct control boundary with the
Distribution Licensee shall issue a similar list of their Control Persons to
the Licensee. This list shall be updated promptly whenever there is any change
of Control Person or details as shared in the list.
8.3.3. :-
Whenever
any work across a cross boundary is to be carried out by the User or the
Distribution Licensee, the Control Person of the User or the Licensee as the
case may be, who has to carry out the work, shall directly contact his
counterpart. Code words shall be agreed to at the time of work to ensure the
correct identification of both parties. Contact between Control Persons shall
normally be made by direct telephone or through emails.
8.3.4. :-
If
the work extends beyond one shift, the Control Person shall hand over charge to
the relief Control Person and fully brief him on the nature of the work and the
code words in the operation.
8.3.5. :-
The
Control Persons shall cooperate to establish and maintain the precautions
necessary to be taken for carrying out the required work in a safe manner. Both
the established isolation and the established earth shall be kept in locked
positions wherever such facilities exist, and these shall be clearly
identified.
8.3.6. :-
The
Control Person in charge of the work shall satisfy himself that all the safety
precautions to be taken are established before commencing the work. He should
issue the safety documentation to the working party to allow the work to
commence.
8.3.7. :-
After
the completion of the work, the Control Person in charge of the work being
carried out should satisfy himself that the safety precautions taken are no
longer required, and shall make a direct contact with his counterpart Control
Person and request removal of the safety precautions. The equipment shall be
declared as suitable for return to service only after confirmation of removal
of all the safety precautions, by direct communication, using the code word
contact between the two Control Persons, and the return of agreed safety
documentation from the working party.
8.3.8. :-
The
Distribution Licensee shall develop an agreed written procedure for Cross
Boundary Safety and continuously update the same.
8.3.9. :-
Any
dispute concerning Cross Boundary Safety shall be resolved at the level of
transmission licensee, if transmission licencsee is not a party. In case where
transmission licensee is a party, the dispute shall be referred to the
Commission for resolution of the dispute.
8.4. Special Considerations :-
8.4.1. :-
All
the equipment on Cross Boundary Circuits, which may be used for the purpose of
safety coordination and establishment of isolation and earthing, shall be
permanently and clearly marked with an identification number or name being
unique to the particular sub-station. This equipment shall be regularly inspected
and maintained in accordance with the manufacturers specifications.
8.4.2. :-
Each
Control Person shall maintain a safety log either hand written in Register(s)
or in soft copy through office PCs. The information should be maintained in
chronological order of all operations and messages relating to the safety
co-ordination sent and received by him.
8.4.3. :-
As
far as possible each of the Distribution Licensees shall maintain an updated
map of his system pertaining to the area fed by each substation.
CHAPTER
9 INCIDENT/ACCIDENT REPORTING
Regulation - 9.
9.1. Objective :-
This
Chapter covers procedure of major incident / accident reporting (which occur in
Distribution System) by User to Licensee and Licensee to User and Commission.
9.2. Major Incident or Accident
Reporting :-
9.2.1. :-
The
Distribution Licensee shall send a preliminary report to the Commission on all
significant Incidents in the Licensees Area of Supply, which results in
interruption to service, substantial damage to equipment or loss of life or
significant injury to human beings within one week of its occurrence followed
by a detailed report within one month.
9.2.2. :-
The
Distribution Licensee and the Users shall establish a format and procedure for
exchange of information.
9.2.3. :-
The
Users shall furnish information to the Distribution Licensee regarding any
major incident occurring in their Systems promptly.
9.3. Reporting Procedure :-
9.3.1. :-
All
reportable incidents occurring in the lines and equipments of 11 kV and above
substations shall be promptly communicated orally by the Licensee whose
equipment has experienced the incident, to all other significantly affected
Users identified by the Distribution Licensee and the Transmission Licensee.
The
Distribution Licensee should submit a written report to the Transmission
Licensee within one hour of such oral communication. If the reporting incident
is of major nature, the written report shall be submitted within two hours duly
followed by a comprehensive report within 48 hours of the submission of the
initial written report. In other cases, the reporting Distribution Licensee
shall submit a report within five working days to the Transmission Licensee.
