GREATER NOIDA INDUSTRIAL DEVELOPMENT AREA BUILDING
(FOURTH AMENDMENT) REGULATIONS, 2018
Regulation - 1. Short title and commencement.--
(1)
These regulations shall be called the Greater
Noida Industrial Development Area Building (Fourth Amendment) Regulations,
2018.
(2)
They sa
Regulation - 2. Amendment of Regulation 24.--
In the Greater Noida Industrial Development Area Building
Regulations, 2010, hereinafter referred to as the said regulations, in
Regulation 24,--
(a)
in sub-regulation (24.2) in Clause 1 for
sub-clause (6) the following sub-clause shall be substituted, namely--
(6) Distance between two adjacent building blocks--
Distance between two adjacent building blocks shall be
minimum 6 mtrs. and maximum 16 mtrs. depending on the height of blocks. For
building height up to 18 mtrs., the spacing shall be 6 mtrs. and thereafter the
spacing shall be increased as per spacing given in table No. 8. If the blocks
have dead-end sides facing each other, than the spacing shall be maximum 9
mtrs. instead of 16 mtrs. Moreover, the allottee may provide or propose more
than 16 mtrs. space between two blocks. In case where height of building one of
the two blocks/building is less than 12 m the minimum distance between blocks
will be 9 mtrs., only after fire NOC has been issued by the competent
department.
(i)
For calculation of distance between two
blocks balcony up to maximum 1.5 m width shall be exempted only, if minimum 6
mtrs. clear space is available for fire tender movement and fire NOC has been
granted with 1.5 meter balcony. Beyond 1.5m width of balcony no consideration
shall be made.
(ii)
The calculation of minimum 9m distance between
building height up to 12 m and the tallest/highest building shall be done only
for buildings permissible in 15% FAR i.e. buildings falling in common areas
such room, visitor toilet, driver room, electric sub-station, service shaft,
community centre, religious building, milk and vegetable booth, nursery school
and creche, only if fire NOC is obtained from fire department;
(b)
in sub-regulation (24.3), in Clause 1 for
sub-clause (5) the following sub-clause shall be substituted, namely--
(5) Distance between two adjacent building blocks--
Distance between two adjacent building blocks shall be
minimum 6 mtrs. and maximum 16 mtrs. depending on the height of blocks. For
building height up to 18 mtrs., the spacing shall be 6 mtrs. and thereafter the
spacing shall be increased as per spacing given in Table No. 8
. If the blocks
have dead-end sides facing each other, than the spacing shall be maximum 9
mtrs. instead of 16 mtrs. Moreover, the allottee may provide or propose more
than 16 mtrs. space between two blocks. In case where height of building one of
the two blocks/building is less than 12 m the minimum distance between blocks
will be minimum 9 mtrs., only after the fire NOC has been issued by the
competent department.
(i) ???For
calculation of distance between two blocks balcony up to maximum 1.5 m width
shall be exempted only, if minimum 6 mtrs. clear space is available for fire
tender movement and fire NOC has been granted with 1.5 meter balcony. Beyond
1.5m width of balcony no consideration shall be made.
(ii) ??The
calculation of minimum 9 m distance between building height up to 12 m and the
tallest/highest building shall be considered only for buildings permissible in
15% FAR i.e. buildings falling in common areas such room, visitor toilet,
driver room, electric sub-station, service shaft, community centre, religious
building, milk and vegetable booth, nursery school and creche, only if fire NOC
is obtained from fire department;
(c)
in sub-regulation (24.4), in Clause 1 for sub-clause
(5) the following sub-clause shall be substituted, namely--
"(5) Distance between two adjacent building
blocks.--
Distance between two adjacent building blocks shall be
minimum 6 mtrs. and maximum 16 mtrs. depending on the height of blocks. For building
height up to 18 mtrs., the spacing shall be 6 mtrs. and thereafter the spacing
shall be increased as per spacing given in table No. 8. If the blocks have
dead-end sides facing each other, than the spacing shall be maximum 9 mtrs.
instead of 16 mtrs. Moreover, the allottee may provide or propose more than 16
mtrs. space between two blocks. In case where height of building one of the two
blocks/building is less than 12 m the minimum distance between blocks will be
minimum 9 mtrs., only after fire NOC has been issued by the competent
department.
(i) ???For
calculation of distance between two blocks balcony up to maximum 1.5 m width
shall be exempted only, if minimum 6 mtrs. clear space is available for fire
tender movement and fire NOC has been granted with 1.5 meter balcony. Beyond
1.5 m width of balcony no consideration shall be made.
(ii) ???The calculation of minimum 9 m distance
between building height up to 12 m and the tallest/highest building shall be
done only for buildings permissible in 15% FAR i.e. buildings falling in common
areas such room, visitor toilet, driver room, electric sub-station, service
shaft, community centre, religious building, milk and vegetable booth, nursery
school and creche, only if fire NOC is obtained from fire department;".