9.3.2. :-
The
Transmission Licensee shall call for a report from the Distribution Licensee(s)
on any reportable incident affecting other Users and particularly in cases
where such User whose equipment might have been a source of the reportable
incident and does not report the same. However, this shall not relieve any User
from the obligation to report events in accordance with Rules framed under
relevant provision made under Electricity Act, 2003. The format for such a
report shall be as per the approval of the Distribution Code Review Panel and
shall typically contain the following:
(a)
Location
of the incident,
(b)
Date
and time of the incident,
(c)
Plant
or Equipment involved,
(d)
Nature
of incident (electrical or non-electrical),
(e)
Supplies
interrupted and the duration wherever applicable,
(f)
Amount
of Generation lost, wherever applicable,
(g)
System
Parameters before and after the incident (Voltage, Frequency, Load, Generation,
etc.)
(h)
Network
configuration before the incident,
(i)
Relay
indications and performance of protection,
(j)
Brief
description of the incident,
(k)
Estimated
time of return to service,
(l)
Any
other relevant information,
(m)
Recommendations
for future improvement,
(n)
Name
and designation of the reporting person.
9.3.3. :-
The
report shall contain sufficient detail to describe the event to enable the
recipient to assess the implications and risks arising out of the same. The
recipient may ask for clarifications and additional information wherever
necessary and it is obligatory that the reporting User shall put his best
efforts and provide all the necessary and reasonable information.
9.3.4. :-
In
case of a request by either party, the oral report shall be written down by the
sender and dictated by way of a telephone message or sent by Fax/e-mail to the
recipient. In case of an emergency the report can be given only orally and
followed by written confirmation.
9.3.5. :-
Reporting
of accidents shall be in accordance with Intimation of Accidents (Form and Time
Service of Notice) Rules 2004 read with section 161 of Electricity Act, 2003,
or other applicable rules. Till such rules are made, the Distribution Licensee
shall follow reporting of accidents as mentioned in Power System Safety
Standard (Indian Electricity Rule 1956) as per Annexure 4 to these regulations.
CHAPTER
10 MISCELLANEOUS
Regulation - 10.
10.1. Dispute Redressal :-
Any
dispute regarding the interpretation of any provision of the Distribution Code,
shall be addressed to the Secretary to the Commission. The decision of the
Commission shall be taken as final and binding on all concerned.
10.2. Power to Remove Difficulties
:-
If
any difficulty arises in giving effect to any of the provisions of the
Distribution Code, the Commission may, by general or specific order, make such
provisions not inconsistent with the provisions of the Act, as may appear to be
necessary for removing the difficulty.
10.3. Power to Relax :-
The
Commission may by general or special order, for reasons to be recorded in
writing and after giving an opportunity of hearing to the parties likely to be
effected by grant of relaxation, may relax any of the provisions of the
Distribution Code on its own motion or on an application made before it by an
interested person.
10.4. Power to Amend :-
The
Commission may, at any time, vary, alter, modify or amend any provision of the
Distribution Code.
10.5. Repeal and Savings :-
10.5.1. :-
Nothing
in these Regulations shall be deemed to limit or otherwise affect the inherent
power of the Commission to make such orders as may be necessary to meet the
ends of justice or to prevent abuses of the process of the Commission.
10.5.2. :-
Nothing
in these Regulations shall bar the Commission from adopting in conformity with
the provisions of the Act a procedure, which is at variance with any of the
provisions of these Regulations, if the Commission, in view of the special
circumstances of a matter or class of matters and for reasons to be recorded in
writing, deems it necessary or expedient for dealing with such a matter or
class of matters.
10.5.3. :-
Nothing
in these Regulations shall, expressly or impliedly, bar the Commission dealing
with any matter or exercising any power under the Act for which no Regulations
have been framed, and the Commission may deal with such matters, powers and
functions in a manner it thinks fit.
10.5.4. :-
On
and from notification of these regulations, adopted, Joint Electricity
Regulatory Commission Goa and Union Territories (Distribution Code)
Regulations, 2010, along with amendments as carried out thereto, shall stand
repealed.