(d)
in sub-regulation (24.5), in Clause 1 for
sub-clause (5) the following sub-clause shall be substituted, namely--
"(5) Distance between two adjacent building
blocks.--
Distance between two adjacent building blocks shall be
minimum 6 mtrs. and maximum 16 mtrs. depending on the height of blocks. For
building height up to 18 mtrs., the spacing shall be 6 mtrs. and thereafter the
spacing shall be increased as per spacing given in table No. 8. If the blocks
have dead-end sides facing each other, than the spacing shall be maximum 9
mtrs. instead of 16 mtrs. Moreover, the allottee may provide or propose more
than 16 mtrs. space between two blocks. In case where height of building one of
the two blocks/building is less than 12 m the minimum distance between blocks
will be minimum 9 mtrs., only after the fire NOC has been issued by the
competent department.
(i) ???For
calculation of distance between two blocks balcony up to maximum 1.5 m width
shall be exempted only, if minimum 6 mtrs. clear space is available for fire
tender movement and fire NOC has been granted with 1.5 meter balcony. Beyond
1.5m width of balcony no consideration shall be made.
(ii) ???The calculation of minimum 9 m distance
between building height up to 12 m and the tallest/highest building shall be
done only for buildings permissible in 15% FAR i.e. buildings falling in common
areas such room, visitor toilet, driver room, electric sub-station, service
shaft, community centre, religious building, milk and vegetable booth, nursery
school and creche, only if fire NOC is obtained from fire department;".
(e) ??in
sub-regulation (24.6), in Clause 1 for sub-clause (3) for item (ii) the
following item shall be substituted, namely--
"(ii) Floor Area Ratio shall not include.--
Basement (s), shall be permissible within the setback
line on each floor. However maximum permissible area under basement shall be limited
up to,--
(a)
Basement area, if use for services, storage
etc. then maximum area under such facilities shall be equivalent to maximum
permissible ground coverage.
(b)
Basement area as defined in parking table, if
used for parking, than area equivalent to parking requirement shall be
permitted.
(c)
In plots bigger than 10,000 sq mtrs. the
basement shall be allowed in setback area after leaving a minimum setback of 6
mtrs.".
(f) ???in
sub-regulation (24.7), in Clause 1 for sub-clause (5) the following sub-clause
shall be substituted, namely--
"(5) Distance between two adjacent building
blocks.--
Distance between two adjacent building blocks shall be
minimum 6 mtrs. and maximum 16 mtrs. depending on the height of blocks. For
building height up to 18 mtrs., the spacing shall be 6 mtrs. and thereafter the
spacing shall be increased as per spacing given in table No. 8. If the blocks
have dead-end sides facing each other, than the spacing shall be maximum 9
mtrs. instead of 16 mtrs. Moreover, the allottee may provide or propose more
than 16 mtrs. space between two blocks. In case where height of building one of
the two blocks/building is less than 12 m the minimum distance between blocks
will be minimum 9 mtrs., only after the fire NOC has been issued by the
competent department.
(i) ???For
calculation of distance between two blocks balcony up to maximum 1.5 m width
shall be exempted only, if minimum 6 mtrs. clear space is available for fire
tender movement and fire NOC has been granted with 1.5 meter balcony. Beyond
1.5m width of balcony no consideration shall be made.
(ii) ???The calculation of minimum 9 m distance
between building height up to 12 m and the tallest/highest building shall be
done only for buildings permissible in 15% FAR i.e. buildings falling in common
areas such room, visitor toilet, driver room, electric sub-station, service
shaft, community centre, religious building, milk and vegetable booth, nursery
school and creche, only if fire NOC is obtained from fire department;".
(g) ???in
sub-regulation (24.7), in Clause 1 for sub-clause (5) the following sub-clause
shall be substituted, namely--
"(5) Distance between two adjacent building blocks--
Distance between two adjacent building blocks shall be
minimum 6 mtrs. and maximum 16 mtrs. depending on the height of blocks. For
building height up to 18 mtrs., the spacing shall be 6 mtrs. and thereafter the
spacing shall be increased as per spacing given in table No. 8. If the blocks
have dead-end sides facing each other, than the spacing shall be maximum 9
mtrs. instead of 16 mtrs. Moreover, the allottee may provide or propose more
than 16 mtrs. space between two blocks. In case where height of building one of
the two blocks/building is less than 12 m the minimum distance between blocks
will be minimum 9 mtrs., only after the fire NOC has been issued by the
competent department.
(i) ??For
calculation of distance between two blocks balcony up to maximum 1.5 m width
shall be exempted only, if minimum 6 mtrs. clear space is available for fire
tender movement and fire NOC has been granted with 1.5 meter balcony. Beyond
1.5m width of balcony no consideration shall be made.
(ii) ?The
calculation of minimum 9 m distance between building height up to 12 m and the
tallest/highest building shall be done only for buildings permissible in 15%
FAR i.e. buildings falling in common areas such room, visitor toilet, driver
room, electric sub-station, service shaft, community centre, religious
building, milk and vegetable booth, nursery school and creche, only if fire NOC
is obtained from fire department;".
(h) ??after
sub-regulation (24.14) the following sub-regulation shall be inserted, namely--
"24.15.1 Integrated Industrial Township (IIT):
(1)
Maximum permissible?
(i)
Global Ground coverage 25%
(ii)
Global Floor Area Ratio 2.50*
(iii) Height no limit. For building above 30 mtrs. In height,
clearance from Airport Authority shall have to be taken.
?
(iv)
Break up of Ground Coverage and FAR:
*No Global FAR will be provided on open spaces and roads.
|
Sl.
No.
|
Land
use category
|
Proposed
Max. Permissible FAR
|
Max.
Permissible Ground Coverage (%)
|
|
1.
|
Hi-tech
(Type A-Flatted Industries)
|
1
|
|
40
|
|
2.
|
Hi-tech
(Type B-IT/ITES Industries)
|
4.25
|
|
30
|
|
3.
|
Bio-Tech
|
4.25
|
|
35
|
|
4.
|
R&D
|
4.25
|
|
35
|
|
5.
|
Commercial
Mixed Use
|
5.25
|
|
40
|
|
6.
|
Residential-Group
Housing
|
5.5
|
|
35
|
|
7.
|
Residential-EWS
Housing
|
2
|
|
40
|
|
8.
|
Utilities
|
1
|
|
50
|
|
Proposed
Max. Permissible Global FAR
|
|
2.5
|
|
|
Proposed
Max. Permissible Global Ground Coverage
|
|
25%
|
|
(v)
Setbacks: Setbacks on individual plots shall
be as per Table No. 2
(vi)
Minimum Road width in the IIT layout shall be
24 m wide.
24.15.2 Other Provisions:
(1)
No construction of any kind shall be
permitted beyond the building envelope (on setbacks) except
(i)
A Chajja (projection) of maximum width of
0.75 metre at lintel or roof level. No construction of any type or any material
shall be permitted over projections.
(ii)
Underground water tanks with top flush with
the adjoining ground level.
(iii) Watchman Shelters and Watch Towers with following
provisions:
(iv)
No projection of watchman shelters and watch
towers shall be allowed outside the plot line.
(v)
Maximum height of watchman shelter shall be 4
metres and for watch towers 15 metres. Total area, as mentioned below, under
such shelters shall be split up in desired number of watch man shelter and
watch towers as follows--
|
Sl.
No.
|
Plot
size
|
Total
area for watchman shelter and watch tower
|
Maximum
area under each watchman shelter
|
Maximum
area under each watch tower
|
|
1
|
Up
to 0.5 acres
|
15
square metres
|
15
square metres
|
5
square metres
|
|
2
|
Above
0.5 acres up to 10 acres
|
30
square metres
|
24
square metres
|
5
square metres
|
|
3
|
Above
10 acres up to 25 acres
|
45
square metres
|
24
square metres
|
5
square metres
|
|
4
|
Above
25 acres up to 50 acres
|
60
square metres
|
24
square metres
|
5
square metres
|
|
5
|
Above
50 acres for an additional 50 acres
|
An
additional 10 square metres and part thereof
|
24
square metres
|
5
square metres
|
(vi)
The following features shall be permitted
after leaving minimum 6 mtrs. open corridor for fire tenders.
(a)
Meter room as per norms of Electricity
Authority.
(b)
Open transformers without any permanent
enclosure keeping in view the necessary safety requirements.
(c)
Other features as mentioned in Table 3.
(d)
Rockery, well and well structures, water
pool, swimming pool (if uncovered), uncovered platform around tree, tank,
fountain, bench, chabutra with open top and unenclosed by side walls, compound
wall, gate, slide swing, culverts on drains.
(e)
Any other feature, primarily ornamental in
nature, not enclosing or covering space of commercial use may be permitted by
the Chief Executive Officer on case to case basis.
(f)
Open generator set, filtration plant, Electrical
distribution equipments, feeder pillars, telephone distribution equipments may
be permitted in open setback as a service utility provided after leaving clear
space for fire tender.
(2) ??Floor
Area Ratio shall include
(i)
Mezzanine
(ii)
The shafts provided for lifts shall be taken
for covered area calculations only on one floor and included in ground
coverage.
(iii) Pergola, shall be counted towards Floor Area Ratio if
closed from three or more than three sides.
(iv)
Meter room as per Electricity Authority
norms.
(3) ??Floor
Area Ratio shall not include:
(i)
A cantilever projection at any level
(setbacks) of a width of 0.75 meter no. construction of any type or any
material shall be permitted over projections.
(ii)
Basement (s), shall be permissible within the
setback line on each floor. However maximum permissible area under basement
shall be limited up to:
(a)?? Basement
area, if used for services, storage etc. then maximum area under such
facilities shall be equivalent to maximum permissible ground coverage.
(b) ???Basement
area/Podium parking as defined in parking table, if used for parking, then area
equivalent to parking requirement shall be permitted.
(c)?? ?In plots bigger than 10,000 sq mtrs. the
basement shall be allowed in setback area after leaving a minimum setback of 6
mtrs.