ANNEXURE 1: LOAD DATA FOR DEMANDS
FOR OF 1 MW AND ABOVE
(1)
Type
of Load: (e.g., Furnace loads, rolling mills, traction loads, pumping loads,
industrial loads etc.)
(2)
Maximum
Demand (KVA)
(3)
Year(s)
by which full/part load supply is required:(Phasing of loads shall be
furnished)
(4)
Location
of load with a location map drawn to scale:
(5)
Rated
voltage, frequency and number of phases at which supply is required:
(6)
Description
of equipment:
(a)
Motors:
(State the purpose and number of installations, voltage and KW rating, method
of starting, starting current and duration, type of motors, types of drives and
control equipment etc.)
(b)
Heating:
(Type and KW rating)
(c)
Furnace:
(Type, Furnace Transformer capacity and voltage ratio)
(d)
Electrolysis:
(Purpose and KVA capacity)
(e)
Lighting:
KW Demand.
(f)
Any
other loads with particulars:
(7)
Sensitivity
of Demand to fluctuations in voltage and frequency of supply at the time of
peak load: (Give details).
(8)
Phase
unbalance imposed on the System:
(9)
Maximum:
____________________ Average: ________________________
(10)
Maximum
harmonic content imposed on the System: (Furnish details of devices proposed
for the suppression of harmonics).
(11)
Details
of the loads likely to cause demand fluctuations greater than 10 MW at the
point of connection including voltage dips (percentage) lasting for 5 seconds
or more.
ANNEXURE 2: EMBEDDED GENERATOR
UNIT-WISE DATA
Sl.No. |
Particulars |
Details
|
1. |
Name and
address of Generating Company: |
|
2. |
Location of
Generating Plants (s): |
|
3. |
Generation
Volts (kV); |
|
4. |
Rated kVA/kW |
|
5. |
Maximum and
minimum Active Power sent out (kW) Reactive Power capability (kVAr), if any; |
|
6. |
Type of
Generating Plant—synchronous, asynchronous, etc.; |
|
7. |
Method of
voltage control; |
|
8. |
Generator
transformer details, if applicable; |
|
9. |
Requirements
for Top-up supplies and/or standby supplies; |
|
10. |
Generator
kW/kVAr capability chart (at lower voltage terminals); |
|
11. |
Type of
excitation system; |
|
12. |
Inertia
constant kW secs/kVA; |
|
13. |
Stator
Resistance; |
|
14. |
Direct-Axis
Reactance (Sub-transient, Transient andSynchronous); |
|
15. |
Quadrature-Axis
Reactance (Sub-transient and Synchronous); |
|
16. |
Zero Sequence
(Resistance and Reactance); |
|
17. |
Negative Sequence
(Resistance and Reactance); |
|
18. |
Generator
Transformer (Resistance, Reactance, kVA Rating, Tap Arrangement, Vector
Group, Grounding, Connection and % Impedance); |
|
19. |
Automatic
Voltage Regulator block diagram, including the data on the gains (forward and
feedback), time constants, and voltage control limits; |
|
20. |
Speed
governor block diagram detailing the governor fly-ball,if applicable, and
control system and Prime Mover time constants, together with the turbine
rating and maximum power |
|
21. |
Standby
requirements: |
|
I. |
Rated
Capacity and Minimum Generation of each Generating Unit and Power Station in
kW for standby capacity requirements. |
|
II. |
Generating
Unit and Power Station auxiliary Demand (Active Power and Reactive Power) in
kW and kVAr, at rated capacity conditions. |
|
III. |
Interface
Arrangements the means of synchronization between the distributors and User; |
|
IV. |
Details of
arrangements for connecting to ground that part of the Generators System
directly connected to the distribution system; |
|
V. |
The means of
connection and disconnection which are to be employed |
|
VI. |
Precautions
to be taken to ensure the continuance of safe conditions should any grounded
neutral point of the Generating unit become disconnected from ground. |
|
VII. |
Details of
Protection System of the Generating Unit |
|
ANNEXURE 3: SYSTEM DATA
The
Distribution Licensee shall provide only relevant details out of the following
details as required by Consumer for designing and selecting electrical
equipment:
(1)
Topological
map of area of supply by licensee marking boundaries.