(iii) ??Basement, if used for any other use other
than mentioned above, shall be included in the FAR of the building.
(iv) ??Stilt
area of non-habitable height 2.40 metres from bottom of beam proposed to be
used for parking, landscaping etc.
(v)? ?Balconies (Up to 1.5 metre width free and
beyond 1.5 m width, half of it shall be included in FAR) may be projected in
open setbacks provided 6 mtrs. Clear space is available for fire tender
movement and fire NOC has been granted.
(vi) ??Other
features as mentioned in Table 3.
(vii) ?Rockery,
well and well structures, water pool, swimming pool (if uncovered), uncovered
platform around tree, tank, fountain, bench, chabutra with open top and
unenclosed by side walls, compound wall, gate, slide, swing, uncovered
staircase (unenclosed and uncovered on three sides except for 0.9 metre high
railing/wall and open to sky), overhead tanks on top of buildings, open shafts,
culverts on drains.
(viii) Open ramps with no area enclosed below
it of usable height, if used for approach to the entrance of the building, then
the height as per requirement may be considered. The space under the ramp shall
not be used for any commercial purpose, however it can be landscaped with
approval of the Chief Executive Officer on case to case basis.
(ix) ??Atrium
shall be kept free from FAR and ground coverage. In case any commercial
activity is proposed in Atrium or any saleable area or any other structure
which is counted in FAR & ground coverage, its respective area shall be
added in total FAR & ground coverage.
(x) ??Any
other feature purely ornamental in nature and not enclosing or covering space
of commercial use may be permitted by the Chief Executive Officer on case to
case basis.
(xi) ??Additional
5% of the plot area as ground coverage will be allowed for dedicated multi
level parking in plots bigger than 10,000 sq mtrs.
(xii) ?In
multi storey building service floor may be allowed after 4 floors. Maximum of 3
service floors may be allowed in a building. Service floor shall not be counted
in FAR and maximum height of service floor shall be 2.40 mtrs. from floor to
bottom of the beam.
(4) ??All
the common facilities prescribed below will have to be provided and shall be
counted in the prescribed FAR.
Shops and community facilities (other than mentioned in
No. 24.15(5)12 as per population norms or specified in the earlier lease deed.
In case of plots where minimum population required for provision of convenient shopping
is not achieved then--
(i)
Area for shopping and commercial activities
equivalent to 1.0 per cent permissible FAR of the plot area shall be allowed;
(ii)
Minimum four kiosks of 4 sq mtrs of carpet
area and two shops of 10 sq m carpet area shall be provided mandatorily;
(iii) Maximum height of shops and kiosks shall be 4 meter from
floor to ceiling;
(iv)
However shops may be allowed as integral part
of Group housing building on the ground floor;
(5) ???15%
of prescribed FAR shall be added towards common areas, which shall include the
following built structures. The structures on ground will be counted in Ground
Coverage.
(i)
Canopy projections of area as mentioned in
Table 4, no construction of any type shall be permitted over the canopy.
Canopy, if cantilevered and no structure on it having a size of 2.4 m x 4.5 m
shall not be counted in Ground Coverage.
(ii)
Loft up to maximum height of 1.5 metre.
(iii) Air-conditioning plant, electrical installation,
generator room, water works, water tank etc.
(iv)
Watchmen/Security shelters and watch towers
(v)
Garbage shafts, lift shafts and 10 sq. mtr
lobby in front of each lift (excluding area of corridor beyond the lift).
(vi)
Fire escape staircases.
(vii) Toilet blocks for visitors, drivers, guards etc. on
ground floor only.
(viii) Mumty, machine room for lifts.
(ix)
Cupboards up to a depth of 0.60 mtr. and 1.80
mtr. in length.
(x)
Bay window up to a depth of 0.60 mtr. and 2.0
mtr. length.
(xi)
Refuge area as per definition for fire
evacuation and National Building Code, 2005.
(xii) Sewage treatment plant, water treatment plant, garbage
collection centre Electric sub-station, service ducts, community hall,
religious building, milk and vegetable booth, school & creche.
(xiii) Covered walkways and pathways.
(xiv) Any other utilities and facilities as decided by the
Chief Executive Officer depending on its requirement.
(6) ??Distance
between two adjacent building blocks: Distance between two adjacent building
blocks shall be minimum 6 mtrs. and maximum 16 mtrs. depending on the height of
blocks. For building height up to 18 mtrs., the spacing shall be 6 mtrs. and
thereafter the spacing shall be increased as per spacing given in Table No. 8
.
If the blocks have dead-end sides facing each other, than the spacing shall be
maximum 9 mtrs. instead of 16 mtrs. Moreover, the allottee may provide or
propose more than 16 mtrs. space between two blocks. In case where height of
building one of the two blocks/building is less than 12 m the minimum distance
between blocks will be minimum 9 mtrs., only after the fire NOC has been issued
by the competent department.
(i) ???For
calculation of distance between two blocks balcony up to maximum 1.5 m width
shall be exempted only, if minimum 6 mtrs. clear space is available for fire
tender movement and fire NOC has been granted with 1.5 meter balcony. Beyond
1.5 m width of balcony no consideration shall be made.
(ii) ??The
calculation of minimum 9m distance between building height up to 12 m and the
tallest/highest building shall be done only for buildings permissible in 15%
FAR i.e. buildings falling in common areas such room, visitor toilet, driver
room, electric sub-station, service shaft, community centre, religious
building, milk and vegetable booth, nursery school and creche, only if fire NOC
is obtained from fire department.
(7) ???The
authority shall have a right to impose such restriction and limitations as to
the number of storey and extent of height of the building as he considers fit
where protected areas, ancient or historical monuments lie within a radius of
one and half kilometer from the boundary line of such buildings by recording
reasons.
(8) ???In
density calculation each servant quarter will be reckoned as half dwelling
unit, (standard size of the family for a dwelling unit for density purpose is
4.5 persons).
(9)?? ?A group housing shall conform to the
provisions of the Sector Plan and Zonal Development Plan or scheme (if any) of
the area, in terms of setbacks, ground coverage, Floor Area Ratio and height
restrictions.
(10) The provisions contained in this
regulations shall not apply to housing for economically weaker sections and low
income group schemes undertaken by the State Government, Authority or any other
public body approved in this behalf by the State Government. The authority may
decide the norms for setback, Ground coverage F.A.R. height, density, parking
etc. for specific projects of these groups depending upon the size of plot,
width of Road, availability of infrastructure, etc. by recording the reasons.
(11) ?The
internal height of the basement (floor to ceiling) shall be minimum 2.4 mtrs
from bottom of beam and maximum 4.5 meter. Except wherever height of equipments
such as electric generator, air conditioner, fire hydrant etc. is more than 4.5
metre. Additional height equivalent to height of equipments may be permitted.
In case of Automatic/semi automatic/mechanised parking facility also more than
4.5 mtrs, height may be allowed by the Chief Executive Officer depending upon
the technology and requirement of space.
(12) ??The
height of basement shall be maximum 1.5 metres up to bottom of the slab above
the plinth of boundary wall. In case the basement is flush with the ground
level adequate light and ventilation shall be ensured.
(13) ?Toilet
block for visitors, drivers etc. comprising of minimum a water closet, a bath
and 2 urinals shall be provided on the ground floor.
(14) In case of group housing having more
than two storey, steps must be taken to ensure water at higher floors. For this
purpose booster pumps and overhead tanks may be installed.
(15) ?At
least one of the lifts provided shall be of the specification of goods lift.
(16) ?Minimum
requirement for sanction/completion--Minimum covered area required for
completion shall be as per lease deed or Memorandum of Understanding or as
follows--
|
Sl.
No.
|
Size
of Plot (Sq. mtrs.)
|
Minimum
Built Up Area (as% of Total Permissible FAR)
|
|
1.
|
Up
to 4000 sq. mtrs.
|
50%
|
|
2.
|
Exceeding
4000 sq. mtrs but not exceeding 10,000 sq. mtrs.
|
40%
|
|
3.
|
Exceeding
10,000 sq. mtrs but not exceeding 20,000 sq. mtrs.
|
35%
|
|
4.
|
Exceeding
20,000 sq. mtrs but not exceeding 1,00,000 sq. mtrs.
|
30%
|
|
5.
|
Exceeding
1,00,000 sq. mtrs but not exceeding 2,00,000 sq. mtrs.
|
25%
|
|
6.
|
Exceeding
2,00,000 sq. mtrs but not exceeding 4,00,000 sq. mtrs.
|
20%
|
|
7.
|
Above
4,00,000 sq. mtrs
|
15%
|
(i)
No further time extension shall be required
if the completion has been taken by the allottee as per table mentioned above.
The above mentioned completion requirement shall be applicable in all
allotments. In the old allotments, the provisions of project report or lease
deed or previous options shall be followed.
(ii)
However validity of plans may be granted to
the allottee in multiples of 5 years after taking completion of minimum area.
(iii)
In all the projects of 40 hectares and above,
block wise temporary occupancy may be allowed subject to a minimum of 1,00,000
sq m built up area, the building completed with all mandatory provisions of
services and the allottee shall segregate these blocks for the purpose of
security during construction period. (17) Provision of following item in
building shall be mandatory for issue of completion certificate?
(iv)
Flooring; i.e. hard surface and completely
finished floors for common areas or public use areas;
(v)
Electrical wiring;
(vi) Plumbing work to be complete;
(vii) Parking and landscaping as per Table No. 5 and Table No.