(2)
Distribution
map of the Distribution Licensee drawn to scale of at least 1 cm to 2.5 KM
showing the existing HT/EHT lines and substations within the Area of Supply of
the Licensee. Lines and substations under construction or planned for the next
five years shall be shown in dotted lines.
(3)
Single
line diagram of the Distribution System showing line length, conductor sizes,
substation capacity, capacitor sizes with locations, auto-reclosures, etc.
(4)
Details
of Metering and Relaying at substations.
(5)
Details
of Grid substations at the point of interconnections as follows:
(i)
MVA
Capacity and voltage,
(ii)
Number
of transformers, capacity of each transformer, voltage ratios, Ranges of taps
Impedance
(iii)
Fault
level at substation bus bars, both three phase and single line to ground fault
(iv)
Bus
impedance,
(v)
Substation
layout diagram.
(6)
Drawl
at Connection Points / Interface Point: Maximum and Minimum MW drawl from each
connection with the Transmission System or with other Distribution Licensees
during last six months ANNEXURE 4: RULE NO. 44 A OF THE INDIAN ELECTRICITY
RULES, 1956 Rule no. 44 A - Intimation
of Accident
If
any accident occurs in connection with the generation, transmission, supply or
use of energy in or in connection with any part of electric supply lines or
other works of any person and the accident results in or is likely to have
resulted in loss of human or animal life or in any injury to a human being or
an animal, such person or any authorized person of the distribution licensee
not below the rank of Junior Engineer or equivalent shall send to the Inspector
a telegraphic report within 24 hours of the knowledge of the occurrence of the
fatal accident and a written report in a form set out in Annexure XIII within
48 hours of the knowledge of the occurrence of the fatal accident and all other
accidents. Where practicable a telephonic message should also be given to the
Inspector immediately the accident comes to the knowledge of authorized officer
of distribution licensee or other person concerned.
The Indian Electricity Rules, 1956
[ANNEXURE XIII]
FORM FOR REPORTING ELECTRICAL
ACCIDENTS
(See Rule 44-A)
Sl.No. |
Particulars |
Details |
||||
1. |
Date and Time
of accident |
|
||||
2. |
Place of
accident (Village/Town, Tehsil /Thana, District and State) |
|
||||
3. |
System and voltage
of supply (Whether EHV/HV/LV line, sub-station/generating station / consumers
installations/service lines/other installations) |
|
||||
4. |
Designation
of the Officer-in-charge (in whose jurisdiction the accident occurred) |
|
||||
5. |
Name of
owner/user of energy in whose premises the accident occurred. |
|
||||
6. |
Details of
victim |
|
||||
(a) |
Human |
|
||||
Sr. No. |
Name |
Fathers Name |
Sex of victim |
Full Postal Address |
Approx. Age |
Fatal / NonFatal
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(b) |
Animals |
|
||||
Sr. No. |
Description of Animals |
Number(s) |
Name(s) of Owner(s) |
Address (es) of owner(s) |
Fatal / NonFatal
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
7 |
In case
the victim(s) is /are employee(s): a)
Designation of such person(s) b) Brief
description of the job undertaken, if any. c) Whether
such person/persons was/were allowed to work on the job. |
|
||||
8 |
In case
the victim(s) is/are employee(s) of a licensed contractor: a) Did the
victim(s) possess any electric workmans permits(s), supervisors certificate
of competency issued under Rule 45? b) If yes
give number and date of issue and the name of issuing authority. c) Name