6 respectively or directions issued from time to time whichever is higher;
(viii) Number plate and illumination board as per direction
amended or direction issued from time to time;
(ix) Internal and external finishing (Plastering may not be
mandatory);
(x) Boundary wall and gates shall be mandatory;
(xi) Buildings shall be lockable i.e. all external doors and
windows shall be provided. In case grill is provided in the windows the fixing
of glass in the windows pane shall not be mandatory;
(xii) No violation should be there in the overall building or
site at the time of issue of occupancy certificate;
(xiii) Any other special provision as mentioned in the lease deed;
(xiv) In case of completion of whole project, all temporary
structures to be removed. In case if any special clause is mentioned in the
lease deed or Memorandum of Understanding then the requirement mentioned in the
same shall be applicable.".
Regulation - 3. Amendment of Regulation 27.--
In the said regulation, in Regulation 27,--
(a)
for sub-regulation 27.1 the following
sub-regulation shall be substituted, namely--
"27.1 Setback
|
Plot
size
|
Front
setback
|
Rear
setback
|
Side
setback for corner
|
|
Up
to 200 square meter
|
2
meter
|
--
|
1.2
meter
|
|
201-500
square meter
|
3
meter
|
--
|
1.2
meter
|
|
501-1000
square meter
|
4.5
meter
|
3
meter
|
3
meter
|
|
1001-2000
square meter
|
10
meter
|
4.5
meter
|
4.5
meter
|
|
2001-4000
square meter
|
12
meter
|
6
meter
|
6
meter
|
|
Above
4000 square meter
|
15
meter
|
6
meter
|
6
meter
|
*Side setbacks will be applicable for all
plots (including corner plots) on both sides for sizes above 500 square mtrs.
In
case the permissible coverage is not achieved within setbacks, the setbacks of
the preceding category may be followed.".
(b)
for sub-regulation 27.4 the following
sub-regulation shall be substituted, namely--
"27.4 Use of the plot.--
On plots in village abadi which have not been notified
for acquisition under the Land Acquisition Act or have been recommended for
de-notification/lease back under the Land Acquisition Act by the competent
authority. Non-residential activities shall be allowed maximum up to 50 per
cent of the total permissible built up area on payment of prescribed charges in
Regulation 27.9. The farmer shall be charged prescribed fees only for the built
up area on which commercial activity is proposed.".
(c)
for sub-regulation 27.9 the following
sub-regulation shall be substituted, namely--
"27.9 Fees for conversion of use--
(i)
Development charge shall be charged only on
commercial conversions up to a maximum conversion of 50% of total built up
area, which shall be levied as follows:
(ii)
On roads of ROW up to 12 meter-25% prevailing
residential rate revised from time to time.
(iii) On roads of ROW above 12 meter and up to 18 mtrs. 1.25
times of the prevailing residential rate revised from time to time.
(iv)
On roads of ROW above 18 meter and up to 24
mtrs. 1.50 times of the prevailing residential rate revised from time to time.
(v)
On roads of ROW above 24 meter and up to 45
mtrs. 100% of the prevailing reserved commercial rate as per plot size, revised
from time to time minus the land cost.
(vi)
For corner plot 5% additional of above
mentioned charges shall be levied.".
(d)
after sub-regulation 27.10 the following
sub-regulation shall be inserted, namely--
"27.11 Minimum requirement for sanction/completion:
40 sq m or 50 per cent of maximum permissible ground
coverage (whichever is more) with provisions of a functional toilet/bath and
kitchen. Provision of following items in building shall be mandatory for issue
of occupancy certificate.
(a)
Flooring;
(b)
Electrical wiring whereas electrical fittings
shall not be mandatory;
(c)
Plumbing and fittings in at least one toilet
and kitchen;
(d)
Trees as per Table No. 6 or direction issued
from time to time which ever is higher;
(e)
Number plate;
(f)
Boundary wall shall be mandatory;
(g)
Internal and extent finishing (Plastering and
transparentwashing shall not be mandatory);
(h)
House shall be lockable i.e. all external
doors and windows shall have to be provided with grill provided in the windows
then fixing of glasses in the windows panes shall not be mandatory;
(i)
No violation of Building Regulations, Zonal
Plan Regulations and Master Plan should be there in the building at the time of
issue of occupancy certificate.".
Regulation - 4. Amendment of Regulation 28.--
In the said regulations, in Regulation 28,--
(a)
for sub-regulation 28.1 the following
sub-regulation shall be substituted, namely--
"28.1 Setback
|
Plot
size
|
Front
setback
|
Rear
setback
|
Side
setback
for
corner
|
|
Up
to 200 square meter
|
2
meter
|
--
|
1.2
meter
|
|
201-500
square meter
|
3
meter
|
--
|
1.2
meter
|
|
501-1000
square meter
|
4.5
meter
|
3
meter
|
3
meter
|
|
1001-2000
square meter
|
10
meter
|
4.5
meter
|
4.5
meter
|
|
2001-4000
square meter
|
12
meter
|
6
meter
|
6
meter
|
|
Above
4000 square meter
|
15
meter
|
6
meter
|
6
meter
|
*Side setbacks will be applicable for all plots
(including corner plots) on both sides for sizes above 500 square meter.
In
case the permissible coverage is not achieved within setbacks, the setbacks of
the preceding category may be followed.".
(b)
for sub-regulation 28.4 the following
sub-regulation shall be substituted, namely--
"28.4 Use of the plot.--
On plots allotted in planned village expansion scheme or
in sectors (5% or 6% or 7%):
Non-Residential activities shall be allowed maximum up to
50 per cent of the total permissible built up area on payment of prescribed
charges and it should be a part of the following activities--
1.
Dharmshala/Night shelter/baratghar
2.
Dispensary/clinic/laboratory
3.
Hostel
4.
Guest House/lodging house
5.
Motor garage and workshop
6.
Office for professionals out of which minimum
50% of the space shall be used for self use.
7.
Restaurant
8.
Vending booth/kiosks
9.
Bank
10.
Post Office
11.
Telegraph Office
12.
Creche and Day-care centre
13.
Retail shop
14.
Telecommunication tower (only ground based)
No activity whatsoever other than those mentioned above
shall be allowed. Allottees under this category will intimate in advance and
provide an undertaking to the authority that the proposal is in-conformity to
the bye-laws and other regulations prevalent at that time.".
(c)
for sub-regulation 28.5 the following
sub-regulation shall be substituted, namely--
"28.5 Fees for conversion of use per sq m. of
approval built up area--
(i) ???On
roads of ROW up to 12 mtrs. 25% prevailing residential rate revised from time
to time.
(ii) ???On roads of ROW above 12 meter and up to 18
mtrs. 1.25 times of the prevailing residential rate revised from time to time.
(iii) ??On roads of ROW above 18 meter and up to 24
mtrs. 1.50 times of the prevailing residential rate revised from time to time.
(iv) ??On
roads of ROW above 24 meter and up to 45 mtrs. 2 times of the prevailing
reserved residential rate as per plot size.
(v) ???For
corner plot 5% additional of above mentioned charges shall be levied.".
(d)
after sub-regulation 28.8 the following
sub-regulation shall be inserted, namely--
"28.9 Minimum requirement for sanction/completion:
40 sq m or 50 per cent of maximum permissible ground
coverage (whichever is more) with provisions of a functional toilet/bath and
kitchen. Provision of following items in building shall be mandatory for issue
of occupancy certificate.
(a)
Flooring;
(b)
Electrical wiring whereas electrical fittings
shall not be mandatory;
(c)
Plumbing and fittings in at least one toilet
and kitchen;
(d)
Trees as per Table No. 6 or direction issued
from time to time which ever is higher;
(e)
Number plate;
(f)
Boundary wall shall be mandatory;
(g)
Internal and external finishing (Plastering
and transparentwashing shall not be mandatory);
(h)
House shall be lockable i.e. all external
doors and windows shall have to be provided with grill provided in the windows
then fixing of glasses in the windows panes shall not be mandatory;
(i)
No violation of Building Regulations, Zonal
Plan Regulations and Master Plan should be there in the building at the time of
issue of occupancy certificate.".
Regulation - 5. Amendment of Table No. 5.--
In the said regulations in Table No. 5,--
(a)
for the entries at Sl. No. 2 the following
entries shall be substituted, namely-
|
Sl.
No.
|
Building/plot
|
Parking
space
|
|
"2
|
Educational
Building
|
One
parking space for every 100 square meter of permissible FAR area
|
|
(a)
IT/ITES, Offices, and institution
|
One
parking space for 50 square meter for administrative office
|
|
(b)
Auditorium
|
One
parking space per 15 seats
|
|
(c)
Bus parking
|
One
bus parking per 7500 square meter of permissible FAR area in case of
nonresidential Higher Secondary School
|
|
(d)
Hostels and Residential area
|
One
parking space for every 150 square meter of permissible FAR area in plot size
of 150 sq.mtrs. and above".
|
(b)
the following note shall be inserted, at the
end--
" The
projects in which the allottees have used less than permissible FAR and
obtained the occupancy certificate or they have applied for obtaining
completion certificate and provided for parking provisions accordingly in those
projects, in this case the remaining FAR/purchasable FAR shall not be permitted
till the parking
Regulation - 6. Insertion of new Tables 7 and 8.--
In the said regulations after Table No. 6 the following
tables shall be inserted, namely--
"Table No. 7
LIST OF VARIOUS DEVIATIONS/ADDITIONS/ALTERATION WHICH CAN
BE CONSIDERED FOR REGULARISATION/COMPOUNDING IN GREATER NOIDA INDUSTRIAL
DEVELOPMENT AUTHORITY
|
Item
|
Rate
Proposed
|
|
|
Setback
infringemention (sic infringement on) each floor:
(a)
Up to 0.15 mtr.
|
For commercial
buildings
|
For
all other type of building
|
|
|
(a)
Three times of current prevailing land rate x area of infringement of
respective use.
|
(a)
Equal to current prevailing land rate x area of infringement of respective
use.
|
|
(b)
Beyond 0.15 mtr. and up to 0.30 mtr.
(c)
Beyond 0.30 mtr.
|
(b)
Twelve times of current prevailing rate x area of infringement of respective
use.