and designation of the person who assigned the duties of the victim(s) |
|
||||
9 |
In case of
accident in the Distribution licensee system, was the Permit to Work (PTW)
taken? |
|
||||
10 |
Describe
fully the nature and extent of injuries, e.g., fatal / disablement (permanent
or temporary) of any portion of the body or burns or other injuries. In case of
fatal accident, was the post mortem performed? |
|
||||
11 |
Detailed
causes leading to the accident (To be given in a separate sheet annexed to
this form) |
|
||||
12 |
Action taken
regarding first-aid, medical attendance etc. immediately after the occurrence
of the accident (give details) |
|
||||
13 |
Whether the
District Magistrate and Police Station concerned have been notified of the
accident (if so, give details) |
|
||||
14 |
Steps taken
to preserve the evidence in connection with accident to the extent possible. |
|
||||
15 |
Names and
designation(s) of the person(s) assisting, supervising the person(s) killed
or injured. |
|
||||
16 |
What safety
equipment were given to and used by the person(s) who met with this accident
(e.g., rubber gloves, rubber mats, safety belts and ladders etc.)? |
|
||||
17 |
Whether
isolating switches and other sectionalizing devices were employed to deaden
the section for working on the same? Whether working section was earthed at
the site of work? |
|
||||
18 |
Whether
the work on live lines was undertaken by authorized person(s)? If so, the
name and the designation of such person(s) may be given. |
|
||||
19 |
Whether
the artificial resuscitation treatment work on live lines was undertaken by
Authorised person(s)? If yes,
how long was it continued before its abandonment? |
|
||||
20 |
Names and
designations of persons present at and witnessed the accident. |
|
||||
21 |
Any other
information/remarks. |
|
||||
|
Place: |
|
||||
|
Time: |
|
||||
|
Date: |
|
Signature:
Name
& Designation:
Address
of the person reporting:
ANNEXURE 5: LIST OF ABBREVIATIONS
Sl. No. |
Abbreviation |
Full Form
|
1 |
AAC |
All Aluminum
Conductor
|
2 |
AAAC |
All Aluminum
Alloy Conductor
|
3 |
ACSR |
Aluminum
Conductor Steel Reinforced
|
4 |
BIS |
The Bureau of
Indian Standards
|
5 |
SAIDI |
System
Average Interruption Duration Index
|
6 |
SAIFI |
System
Average Interruption Frequency Index
|
7 |
CBIP |
The Central
Board of Irrigation and Power
|
8 |
CEA |
Central
Electricity Authority
|
9 |
CEI |
Chief
Electrical Inspector
|
10 |
CT |
Current
Transformer
|
11 |
DCR |
Distribution
Code Review
|
12 |
DCRP |
Distribution
Code Review Panel
|
13 |
EHV/EHT |
Extra High
Voltage/ Extra High Tension
|
14 |
GI |
Galvanized
Iron
|
15 |
GSS |
Gas
Sub-station
|
16 |
HV |
High Voltage/
|
17 |
HT |
High Tension
|
18 |
Hz |
Hertz (cycles
per seconds)
|
19 |
IDMT |
Inverse
Definite Minimum Time
|
20 |
IEEE |
Institute of
Electrical and Electronics Engineers
|
21 |
IEC |
International
Electro Technical Commission
|
22 |
IEGC |
Indian
Electrical Grid Code
|
23 |
IS |
Indian
Standards
|
24 |
IP |
Irrigation
Pump
|
25 |
kA |
Kilo Ampere
|
26 |
kW |
Kilo Watt
|
27 |
kWh |
Kilo Watt
hour
|
28 |
kVA |
Kilo Volt
Ampere
|
29 |
LT |
Low Tension
|
30 |
LV |
Low Voltage
|
31 |
MCB |
Miniature
Circuit Breaker
|
32 |
MVA |
Mega Volt
Ampere
|
33 |
MW |
Megawatt
|
34 |
PCC |
Prestressed
Cement Concrete
|
35 |
PT |
Potential
transformer
|
36 |
PTW |
Permit to
work
|
37 |
RCC |
Reinforced
Cement Concrete
|
38 |
REC |
Rural
Electrification Corporation
|
39 |
R&R |
Rehabilitation
and Resettlement
|
40 |
SCADA |
Supervisory
Control and Data Acquisition
|
41 |
SLDC |
State Load Despatch
Centre
|
42 |
STU |
State
Transmission Utility
|