(c)
Not permitted
|
(b)
Four times of current prevailing rate x area of infringement of respective
use.
(c)
Not permitted
|
|
Excess
coverage beyond permissible coverage on each floor (a) 5 per cent of the
achieved coverage on each floor*.
(a)
Beyond 5 per cent
|
(a)
Three times of current prevailing land rate or bid rate (whichever is
higher).
(b)
excess covered area
Not
permitted
|
(a)
Equal to current prevailing land rate of respective use or bid rate
(whichever is higher).
(b)
excess covered area.
Not
permitted
|
|
Pergola
if not three side open and provided only for architectural reasons and in
case of residential building only.
|
Rs. 2000
per sq m. for two side open
Rs.
5000 per sq m. for one side open
|
|
Basement
infringement (for parking and services) Beyond permissible limit of extended
basement:
(a)
Up to 30 cm. (6) 30 cm to 50 cm
(c)
50 cm to 1 mtr
(d)
beyond 1 meter
|
(a)
infringed height x width x 1/2 of current land rate
(b)
infringed height x width x 2/3 of current land rate
(c)
infringed height x width x current land rate
(d)
not permitted
|
|
Reduction
in minimum distance required between two blocks:
(a)
Up to 15 cm
(b)
15 cm to 45 cm
(c)
45 cm to 100 cm
(d)
above 100 cm
|
(a)
Rs. 500 sq m for surface area of elevation of each block where in there
reduction
(h)
Rs. 1000 sq m for surface area of elevation of each block where in there
reduction
(c)
Rs. 2000 sq m for surface area of elevation of each block where in there
reduction
(d)
Not permitted
"fire
NOC has to be taken"
|
|
Defective
height of the basement:
(a)
Up to 0.015 mtr.
(b)
Beyond 0.015 mtr and up to 0.30 mtr
(c)
Beyond 0.30 mtr. and up to 0.45 mtr.
(d)
Beyond 0.45 mtr
|
(a)
@Rs. 1000 per sq m.
(b)
@ Rs. 2000 per sq m
(c)
@ Rs. 5000 per sq m
(d)
Not permitted
|
|
(a)
End wall up to 0.45 mtr. As architectural feature
(b)
End wall beyond 45 cm up to 90 cm as architectural feature
(c)
End wall beyond 90 cm
|
(a)
No penalty (as provision is already there in the bylaws)
(b)
Rs. 5000 per wall at each floor
(c)
Not permitted
|
|
(a)
RCC Cub Board up to 0.60 mtr width in setback from ground level
(b)
Beyond 0.6 mtr
|
(a)
Rs. 2000 per sq m
(b)
Not permitted
|
|
Bay window
from ground level
(a)
Up to 0.60 mtr. Width from ground level
(b)
Beyond 0.60 mtr width in setback
|
(a)
Rs. 2000 per sq m
(b)
Not permitted
|
|
Boiler
with flue bhatties, electrical furnace and the like if uncovered and cooling
tower in the setback in case of industrial plot shall be permitted only if
the fire NOC is received from the Fire Department.
|
(a)
Rs. 1500 per sq m up to 10 sq m
(b)
Rs. 3000 per sq m next 10 sq m
(c)
Above 20 sq m not allowed
|
|
Cooling
tower in the setback of industrial plot
|
Rs.
500 per sq m for covered area
|
|
DG
stack in setback infringement shall only be allowed after clearance from fire
department
|
(a)
Rs. 1500 per sq m up to 20 sq m
(b)
Rs. 3000 per sq m next 20 sq m
(c)
Rs. 4500 per sq m next 20 sq m
(d)
Rs. 4500 per sq m next 40 sq m
(e)
Above 100 sq m not allowed
|
|
Increase
in building height beyond max permissible limit
(a)
Up to 30 cm
(b)
30 cm to 50 cm
(c)
50 cm to 1 mtr
(d)
beyond 1 meter
|
(a)
Rs. 1000 per sq m of area for which there is increase in building height
(b)
Rs. 2000 per sq m of area for which there is increase in building height
(c)
Rs. 5000 per sq m of area for which there is increase in building height
(d)
Not permitted of area for which there is increase in is building height
|
Table No. 8
DISTANCE BETWEEN TWO ADJACENT BUILDING BLOCKS
|
Sl.
No.
|
Height
of Building (in mtrs.) (1)
|
Side
and rear open space to be left around building (mt) (2)
|
|
i.
|
Up
to 18
|
6
|
|
ii.
|
Above
18 to 21
|
7
|
|
iii.
|
Above
21 to 24
|
8
|
|
iv.
|
Above
24 to 27
|
9
|
|
v.
|
Above
27 to 30
|
10
|
|
vi.
|
Above
30 to 35
|
11
|
|
vii.
|
Above
35 to 40
|
12
|
|
viii.
|
Above
40 to 45
|
13
|
|
ix.
|
Above
45 to 50
|
14
|
|
X.
|
Above
50 but less than 55
|
15
|
|
xi.
|
55
and above
|
16".
|